13 Finishing

A. Mantel and Wall Projections

WARNING! Risk of Fire! Comply with all minimum clear- ances as specified. Framing closer than the minimums listed must be constructed entirely of noncombustible materials (i.e., steel studs, concrete board, etc.) Failure to comply could cause fire.

Mantels

35-1/2 in. minimum

to ceiling

 

 

 

 

 

 

 

 

 

18

 

 

 

 

 

 

 

 

 

17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

16

 

17-

 

1/2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

 

 

 

 

16-

 

3/4

 

 

 

 

 

 

3 - 12

13

 

15-

 

1/4

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 - 3

 

 

 

14-

 

1/2

 

 

 

 

 

 

 

 

 

 

13

13-

 

3/4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12-

1/2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Measured from top of hood (in inches)

Figure 13.1 Minimum Vertical and Maximum Horizontal Dimen- sions of Combustibles

Mantel Legs or Wall Projections

Top of

Appliance

Drywall

A

B

Mantel Leg or

Perpendicular Wall

A1 in. (25 mm) min. to perpendicular wall

B2-3/8 in. (60 mm) min. from fireplace opening to perpendicular wall

Figure 13.2 Combustible Mantel Leg or Wall Projections (Accept- able on both sides of opening)

B. Facing Material

Metal front faces may be covered with non-combustible materials only.

Facing and/or finishing materials must not interfere with air flow through louvers, operation of louvers or doors, or access for service.

Facing and/or finishing materials must never overhang into the glass opening.

Observe all clearances when applying combustible materials.

Seal joints between the finished wall and appliance top and sides using a 300 °F minimum sealant. Refer to Figure 13.3.

WARNING! Risk of Fire! DO NOT apply combustible ma- terials beyond the minimum clearances. Comply with all minimum clearances to combustibles as specified in this manual. Overlapping materials could ignite and will inter- fere with proper operation of doors and louvers.

These surfaces

 

may be covered

 

with non-combustible

 

material.

Non-combustible

 

 

sealant.

Figure 13.3 Noncombustible Facing Diagram

 

Heatilator • BCBV36 • 4008-033 • Rev F • 12/08

29

Image 29 Contents
Models Installation and OperationVent Gas Appliance What to do if you smell gasHomeowner Reference Information CongratulationsUser Guide Table of ContentsInstaller Guide Warranty Warranty Listing and Code Approvals Your Fireplace Gas Fireplace SafetyOperating Instructions Clear Space Remote Controls, Wall Controls and Wall SwitchesDecorative Doors and Fronts Outside Air optionalLighting Instructions IPI For Your Safety Read Before LightingPilot LightingInstructions Standing After Fireplace is Lit Frequently Asked QuestionsInitial Break-in Procedure Maintenance Tasks-Homeowner Maintenance and ServiceGlass Cleaning Remote ControlFirebox LogsControl Compartment and Firebox Top Burner Ignition and OperationTypical Appliance System Getting StartedInspect Appliance and Components Design and Installation ConsiderationsTools and Supplies Needed Negative Pressure Framing and Clearances Framing dimensions are the same with or without outside airSelect Appliance Location Construct the Appliance ChaseClearances to Combustibles ClearancesMantel Legs or Wall Projections Mantel and Wall ProjectionsMantels Vent Termination Minimum Clearances Termination LocationsVent System Configuration Vent Information and DiagramsVent Guidelines Pipe Clearances to Combustibles Vent Clearances and FramingWall and Ceiling Penetration Framing Vertical Penetration FramingAppliance Preparation Install Outside Air Kit Damper AssemblyGas and Electrical Connections Secure and Level the ApplianceAssembly of Vent Sections Installing Vent PipeInstall Attic Insulation Shield Secure Vent Sections Fuel Conversion Gas Information Gas Pressure Gas ConnectionStanding Pilot Ignition System Wiring Wiring RequirementsIntellifire Ignition System Wiring Optional Accessories RequirementsGAS Electrical Service and RepairPrepare Junction Box Bracket Junction Box InstallationFacing Material FinishingAppliance Setup Place the Rockwool Place the Vermiculite Log Removal/ReplacementHood Air Shutter SettingStanding Pilot Ignition System TroubleshootingShould be Placed in this Opening Intellifire Ignition System Symptom Possible Cause Corrective ActionPilot lights but continues Shorted or loose connection Reference Materials Appliance Dimension DiagramBCBV36 Service Parts ListParts List ServiceBCBV36I Description Commnets Part Number Service Parts ListSMART-BATT-HTL Optional ComponentsThis page intentionally left blank Contact Information