Honeywell MS-2 manual Combination Waterflow/Supervisory Zone

Page 21

Input Circuits

Installation

Combination Waterflow/Supervisory Zone

A combination Waterflow/Supervisory circuit allows an FACP to distinguish between an Alarm switch (waterflow device) and a Supervisory switch (tamper) installed on the same circuit. The following figure illustrates the wiring of Zone 2 as a Style B (Class

B)Waterflow/Supervisory circuit. Note that only Zone 1 on the MS-2 and Zone 2 on the MS-4 can be configured in this manner.

Class B Initiating Device Circuits (supervised and power-limited)

4.7 K, ½ watt resistor P/N:71252

Supervisory Switch (tamper)

Supervisory Switch (tamper)

In-Line-Resistor

1.2 KΩ, ½ watt resistor P/N: 75579

Alarm Switch (waterflow)

Dummy load all unused circuits - 4.7 K, ½ watt resistor (P/N: 71245)

TB3

Note: Zones 3 & 4

on MS-4 only

 

B+ B- B+ B- B+ B- B+ B-

ZONE 1 ZONE 2 ZONE 3 ZONE 4

ms-4zon1.cdr

Figure 2.5 Style B Combination Circuit on Zone 2 of the MS-4

Requirements for the Combination Waterflow/Supervisory circuit are as follows:

The Waterflow Alarm Switch(es) must connect to the FACP Initiating Device Circuit before the In-Line Resistor as shown in Figure 2.5

The Waterflow Supervisory Switch(es) must connect to the FACP Initiating Device Circuit after the In-Line Resistor as shown in Figure 2.5

Program the FACP Initiating Device Circuit #1 on the MS-2 or Circuit #2 on the MS-4 as a Combination circuit by placing SW1 DIP switch 8 to the ON position as described in "SW1 DIP Switch Settings" on page 34

Waterflow Alarm Switch activation causes the panel to latch into alarm until the alarm condition is cleared and the FACP is reset

Supervisory Switch activation causes the panel to track the supervisory condition, that is, the panel will clear when the supervisory condition is cleared (if FACP is programmed for Autoresettable Supervisory)

MS-2/MS-4 PN 51512:E 01/18/05

21

Image 21
Contents MS-2 & MS-4 MS-2E & MS-4E Fire Alarm System Limitations Installation Precautions MS-2/MS-4 PN 51512E 01/18/05 Table of Contents Operating Instructions Power Supply CalculationsUnderwriters Laboratories Documents for Reference OtherFireLite Documents MS-2E Main Circuit Board J8 Battery Connector Supervised, nonpower-limitedSupv. Relay TB7 2A @ 30 VAC nonsupervised MS-4E Main Circuit BoardProduct Description Product FeaturesProduct Features Product Description Specifications Controls and Indicators LED IndicatorsFront Panel Membrane Buttons Components CircuitsOptional Modules and Accessories 411UD Digital Alarm Communicator/Transmitter Battery BoxBackbox Mounting Backbox Mounting DimensionsBackbox and Battery Box Operating Power Primary Power Source AC and Earth Ground ConnectionsSecondary Power Source Batteries IDC Connections Input CircuitsStyle B Combination Circuit on Zone 2 of the MS-4 Combination Waterflow/Supervisory ZoneNotification Appliance Circuits Output CircuitsSpecial Application DC Power Output Connections Relays+ + Typical UL Power-limited Wiring Requirements Power-limited Wiring RequirementsInstallation Installation of Optional ModulesJ1 Connector CAC-4 Class a Converter Module MS-4 only11 Wiring NACs and IDCs for Class a Operation Wiring NACs and IDCs for Class a12 4X Option Module Connection to MS-4 2 4XTMF, 4XLMF and 4XZMF Option Modules13 4XTMF Transmitter Module 2.1 4XTMF Transmitter Module Installation14 4XZMF Zone Relay Module 2.2 4XZMF Zone Relay Module MS-4 only15 4XLMF LED Interface Module 2.3 4XLMF LED Interface Module MS-4 onlyProgram Options via DIP Switch MS-2 DIP Switch Settings DIP Switch SettingsMS-4 DIP Switch Settings 1 SW1 DIP Switch Settings 2.1 IDC1 Verification MS-4 only 2 SW2 DIP Switch Settings2.2 IDC1 Supervisory MS-4 only 2.4 IDC1 Supervisory for MS-2 or IDC2 Supervisory for MS-43 SW3 DIP Switch Settings Maximum Number of Strobes for Synchronization Strobe SynchronizationNonsilenceable Waterflow for Combination Circuit SparesZone Enable/Disable Switch Functions in Normal ModeReset/Lamp Test ACK AcknowledgeWalktest WalktestAudible Walktest Status LEDs Operation Fire Alarm Restoral Fire Alarm ResponseSystem Supervisory Condition Response System Supervisory Restoral ResponseTrouble Condition Restoral Trouble Condition Response1120 VAC Branch Circuit Requirements Power Supply Calculations2Converting to Full Amperes Calculating the System Current Draw3System Current Draw Calculations Calculating the System Current Draw4Total Secondary Power Requirements at 24 VDC Calculating the Battery SizeMS-2/MS-4 PN 51512E 01/18/05 Numerics IndexJP2 Fail-safeIndex Verification MS-2/MS-4 PN 51512E 01/18/05 MS-2/MS-4 PN 51512E 01/18/05 Limited Warranty

MS-2 specifications

The Honeywell MS-2 is a sophisticated control panel designed for fire alarm detection systems. It is renowned for its reliability, efficiency, and advanced features which make it a popular choice among industry professionals. The MS-2 is especially well-suited for small to medium-sized commercial buildings, providing comprehensive fire detection and alarm capabilities.

One of the standout features of the Honeywell MS-2 is its dual-loop architecture. This allows for the connection of two loop circuits, each capable of supporting a wide range of devices such as smoke detectors, heat detectors, and manual pull stations. This flexibility in device connectivity enables tailored solutions based on specific building requirements, ensuring maximum safety and compliance with fire codes.

The MS-2 incorporates a user-friendly graphical interface that simplifies operation and monitoring. This LCD display provides real-time system status updates, which allows users to quickly identify any issues or alarms. Moreover, it features intuitive navigation buttons, making it easy for operators to interact with system functionalities.

In terms of technology, the MS-2 is built upon a robust digital platform that ensures precise detection and response times. With advanced signal processing capabilities, the system can differentiate between actual fire signals and nuisance alarms, thereby minimizing false alarms. This not only enhances safety but also reduces unnecessary disruptions and maintenance costs.

The MS-2 also supports addressable technology, enabling precise identification of device locations within the system. This is particularly beneficial in emergency situations where rapid response is critical. Furthermore, the panel can facilitate remote monitoring, allowing for real-time data access and integration with building management systems, thereby enhancing overall operational efficiency.

Another noteworthy characteristic of the Honeywell MS-2 is its compliance with various industry standards, ensuring that it meets the stringent requirements of fire safety regulations. The system is compatible with a wide range of Honeywell's fire alarm devices, offering versatility and scalability for future expansions.

In conclusion, the Honeywell MS-2 fire alarm control panel combines advanced technology, user-friendly design, and robust features to deliver reliable fire safety solutions. Its dual-loop capability, addressable technology, and real-time monitoring make it an ideal choice for businesses aiming to enhance their fire safety infrastructure. By choosing the MS-2, organizations can better protect their assets, ensure compliance, and safeguard the lives of occupants.