Honeywell MS-2 Fire Alarm Response, Fire Alarm Restoral, System Supervisory Condition Response

Page 42

Operating Instructions

Operation

4.4.1 Fire Alarm Response

The control panel will, upon detection of an alarm condition, cause the following:

Latch the alarm condition - requires panel reset to clear alarm condition

Blink the Zone Alarm LED one second On and one second Off

Turn on remote annunciator alarm LED and piezo sounder

Turn the Notification Appliance Circuit(s) on

Turn the FACP piezo sounder on steady

Turn on the alarm relay

Start the Silence Inhibit, Auto-silence and Trouble Reminder functions if enabled

4.4.2 Fire Alarm Restoral

The control panel returns to normal after all alarms have been cleared and a system reset button has been pressed (pull stations have been reset, smoke detectors have reset and no smoke is present, waterflow has stopped). The control panel will perform the following upon restoral of all active alarms:

Turn off the FACP Zone Alarm LED

Turn off remote annunciator alarm LED and piezo sounder

Turn off the Notification Appliance Circuit(s)

Turn off the FACP piezo sounder

Turn off the alarm relay

I3 smoke detectors will be polled for maintenance and freeze conditions on initial entry into Normal mode. Thereafter, each device will be polled every hour for freeze and every four hours for maintenance conditions

4.4.3 System Supervisory Condition Response

Zones can be programmed for supervisory in applications where a waterflow sensing device has been employed and a sprinkler tamper switch is to be monitored. An I3 detector in a ‘freeze’ condition (detected abnormally low ambient temperature) will also generate a supervisory condition on its alarm zone (refer to the I3 specification sheet for temperature threshold). Any supervisory condition will cause the control panel to perform the following functions:

Blink the FACP Zone Supervisory LED ½ second On and ½ second Off

Pulse the piezo sounder ½ second On and ½ second Off

Turn on the supervisory relay (MS-4 only)

4.4.4 System Supervisory Restoral Response

When the supervisory condition has been cleared, the control panel will perform the following:

Turn off the FACP Zone Supervisory LED

Turn off the piezo sounder

Turn off the supervisory relay (MS-4 only)

42

MS-2/MS-4 PN 51512:E 01/18/05

Image 42
Contents MS-2 & MS-4 MS-2E & MS-4E Fire Alarm System Limitations Installation Precautions MS-2/MS-4 PN 51512E 01/18/05 Table of Contents Power Supply Calculations Operating InstructionsUnderwriters Laboratories Documents for Reference OtherFireLite Documents J8 Battery Connector Supervised, nonpower-limited MS-2E Main Circuit BoardMS-4E Main Circuit Board Supv. Relay TB7 2A @ 30 VAC nonsupervisedProduct Features Product DescriptionProduct Features Product Description Specifications Controls and Indicators LED IndicatorsFront Panel Membrane Buttons Circuits ComponentsOptional Modules and Accessories Battery Box 411UD Digital Alarm Communicator/TransmitterBackbox Mounting Dimensions Backbox MountingBackbox and Battery Box Operating Power Primary Power Source AC and Earth Ground ConnectionsSecondary Power Source Batteries Input Circuits IDC ConnectionsCombination Waterflow/Supervisory Zone Style B Combination Circuit on Zone 2 of the MS-4Output Circuits Notification Appliance CircuitsSpecial Application DC Power Output Connections Relays+ + Power-limited Wiring Requirements Typical UL Power-limited Wiring RequirementsJ1 Connector Installation of Optional ModulesInstallation CAC-4 Class a Converter Module MS-4 onlyWiring NACs and IDCs for Class a 11 Wiring NACs and IDCs for Class a Operation2 4XTMF, 4XLMF and 4XZMF Option Modules 12 4X Option Module Connection to MS-42.1 4XTMF Transmitter Module Installation 13 4XTMF Transmitter Module2.2 4XZMF Zone Relay Module MS-4 only 14 4XZMF Zone Relay Module2.3 4XLMF LED Interface Module MS-4 only 15 4XLMF LED Interface ModuleProgram Options via DIP Switch DIP Switch Settings MS-2 DIP Switch SettingsMS-4 DIP Switch Settings 1 SW1 DIP Switch Settings 2.2 IDC1 Supervisory MS-4 only 2 SW2 DIP Switch Settings2.1 IDC1 Verification MS-4 only 2.4 IDC1 Supervisory for MS-2 or IDC2 Supervisory for MS-43 SW3 DIP Switch Settings Nonsilenceable Waterflow for Combination Circuit Strobe SynchronizationMaximum Number of Strobes for Synchronization SparesReset/Lamp Test Switch Functions in Normal ModeZone Enable/Disable ACK AcknowledgeWalktest WalktestAudible Walktest Status LEDs Operation System Supervisory Condition Response Fire Alarm ResponseFire Alarm Restoral System Supervisory Restoral ResponseTrouble Condition Response Trouble Condition RestoralPower Supply Calculations 1120 VAC Branch Circuit RequirementsCalculating the System Current Draw 2Converting to Full AmperesCalculating the System Current Draw 3System Current Draw CalculationsCalculating the Battery Size 4Total Secondary Power Requirements at 24 VDCMS-2/MS-4 PN 51512E 01/18/05 Index NumericsFail-safe JP2Index Verification MS-2/MS-4 PN 51512E 01/18/05 MS-2/MS-4 PN 51512E 01/18/05 Limited Warranty

MS-2 specifications

The Honeywell MS-2 is a sophisticated control panel designed for fire alarm detection systems. It is renowned for its reliability, efficiency, and advanced features which make it a popular choice among industry professionals. The MS-2 is especially well-suited for small to medium-sized commercial buildings, providing comprehensive fire detection and alarm capabilities.

One of the standout features of the Honeywell MS-2 is its dual-loop architecture. This allows for the connection of two loop circuits, each capable of supporting a wide range of devices such as smoke detectors, heat detectors, and manual pull stations. This flexibility in device connectivity enables tailored solutions based on specific building requirements, ensuring maximum safety and compliance with fire codes.

The MS-2 incorporates a user-friendly graphical interface that simplifies operation and monitoring. This LCD display provides real-time system status updates, which allows users to quickly identify any issues or alarms. Moreover, it features intuitive navigation buttons, making it easy for operators to interact with system functionalities.

In terms of technology, the MS-2 is built upon a robust digital platform that ensures precise detection and response times. With advanced signal processing capabilities, the system can differentiate between actual fire signals and nuisance alarms, thereby minimizing false alarms. This not only enhances safety but also reduces unnecessary disruptions and maintenance costs.

The MS-2 also supports addressable technology, enabling precise identification of device locations within the system. This is particularly beneficial in emergency situations where rapid response is critical. Furthermore, the panel can facilitate remote monitoring, allowing for real-time data access and integration with building management systems, thereby enhancing overall operational efficiency.

Another noteworthy characteristic of the Honeywell MS-2 is its compliance with various industry standards, ensuring that it meets the stringent requirements of fire safety regulations. The system is compatible with a wide range of Honeywell's fire alarm devices, offering versatility and scalability for future expansions.

In conclusion, the Honeywell MS-2 fire alarm control panel combines advanced technology, user-friendly design, and robust features to deliver reliable fire safety solutions. Its dual-loop capability, addressable technology, and real-time monitoring make it an ideal choice for businesses aiming to enhance their fire safety infrastructure. By choosing the MS-2, organizations can better protect their assets, ensure compliance, and safeguard the lives of occupants.