Hearth and Home Technologies BCBV36I owner manual Gas Information, Fuel Conversion, Gas Pressure

Page 25

11 Gas Information

A. Fuel Conversion

Make sure the appliance is compatible with available gas types.

Conversions must be made by a qualified service technician using Hearth & Home Technologies specified and approved parts.

B. Gas Pressure

Optimum appliance performance requires proper input pressures.

Gas line sizing requirements will be determined in ANSI Z221.3 National Fuel Gas Code in the USA and CAN/ CGA B149 in Canada.

Pressure requirements are:

Gas Pressure

Natural Gas

Propane

Minimum inlet pressure

5.0 in. w.c.

11.0 in. w.c.

Maximum inlet pressure

7.0 in. w.c.

14.0 in. w.c.

Manifold pressure

3.5 in. w.c.

10.0 in. w.c.

WARNING! Risk of Fire or Explosion! High pressure will damage valve. Low pressure may cause explosion.

Verify inlet pressures. Verify minimum pressures when other household gas appliances are operating.

Install regulator upstream of valve if line pressure is greater than 1/2 psig.

WARNING

Fire Risk.

Explosion Hazard.

High pressure will damage valve.

Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 1/2 psig.

Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1/2 psig.

Note: Have the gas supply line installed in accordance with local

codes, if any. If not, follow ANSI 223.1. Installation should be done by a qualified installer approved and/or licensed as required by the locality. (In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fitter).

Note: A listed (and Commonwealth of Massachusetts approved)

1/2 in. (13 mm) T-handle manual shut-off valve and flexible gas connector are connected to the 1/2 in. (13 mm) control valve inlet.

If substituting for these components, please consult local codes for compliance.

C. Gas Connection

Refer to Reference Section 16.A. for location of gas line access in appliance.

Gas line may be run through knockout(s) provided.

The gap between supply piping and gas access hole may be caulked with high temperature caulk or stuffed with non-combustible, unfaced insulation to prevent cold air infiltration.

Ensure that gas line does not come in contact with outer wrap of the appliance. Follow local codes.

Pipe incoming gas line into valve compartment.

Connect incoming gas line to the 1/2 in. (13 mm) connection on manual shutoff valve.

WARNING! Risk of Fire or Explosion! Support control when attaching pipe to prevent bending gas line.

A small amount of air will be in the gas supply lines.

WARNING! Risk of Fire or Explosion! Gas build-up dur- ing line purge could ignite.

Purge should be performed by qualified service technician.

Ensure adequate ventilation.

Ensure there are no ignition sources such as sparks or open flames.

Light the appliance. It will take a short time for air to purge from lines. When purging is complete the appliance will light and operate normally.

WARNING! Risk of Fire, Explosion or Asphyxiation! Check all fittings and connections with a non-corrosive commercially available leak-check solution. DO NOT use open flame. Fittings and connections could have loos- ened during shipping and handling.

WARNING! Risk of Fire! DO NOT change valve settings. This valve has been preset at the factory.

D. High Altitude Installations

NOTICE: If the heating value of the gas has been reduced, these rules do not apply. Check with your local gas utility or authorities having jurisdiction.

When installing above 2000 feet elevation:

In the USA: Reduce burner orifice 4% for each 1000 feet above 2000 feet.

In CANADA: Reduce burner orifice 10% for elevations between 2000 feet and 4500 feet. Above 4500 feet, consult local gas utility.

Heatilator • BCBV36 • 4008-033 • Rev F • 12/08

25

Image 25 Contents
Models Installation and OperationVent Gas Appliance What to do if you smell gasHomeowner Reference Information CongratulationsInstaller Guide Table of ContentsUser Guide Warranty Warranty Listing and Code Approvals Operating Instructions Gas Fireplace SafetyYour Fireplace Clear Space Remote Controls, Wall Controls and Wall SwitchesDecorative Doors and Fronts Outside Air optionalLighting Instructions IPI For Your Safety Read Before LightingInstructions Standing LightingPilot Initial Break-in Procedure Frequently Asked QuestionsAfter Fireplace is Lit Maintenance Tasks-Homeowner Maintenance and ServiceGlass Cleaning Remote ControlFirebox LogsControl Compartment and Firebox Top Burner Ignition and OperationTypical Appliance System Getting StartedTools and Supplies Needed Design and Installation ConsiderationsInspect Appliance and Components Negative Pressure Framing and Clearances Framing dimensions are the same with or without outside airSelect Appliance Location Construct the Appliance ChaseClearances to Combustibles ClearancesMantels Mantel and Wall ProjectionsMantel Legs or Wall Projections Vent Termination Minimum Clearances Termination Locations Vent Guidelines Vent Information and Diagrams Vent System Configuration Pipe Clearances to Combustibles Vent Clearances and FramingWall and Ceiling Penetration Framing Vertical Penetration FramingAppliance Preparation Install Outside Air Kit Damper AssemblyGas and Electrical Connections Secure and Level the ApplianceAssembly of Vent Sections Installing Vent PipeInstall Attic Insulation Shield Secure Vent SectionsFuel Conversion Gas InformationGas Pressure Gas ConnectionStanding Pilot Ignition System Wiring Wiring RequirementsIntellifire Ignition System Wiring Optional Accessories RequirementsGAS Electrical Service and RepairPrepare Junction Box Bracket Junction Box InstallationFacing Material FinishingAppliance Setup Place the Rockwool Place the Vermiculite Log Removal/ReplacementHood Air Shutter SettingStanding Pilot Ignition System TroubleshootingShould be Placed in this Opening Intellifire Ignition System Symptom Possible Cause Corrective ActionPilot lights but continues Shorted or loose connection Reference Materials Appliance Dimension DiagramBCBV36 Service Parts ListParts List ServiceBCBV36I Description Commnets Part Number Service Parts ListSMART-BATT-HTL Optional ComponentsThis page intentionally left blank Contact Information