Hearth and Home Technologies BCBV36I owner manual Negative Pressure

Page 16

E. Negative Pressure

WARNING! Asphyxiation Risk! Negative pressure can cause spillage of combustion fumes and soot. Fireplace needs to draft properly for safety.

Draft is the pressure difference needed to vent fireplaces successfully. Considerations for successful draft include:

Preventing negative pressure

Location of fireplace and chimney

Negative pressure results from the imbalance of air available for the fireplace to operate properly. Causes for this imbalance include:

Exhaust fans (kitchen, bath, etc.)

Range hoods

Combustion air requirements for furnaces, water heaters and other combustion appliances

Clothes dryers

Location of return-air to furnace or air conditioning

Imbalances of the HVAC air handling system

Upper level air leaks (recessed lighting, attic hatch opening, duct leaks)

To minimize the effects of negative air pressure, the fol- lowing must be considered:

Install the fresh air kit. Install the intake on the side of the house towards prevailing winds during the heating season.

Ensure adequate outdoor air is supplied for combustion appliances and exhaust equipment.

Ensure furnace and air conditioning return vents are not located in the immediate vicinity of the fireplace.

Avoid installing the fireplace near doors, walkways or small isolated spaces.

Recessed lighting should be of “sealed can” design; attic hatches weather stripped or sealed; and attic mounted ductwork and air handler joints and seams taped or sealed.

Basement installations should be avoided due to stack effect. Stack effect creates negative pressure in lower levels. Hearth & Home Technologies recommends the use of direct vent fireplaces in basements.

Location of the fireplace and chimney will affect perfor- mance. As shown in Figure 4.2, the chimney should:

Be installed through the warm space enclosed by the building envelope. This helps to produce more draft, especially during lighting and die-down of the fire.

Penetrate the highest part of the roof. This minimizes the effects of wind turbulence.

Be located away from trees, adjacent structures, uneven roof lines and other obstructions.

Offsets can restrict draft so their use should be mini- mized. Consider the fireplace location relative to floor and ceiling and attic joists.

 

 

Recommended

Recommended

 

 

Location

 

 

 

Location

 

Location

Marginal

 

 

Location

 

 

Not

 

 

 

 

 

Recommended

 

 

 

 

 

Location

 

 

 

Not

 

 

 

Recommended

Windward

 

 

 

 

 

 

Leeward

 

 

Multi-level Roofs

 

Figure 4.2

 

 

 

16

 

Heatilator • BCBV36 • 4008-033 • Rev F • 12/08

Image 16 Contents
Installation and Operation ModelsVent Gas Appliance What to do if you smell gasCongratulations Homeowner Reference InformationInstaller Guide Table of ContentsUser Guide Warranty Warranty Listing and Code Approvals Operating Instructions Gas Fireplace SafetyYour Fireplace Remote Controls, Wall Controls and Wall Switches Clear SpaceDecorative Doors and Fronts Outside Air optionalFor Your Safety Read Before Lighting Lighting Instructions IPIInstructions Standing LightingPilot Initial Break-in Procedure Frequently Asked QuestionsAfter Fireplace is Lit Maintenance and Service Maintenance Tasks-Homeowner Glass Cleaning Remote ControlLogs FireboxControl Compartment and Firebox Top Burner Ignition and OperationGetting Started Typical Appliance SystemTools and Supplies Needed Design and Installation ConsiderationsInspect Appliance and Components Negative Pressure Framing dimensions are the same with or without outside air Framing and ClearancesSelect Appliance Location Construct the Appliance ChaseClearances Clearances to CombustiblesMantels Mantel and Wall ProjectionsMantel Legs or Wall Projections Termination Locations Vent Termination Minimum ClearancesVent Guidelines Vent Information and DiagramsVent System Configuration Vent Clearances and Framing Pipe Clearances to CombustiblesWall and Ceiling Penetration Framing Vertical Penetration FramingInstall Outside Air Kit Damper Assembly Appliance PreparationGas and Electrical Connections Secure and Level the ApplianceInstalling Vent Pipe Assembly of Vent SectionsInstall Attic Insulation Shield Secure Vent SectionsGas Information Fuel ConversionGas Pressure Gas ConnectionWiring Requirements Standing Pilot Ignition System WiringIntellifire Ignition System Wiring Optional Accessories RequirementsElectrical Service and Repair GASJunction Box Installation Prepare Junction Box BracketFinishing Facing MaterialAppliance Setup Place the Vermiculite Log Removal/Replacement Place the RockwoolAir Shutter Setting HoodTroubleshooting Standing Pilot Ignition SystemShould be Placed in this Opening Symptom Possible Cause Corrective Action Intellifire Ignition SystemPilot lights but continues Shorted or loose connection Appliance Dimension Diagram Reference MaterialsService Parts List BCBV36Service Parts ListBCBV36I Service Parts List Description Commnets Part NumberOptional Components SMART-BATT-HTLThis page intentionally left blank Contact Information