4 FPA‑1000 Analog Addressable Fire Panels
use these devices on addresses above 127 and other devices below address 127. All compatible detectors and modules are addressed using the D5070 Programmer.
Parts Included
Quant. Component
1FPA‑1000‑V2 main board
1Enclosure with transformer
1Enclosure lock and two keys1 (replacement key: D102)
1Hardware pack
3Wiring labels (one each in English, Spanish, and Portuguese)
22.21 kΩ EOL resistors (replacement resistors: EOL‑2.2K, 8 per package)
Tabs with different language versions for LED and key text Literature (in English, Spanish, and Portuguese)
•Installation and Operation Guide
•Operating Instruction Sheet
•Release Notes
1Key code stamped on both lock and key
Technical Specifications
Electrical
Power supply (primary)
• | Current: | 120 VAC: 2 A maximum |
|
| 240 VAC: 1 A maximum |
|
|
|
• | Voltage: | 120 VAC, 60 Hz or 240 VAC, 50 Hz |
|
| |
Power supply (secondary) |
| |
|
|
|
• | Current (alarm): | • Panel < 0.240 A |
|
| • SLC = 0.63 A maximum |
• | Current (load): | Standby: < 1.25 A |
|
| Alarm: 4 A Shared maximum |
|
| • NAC 1 = 2.5 A maximum |
|
| • NAC 2 = 2.5 A maximum |
|
| • AUX/FWR = 0.5 A maximum |
|
| • AUX/RST = 0.5 A maximum |
|
| • Option bus = 0.5 A maximum |
• | Voltage: | 24 VDC |
|
| |
Batteries |
| |
|
|
|
• | Voltage: | 2 x 12 VDC in series |
|
|
|
• | Capacities: | maximum 40 Ah |
|
| • in cabinet: 7 Ah to 18 Ah |
|
| • in additional battery box: 24 Ah |
|
| to 40 Ah |
• | Fuses: | 15 A blade type |
|
|
|
Auxiliary power supply (AUX)
• AUX/FWR: | 0.5 A at 24 V FWR |
|
| Non‑switched, power‑limited, unfiltered, |
|
| unsupervised |
• | AUX/RST: | 0.5 A at 24 VDC |
|
| Switched, power‑limited, filtered, |
|
| unsupervised |
Environmental |
| |
|
| |
Environment: | Indoor, dry | |
|
| |
Protection Class: | IP 30 | |
|
| |
Relative Humidity: | Up to 95%, | |
|
| |
Temperature (operating): | +32°F to +120°F (0°C to +49°C) | |
|
| |
Temperature (storage): | +14°F to +131°F | |
|
| |
Mechanical |
| |
|
| |
Operating Elements |
| |
|
|
|
• | LCD: | 4‑line x 20‑character display, backlit |
|
|
|
• | LEDs: | Six total: Fire, Gas Alarm, Power, |
|
| Supervisory, Silenced, and Trouble |
• | Operation Keys: | Drill, Reset, Silence, and Acknowledge |
|
|
|
• | Alphanumeric | 12 alphanumeric keys, escape, enter, |
| Keypad: | and navigation buttons (left, right, up, |
|
| down) |
Interfaces |
| |
|
|
|
• | PSTN/DACT: | 2 lines, RJ45 |
|
|
|
• | Ethernet: | 1 x RJ45 |
|
| |
• | Each interconnected panel requires one | |
| communication: | of the following: |
|
| • FPE‑1000‑NE Networking Card |
|
| 3‑Ethermet |
|
| • FPE‑1000‑NF Networking Card |
|
| 1‑Ethernet 2‑Fiber Optic |
|
| • FPE‑1000‑NW Networking Card |
|
| 1‑Ethernet 2‑Wired |
|
|
|
Network Connections
• | Ethernet: | minimum of CAT 5 cable at a maximum |
|
| length of 328 ft (100 m) |
|
|
|
• | Fiber Optics: | |
|
| 125 μm fiber size; 1270 nm to 1380 nm |
|
| wavelength) with LC connectors at a |
|
| maximum length of 6560 ft (2000 m or a |
|
| 10 db loss, whichever occurs first) |
• | Wired: | 12 AWG (2.05 mm) to 26 AWG |
|
| (0.41 mm) twisted pair wire (shielded or |
|
| unshielded) at a maximum length of |
|
| 2952 ft (900 m) or CAT 5 cable or better |
|
| at a maximum length of 3280 ft |
|
| (1000 m) |
|
|
|
Wiring
• Cable Entries: | Triple |
|
|