Bosch Appliances FPA-1000 Parts Included, Technical Specifications, Electrical, Environmental

Page 4

4 FPA1000 Analog Addressable Fire Panels

use these devices on addresses above 127 and other devices below address 127. All compatible detectors and modules are addressed using the D5070 Programmer.

Parts Included

Quant. Component

1FPA1000V2 main board

1Enclosure with transformer

1Enclosure lock and two keys1 (replacement key: D102)

1Hardware pack

3Wiring labels (one each in English, Spanish, and Portuguese)

22.21 kΩ EOL resistors (replacement resistors: EOL2.2K, 8 per package)

Tabs with different language versions for LED and key text Literature (in English, Spanish, and Portuguese)

Installation and Operation Guide

Operating Instruction Sheet

Release Notes

1Key code stamped on both lock and key

Technical Specifications

Electrical

Power supply (primary)

Current:

120 VAC: 2 A maximum

 

 

240 VAC: 1 A maximum

 

 

 

Voltage:

120 VAC, 60 Hz or 240 VAC, 50 Hz

 

 

Power supply (secondary)

 

 

 

 

Current (alarm):

• Panel < 0.240 A

 

 

• SLC = 0.63 A maximum

Current (load):

Standby: < 1.25 A

 

 

Alarm: 4 A Shared maximum

 

 

• NAC 1 = 2.5 A maximum

 

 

• NAC 2 = 2.5 A maximum

 

 

• AUX/FWR = 0.5 A maximum

 

 

• AUX/RST = 0.5 A maximum

 

 

• Option bus = 0.5 A maximum

Voltage:

24 VDC

 

 

Batteries

 

 

 

 

Voltage:

2 x 12 VDC in series

 

 

 

Capacities:

maximum 40 Ah

 

 

• in cabinet: 7 Ah to 18 Ah

 

 

• in additional battery box: 24 Ah

 

 

to 40 Ah

Fuses:

15 A blade type

 

 

 

Auxiliary power supply (AUX)

• AUX/FWR:

0.5 A at 24 V FWR

 

 

Nonswitched, powerlimited, unfiltered,

 

 

unsupervised

AUX/RST:

0.5 A at 24 VDC

 

 

Switched, powerlimited, filtered,

 

 

unsupervised

Environmental

 

 

 

Environment:

Indoor, dry

 

 

Protection Class:

IP 30

 

 

Relative Humidity:

Up to 95%, non-condensing

 

 

Temperature (operating):

+32°F to +120°F (0°C to +49°C)

 

 

Temperature (storage):

+14°F to +131°F (-10°C to +55°C)

 

 

Mechanical

 

 

 

Operating Elements

 

 

 

 

LCD:

4line x 20character display, backlit

 

 

 

LEDs:

Six total: Fire, Gas Alarm, Power,

 

 

Supervisory, Silenced, and Trouble

Operation Keys:

Drill, Reset, Silence, and Acknowledge

 

 

 

Alphanumeric

12 alphanumeric keys, escape, enter,

 

Keypad:

and navigation buttons (left, right, up,

 

 

down)

Interfaces

 

 

 

 

PSTN/DACT:

2 lines, RJ45

 

 

 

Ethernet:

1 x RJ45

 

 

Peer-to-peer

Each interconnected panel requires one

 

communication:

of the following:

 

 

• FPE1000NE Networking Card

 

 

3Ethermet

 

 

• FPE1000NF Networking Card

 

 

1Ethernet 2Fiber Optic

 

 

• FPE1000NW Networking Card

 

 

1Ethernet 2Wired

 

 

 

Network Connections

Ethernet:

minimum of CAT 5 cable at a maximum

 

 

length of 328 ft (100 m)

 

 

 

Fiber Optics:

multi-mode fiber optic cable (62.5 μm/

 

 

125 μm fiber size; 1270 nm to 1380 nm

 

 

wavelength) with LC connectors at a

 

 

maximum length of 6560 ft (2000 m or a

 

 

10 db loss, whichever occurs first)

Wired:

12 AWG (2.05 mm) to 26 AWG

 

 

(0.41 mm) twisted pair wire (shielded or

 

 

unshielded) at a maximum length of

 

 

2952 ft (900 m) or CAT 5 cable or better

 

 

at a maximum length of 3280 ft

 

 

(1000 m)

 

 

 

Wiring

• Cable Entries:

Triple knock-outs (3/4, 1/2, 1 in)

 

 

Image 4
Contents FPA‑1000 Analog Addressable Fire Panels System Overview Functions Installation/Configuration Notes Certifications and ApprovalsTechnical Specifications Parts IncludedElectrical EnvironmentalOrdering Information Carbon monoxide detector Enclosure with dead front door Order number FPP-RNAC-8A-4C