B. Clearances
WARNING! Risk of Fire! You must comply with all minimum air space clearances to combustibles as specified in Fig- ure 6.2. DO NOT pack required air spaces with insulation or other materials.
Storm Collar
Roof Flashing
(attic)
(insulation)
2 in. (51 mm) min.
Shaded areas
represent
2 in. (51 mm) min. air space clearance required around pipe
Attic
Insulation
Shield
(ceiling)
Offset/Return (secured
with hanger straps)
(ceiling)
Ceiling Firestop | Must have 2 in. (51 mm) |
| minimum clearance |
| to header |
| Transition |
Object |
|
Combustible | 48 in. |
| |
| 1219 mm |
| 0 in. |
| to floor |
Figure 6.2 Air Space Clearances |
Heatilator • Birmingham BIR42 • | 19 |