Honeywell MS-2 manual Audible Walktest

Page 39

Walktest

Operating Instructions

4.1.5 Walktest

The Walktest button, which is located on the FACP membrane switch panel, allows a panel walktest to be performed. Pressing and holding the Walktest button for a minimum of two seconds causes the FACP to enter audible walktest. Pressing the Walktest button and then the Silence button and holding both for a minimum of two seconds will cause the panel to enter silent walktest. Walktest can be exited by pressing and holding the Walktest button for a minimum of three seconds or by pressing the Reset button. Refer to “Walktest” for a complete description of this feature.

4.2 Walktest

!

Walktest allows the testing of all control panel IDCs (input zones). An audible or silent walktest may be performed.

It is important to note that while the FACP is in Walktest mode, the control panel is in an off-normal condition and does not provide fire protection.

It should also be noted that the trouble relay will be activated while the control panel is in Walktest mode. Placing the control panel into Walktest mode will only be possible if the system has no active alarms.

Prior to initiating a walktest, check to make certain that all system faults have been cleared. Upon entering Walktest mode, the following conditions should occur:

Trouble relay will activate

Alarm relay will be disabled

Supervision relay will be disabled (MS-4 only)

Piezo sounder will be disabled

I3 smoke detectors will enter their own test mode causing their LEDs to flash twice every five seconds (refer to the I3 specification document)

All alarm conditions will be displayed as they occur by blinking zone alarm LED

All zone troubles will be displayed as they occur by blinking zone trouble LED

During walktest, the FACP zone LEDs will blink for the first activation on a zone. Subsequent activations on the same zone will cause the corresponding zone LED to blink the number of alarms on the zone since the start of the test, followed by a two second pause and then a repeat of the sequence.

Note that following a zone activation, a 6 second reset for conventional and 60 second reset for I3 detectors is initiated. No new alarms or troubles will be detected during this reset period.

Disabled zones will not respond during Walktest. A zone may be disabled while in Walktest mode, should a faulty device be detected. This allows the user to return the system to Normal mode, enabling all other zones while preventing the faulty zone from triggering a false alarm.

Audible Walktest

To perform an audible Walktest, press and hold the Walktest button for a minimum of two seconds. The Trouble and Walktest LEDs will blink at a ¼ second rate.

While testing input devices, the first initiating device activated on a zone will cause the NACs to sound for four seconds. Subsequent device activations on the same zone will cause the NACs to turn on for one second. Any smoke detectors that are activated will automatically be reset by the panel. Zone faults (open circuits) will cause the NACs to remain on steadily until the fault is cleared.

During an audible walktest, if a device remains latched in alarm (such as a Pull Station that is not reset after activation), subsequent testing of devices on the same zone will not trigger the NACs. Be certain to reset or clear each device after testing.

MS-2/MS-4 PN 51512:E 01/18/05

39

Image 39
Contents MS-2 & MS-4 MS-2E & MS-4E Fire Alarm System Limitations Installation Precautions MS-2/MS-4 PN 51512E 01/18/05 Table of Contents Operating Instructions Power Supply CalculationsUnderwriters Laboratories Documents for Reference OtherFireLite Documents MS-2E Main Circuit Board J8 Battery Connector Supervised, nonpower-limitedSupv. Relay TB7 2A @ 30 VAC nonsupervised MS-4E Main Circuit BoardProduct Description Product FeaturesProduct Features Product Description Specifications Controls and Indicators LED IndicatorsFront Panel Membrane Buttons Components CircuitsOptional Modules and Accessories 411UD Digital Alarm Communicator/Transmitter Battery BoxBackbox Mounting Backbox Mounting DimensionsBackbox and Battery Box Operating Power Primary Power Source AC and Earth Ground ConnectionsSecondary Power Source Batteries IDC Connections Input CircuitsStyle B Combination Circuit on Zone 2 of the MS-4 Combination Waterflow/Supervisory ZoneNotification Appliance Circuits Output CircuitsSpecial Application DC Power Output Connections Relays+ + Typical UL Power-limited Wiring Requirements Power-limited Wiring RequirementsCAC-4 Class a Converter Module MS-4 only Installation of Optional ModulesInstallation J1 Connector11 Wiring NACs and IDCs for Class a Operation Wiring NACs and IDCs for Class a12 4X Option Module Connection to MS-4 2 4XTMF, 4XLMF and 4XZMF Option Modules13 4XTMF Transmitter Module 2.1 4XTMF Transmitter Module Installation14 4XZMF Zone Relay Module 2.2 4XZMF Zone Relay Module MS-4 only15 4XLMF LED Interface Module 2.3 4XLMF LED Interface Module MS-4 onlyProgram Options via DIP Switch MS-2 DIP Switch Settings DIP Switch SettingsMS-4 DIP Switch Settings 1 SW1 DIP Switch Settings 2.4 IDC1 Supervisory for MS-2 or IDC2 Supervisory for MS-4 2 SW2 DIP Switch Settings2.1 IDC1 Verification MS-4 only 2.2 IDC1 Supervisory MS-4 only3 SW3 DIP Switch Settings Spares Strobe SynchronizationMaximum Number of Strobes for Synchronization Nonsilenceable Waterflow for Combination CircuitACK Acknowledge Switch Functions in Normal ModeZone Enable/Disable Reset/Lamp TestWalktest WalktestAudible Walktest Status LEDs Operation System Supervisory Restoral Response Fire Alarm ResponseFire Alarm Restoral System Supervisory Condition ResponseTrouble Condition Restoral Trouble Condition Response1120 VAC Branch Circuit Requirements Power Supply Calculations2Converting to Full Amperes Calculating the System Current Draw3System Current Draw Calculations Calculating the System Current Draw4Total Secondary Power Requirements at 24 VDC Calculating the Battery SizeMS-2/MS-4 PN 51512E 01/18/05 Numerics IndexJP2 Fail-safeIndex Verification MS-2/MS-4 PN 51512E 01/18/05 MS-2/MS-4 PN 51512E 01/18/05 Limited Warranty

MS-2 specifications

The Honeywell MS-2 is a sophisticated control panel designed for fire alarm detection systems. It is renowned for its reliability, efficiency, and advanced features which make it a popular choice among industry professionals. The MS-2 is especially well-suited for small to medium-sized commercial buildings, providing comprehensive fire detection and alarm capabilities.

One of the standout features of the Honeywell MS-2 is its dual-loop architecture. This allows for the connection of two loop circuits, each capable of supporting a wide range of devices such as smoke detectors, heat detectors, and manual pull stations. This flexibility in device connectivity enables tailored solutions based on specific building requirements, ensuring maximum safety and compliance with fire codes.

The MS-2 incorporates a user-friendly graphical interface that simplifies operation and monitoring. This LCD display provides real-time system status updates, which allows users to quickly identify any issues or alarms. Moreover, it features intuitive navigation buttons, making it easy for operators to interact with system functionalities.

In terms of technology, the MS-2 is built upon a robust digital platform that ensures precise detection and response times. With advanced signal processing capabilities, the system can differentiate between actual fire signals and nuisance alarms, thereby minimizing false alarms. This not only enhances safety but also reduces unnecessary disruptions and maintenance costs.

The MS-2 also supports addressable technology, enabling precise identification of device locations within the system. This is particularly beneficial in emergency situations where rapid response is critical. Furthermore, the panel can facilitate remote monitoring, allowing for real-time data access and integration with building management systems, thereby enhancing overall operational efficiency.

Another noteworthy characteristic of the Honeywell MS-2 is its compliance with various industry standards, ensuring that it meets the stringent requirements of fire safety regulations. The system is compatible with a wide range of Honeywell's fire alarm devices, offering versatility and scalability for future expansions.

In conclusion, the Honeywell MS-2 fire alarm control panel combines advanced technology, user-friendly design, and robust features to deliver reliable fire safety solutions. Its dual-loop capability, addressable technology, and real-time monitoring make it an ideal choice for businesses aiming to enhance their fire safety infrastructure. By choosing the MS-2, organizations can better protect their assets, ensure compliance, and safeguard the lives of occupants.