Honeywell MS-2 manual Calculating the Battery Size, 4Total Secondary Power Requirements at 24 VDC

Page 47

Calculating the Battery Size

Power Supply Calculations

5.4Calculating the Battery Size

Use Table 5-4 to calculate the total Standby and Alarm load in ampere hours (AH). This total load determines the battery size (in AH), required to support the control panel under the loss of AC power. Complete Table 5-4 as follows:

1.Enter the totals from Table 5-3 on page 46, Calculation Columns 2 and 3 where shown

2.Enter the NFPA Standby and Alarm times (refer to ‘NFPA Requirements’ below)

3.Calculate the ampere hours for Standby and Alarm, then sum the Standby and Alarm ampere hours

4.Multiply the sum by the derating factor of 1.2 to calculate the proper battery size (in AH)

5.Write the ampere hour requirements on the Protected Premises label located inside the cabinet door

TABLE 5-4:Total Secondary Power Requirements at 24 VDC

Secondary Standby Load

Required Standby Time

 

 

(total from Table 5-3 Calculation

(24 or 60 hours)

 

 

Column 3)

 

 

 

 

 

[

]

X[

]

=

AH

 

 

 

 

Primary Alarm Load

Required Alarm Time

 

 

(total from Table 5-3 Calculation

(for 5 min., enter 0.084,

 

 

Column 2)

 

for 10 min., enter 0.168)

 

 

[

]

X[

]

=

AH

 

 

 

 

 

Sum of Standby and Alarm Ampere Hours

 

=

AH

 

 

 

 

 

Multiply by the Derating Factor

 

 

X 1.2

 

 

 

 

 

Battery Size, Total Ampere Hours Required

 

=

AH

 

 

 

 

 

 

5.4.1 NFPA Battery Requirements

NFPA 72 Local, Central and Proprietary Fire Alarm Systems require 24 hours of standby power followed by 5 minutes in alarm

NFPA 72 Auxiliary and Remote Station require 60 hours of standby followed by 5 minutes in alarm. Batteries installed in a system powered by a generator need to provide at least 4 hours of standby power

5.4.2 Selecting and Locating Batteries

Select batteries that meet or exceed the total ampere hours calculated in Table 5-4 . The control panel can charge batteries in the 7 AH to 18 AH range. The control panel cabi- net is capable of housing batteries up to 7 AH. Batteries larger than 7 AH require the BB-17F or other UL listed external battery cabinet.

MS-2/MS-4 PN 51512:E 01/18/05

47

Image 47
Contents MS-2 & MS-4 MS-2E & MS-4E Fire Alarm System Limitations Installation Precautions MS-2/MS-4 PN 51512E 01/18/05 Table of Contents Operating Instructions Power Supply CalculationsFireLite Documents Underwriters Laboratories Documents for ReferenceOther MS-2E Main Circuit Board J8 Battery Connector Supervised, nonpower-limitedSupv. Relay TB7 2A @ 30 VAC nonsupervised MS-4E Main Circuit BoardProduct Description Product FeaturesProduct Features Product Description Specifications Front Panel Membrane Buttons Controls and IndicatorsLED Indicators Components CircuitsOptional Modules and Accessories 411UD Digital Alarm Communicator/Transmitter Battery BoxBackbox Mounting Backbox Mounting DimensionsBackbox and Battery Box Secondary Power Source Batteries Operating PowerPrimary Power Source AC and Earth Ground Connections IDC Connections Input CircuitsStyle B Combination Circuit on Zone 2 of the MS-4 Combination Waterflow/Supervisory ZoneNotification Appliance Circuits Output Circuits+ + Special Application DC Power Output ConnectionsRelays Typical UL Power-limited Wiring Requirements Power-limited Wiring RequirementsCAC-4 Class a Converter Module MS-4 only Installation of Optional ModulesInstallation J1 Connector11 Wiring NACs and IDCs for Class a Operation Wiring NACs and IDCs for Class a12 4X Option Module Connection to MS-4 2 4XTMF, 4XLMF and 4XZMF Option Modules13 4XTMF Transmitter Module 2.1 4XTMF Transmitter Module Installation14 4XZMF Zone Relay Module 2.2 4XZMF Zone Relay Module MS-4 only15 4XLMF LED Interface Module 2.3 4XLMF LED Interface Module MS-4 onlyProgram Options via DIP Switch MS-2 DIP Switch Settings DIP Switch SettingsMS-4 DIP Switch Settings 1 SW1 DIP Switch Settings 2.4 IDC1 Supervisory for MS-2 or IDC2 Supervisory for MS-4 2 SW2 DIP Switch Settings2.1 IDC1 Verification MS-4 only 2.2 IDC1 Supervisory MS-4 only3 SW3 DIP Switch Settings Spares Strobe SynchronizationMaximum Number of Strobes for Synchronization Nonsilenceable Waterflow for Combination CircuitACK Acknowledge Switch Functions in Normal ModeZone Enable/Disable Reset/Lamp TestAudible Walktest WalktestWalktest Status LEDs Operation System Supervisory Restoral Response Fire Alarm ResponseFire Alarm Restoral System Supervisory Condition ResponseTrouble Condition Restoral Trouble Condition Response1120 VAC Branch Circuit Requirements Power Supply Calculations2Converting to Full Amperes Calculating the System Current Draw3System Current Draw Calculations Calculating the System Current Draw4Total Secondary Power Requirements at 24 VDC Calculating the Battery SizeMS-2/MS-4 PN 51512E 01/18/05 Numerics IndexJP2 Fail-safeIndex Verification MS-2/MS-4 PN 51512E 01/18/05 MS-2/MS-4 PN 51512E 01/18/05 Limited Warranty

MS-2 specifications

The Honeywell MS-2 is a sophisticated control panel designed for fire alarm detection systems. It is renowned for its reliability, efficiency, and advanced features which make it a popular choice among industry professionals. The MS-2 is especially well-suited for small to medium-sized commercial buildings, providing comprehensive fire detection and alarm capabilities.

One of the standout features of the Honeywell MS-2 is its dual-loop architecture. This allows for the connection of two loop circuits, each capable of supporting a wide range of devices such as smoke detectors, heat detectors, and manual pull stations. This flexibility in device connectivity enables tailored solutions based on specific building requirements, ensuring maximum safety and compliance with fire codes.

The MS-2 incorporates a user-friendly graphical interface that simplifies operation and monitoring. This LCD display provides real-time system status updates, which allows users to quickly identify any issues or alarms. Moreover, it features intuitive navigation buttons, making it easy for operators to interact with system functionalities.

In terms of technology, the MS-2 is built upon a robust digital platform that ensures precise detection and response times. With advanced signal processing capabilities, the system can differentiate between actual fire signals and nuisance alarms, thereby minimizing false alarms. This not only enhances safety but also reduces unnecessary disruptions and maintenance costs.

The MS-2 also supports addressable technology, enabling precise identification of device locations within the system. This is particularly beneficial in emergency situations where rapid response is critical. Furthermore, the panel can facilitate remote monitoring, allowing for real-time data access and integration with building management systems, thereby enhancing overall operational efficiency.

Another noteworthy characteristic of the Honeywell MS-2 is its compliance with various industry standards, ensuring that it meets the stringent requirements of fire safety regulations. The system is compatible with a wide range of Honeywell's fire alarm devices, offering versatility and scalability for future expansions.

In conclusion, the Honeywell MS-2 fire alarm control panel combines advanced technology, user-friendly design, and robust features to deliver reliable fire safety solutions. Its dual-loop capability, addressable technology, and real-time monitoring make it an ideal choice for businesses aiming to enhance their fire safety infrastructure. By choosing the MS-2, organizations can better protect their assets, ensure compliance, and safeguard the lives of occupants.