Honeywell MS-2 manual Wiring NACs and IDCs for Class a Operation

Page 26

Installation

Installation of Optional Modules

2.6.1.2 Wiring NACs and IDCs for Class A

Wire the Style Z (Class A) Notification Appliance Circuits using TB2 of the MS-4 and TB1 of the CAC-4 module. Wire the Style D (Class A) Initiating Device Circuits using TB3 of the MS-4 and TB1 of the CAC-4. Make certain to observe polarity when connecting the devices to the circuits. The B+ and A+ terminals must comprise the feed and return for the positive side of a device and the B- and A- terminals must comprise the feed and return for the negative side of a device. To configure any of the zones for Class B when the CAC-4 is installed, simply wire to the B+ and B- input on the FACP terminal(s) and install the End-of-Line Resistor after the last device on the circuit. Do not wire to the corresponding A+ and A- terminals on the CAC-4 module. Note that Zone 1 IDC on the MS-2 and Zone 2 IDC on the MS-4 can be configured as a combination waterflow/supervisory circuit as illustrated in the following figure.

Class B (Style B)

IMPORTANT!

Class A

 

IDC - 4.7 K

All devices must be

(Style D) IDC

 

½ watt ELR

within 20 feet of the

Combo Waterflow

 

resistor

Class A portion of

& Supervisory

 

P/N:71252

the circuit and

20KΩ, ½ watt ELR

Class A

(supervised and

wiring must be in

resistor P/N:75477

(Style D) IDC

power-limited)

conduit.

(supervised and

(supervised and

 

 

power-limited)

power-limited)

Class A (Style Z) NAC

 

 

Tamper

 

 

(supervised and power-limited)

 

Smoke

 

 

Smoke

 

Polarized

 

 

 

 

 

Bell

 

 

 

 

 

 

 

 

 

 

 

 

Tamper

 

 

Polarized

 

 

 

 

 

 

 

Strobe

 

 

Pull Station

 

Pull Station

 

 

 

 

 

 

 

 

 

 

 

 

Polarized

 

 

 

 

 

 

 

Horn

1.2 K

 

 

 

 

 

 

 

 

 

 

 

 

½ watt

Heat

Waterflow

 

 

 

In-Line

Heat

 

 

 

 

 

 

 

 

 

 

resistor

 

 

 

 

 

 

P/N:75579

 

 

 

 

 

 

 

 

 

 

 

 

Dummy load all unused

Circuit polarities

 

 

 

 

 

 

circuits - 4.7 K

 

 

 

 

 

 

½ watt ELR resistor

shown in alarm

 

 

 

 

 

 

(P/N: 71245)

condition

 

 

 

 

 

 

 

TB2

 

TB3

 

 

 

MS-4

 

 

 

 

Circuit Board

B+ B-

B+

B-

B+ B- B+ B-

B+ B- B+ B-

NAC 1

NAC

ZONE 1 ZONE

ZONE 3 ZONE

TB1

 

 

 

 

 

 

 

A+

A-

A+

A- A+ A- A+ A-

A+ A- A+ A-

CLASS A CLASS A CLASS A CLASS A

CLASS A CLASS A

NAC 1

NAC 2

ZONE 1

ZONE 2

ZONE 3

ZONE 4

 

CAC-4 Class A Converter Module

ms4comba.cdr

 

 

 

 

 

 

 

Figure 2.11 Wiring NACs and IDCs for Class A Operation

26

MS-2/MS-4 PN 51512:E 01/18/05

Image 26
Contents MS-2 & MS-4 MS-2E & MS-4E Fire Alarm System Limitations Installation Precautions MS-2/MS-4 PN 51512E 01/18/05 Table of Contents Power Supply Calculations Operating InstructionsFireLite Documents Underwriters Laboratories Documents for ReferenceOther J8 Battery Connector Supervised, nonpower-limited MS-2E Main Circuit BoardMS-4E Main Circuit Board Supv. Relay TB7 2A @ 30 VAC nonsupervisedProduct Features Product DescriptionProduct Features Product Description Specifications Front Panel Membrane Buttons Controls and IndicatorsLED Indicators Circuits ComponentsOptional Modules and Accessories Battery Box 411UD Digital Alarm Communicator/TransmitterBackbox Mounting Dimensions Backbox MountingBackbox and Battery Box Secondary Power Source Batteries Operating PowerPrimary Power Source AC and Earth Ground Connections Input Circuits IDC ConnectionsCombination Waterflow/Supervisory Zone Style B Combination Circuit on Zone 2 of the MS-4Output Circuits Notification Appliance Circuits+ + Special Application DC Power Output ConnectionsRelays Power-limited Wiring Requirements Typical UL Power-limited Wiring RequirementsJ1 Connector Installation of Optional ModulesInstallation CAC-4 Class a Converter Module MS-4 onlyWiring NACs and IDCs for Class a 11 Wiring NACs and IDCs for Class a Operation2 4XTMF, 4XLMF and 4XZMF Option Modules 12 4X Option Module Connection to MS-42.1 4XTMF Transmitter Module Installation 13 4XTMF Transmitter Module2.2 4XZMF Zone Relay Module MS-4 only 14 4XZMF Zone Relay Module2.3 4XLMF LED Interface Module MS-4 only 15 4XLMF LED Interface ModuleProgram Options via DIP Switch DIP Switch Settings MS-2 DIP Switch SettingsMS-4 DIP Switch Settings 1 SW1 DIP Switch Settings 2.2 IDC1 Supervisory MS-4 only 2 SW2 DIP Switch Settings2.1 IDC1 Verification MS-4 only 2.4 IDC1 Supervisory for MS-2 or IDC2 Supervisory for MS-43 SW3 DIP Switch Settings Nonsilenceable Waterflow for Combination Circuit Strobe SynchronizationMaximum Number of Strobes for Synchronization SparesReset/Lamp Test Switch Functions in Normal ModeZone Enable/Disable ACK AcknowledgeAudible Walktest WalktestWalktest Status LEDs Operation System Supervisory Condition Response Fire Alarm ResponseFire Alarm Restoral System Supervisory Restoral ResponseTrouble Condition Response Trouble Condition RestoralPower Supply Calculations 1120 VAC Branch Circuit RequirementsCalculating the System Current Draw 2Converting to Full AmperesCalculating the System Current Draw 3System Current Draw CalculationsCalculating the Battery Size 4Total Secondary Power Requirements at 24 VDCMS-2/MS-4 PN 51512E 01/18/05 Index NumericsFail-safe JP2Index Verification MS-2/MS-4 PN 51512E 01/18/05 MS-2/MS-4 PN 51512E 01/18/05 Limited Warranty

MS-2 specifications

The Honeywell MS-2 is a sophisticated control panel designed for fire alarm detection systems. It is renowned for its reliability, efficiency, and advanced features which make it a popular choice among industry professionals. The MS-2 is especially well-suited for small to medium-sized commercial buildings, providing comprehensive fire detection and alarm capabilities.

One of the standout features of the Honeywell MS-2 is its dual-loop architecture. This allows for the connection of two loop circuits, each capable of supporting a wide range of devices such as smoke detectors, heat detectors, and manual pull stations. This flexibility in device connectivity enables tailored solutions based on specific building requirements, ensuring maximum safety and compliance with fire codes.

The MS-2 incorporates a user-friendly graphical interface that simplifies operation and monitoring. This LCD display provides real-time system status updates, which allows users to quickly identify any issues or alarms. Moreover, it features intuitive navigation buttons, making it easy for operators to interact with system functionalities.

In terms of technology, the MS-2 is built upon a robust digital platform that ensures precise detection and response times. With advanced signal processing capabilities, the system can differentiate between actual fire signals and nuisance alarms, thereby minimizing false alarms. This not only enhances safety but also reduces unnecessary disruptions and maintenance costs.

The MS-2 also supports addressable technology, enabling precise identification of device locations within the system. This is particularly beneficial in emergency situations where rapid response is critical. Furthermore, the panel can facilitate remote monitoring, allowing for real-time data access and integration with building management systems, thereby enhancing overall operational efficiency.

Another noteworthy characteristic of the Honeywell MS-2 is its compliance with various industry standards, ensuring that it meets the stringent requirements of fire safety regulations. The system is compatible with a wide range of Honeywell's fire alarm devices, offering versatility and scalability for future expansions.

In conclusion, the Honeywell MS-2 fire alarm control panel combines advanced technology, user-friendly design, and robust features to deliver reliable fire safety solutions. Its dual-loop capability, addressable technology, and real-time monitoring make it an ideal choice for businesses aiming to enhance their fire safety infrastructure. By choosing the MS-2, organizations can better protect their assets, ensure compliance, and safeguard the lives of occupants.