Hearth and Home Technologies BIR42 owner manual Sidewalls/Surrounds, Frame the Fireplace

Page 20

C. Sidewalls/Surrounds

Locate adjacent combustible sidewalls a minimum of 24 in. (610 mm) from fireplace opening.

Mantle leg, surround, stub wall, whether combustible or noncombustible, may be constructed as shown in Figure 6.3.

Note: Grid depicts 1 inch squares.

22 3/8 in.

[568 mm]

FLUSH

FRONT

50°

angle

 

18 1/2 in.

[470 mm]

24 in. [610 mm]

 

BRICK

4 in.

 

[102 mm]

 

FRONT

 

 

42 in.

 

 

 

[1067 mm]

 

 

19 3/4 in.

52-7/8 in.

39°

 

angle

[500 mm]

(1343 mm)

 

 

 

 

 

 

24 in.

 

 

[610 mm]

 

Figure 6.3 Mantel Leg, Surround or Wall Projection (acceptable on both sides of opening)

D. Frame the Fireplace

Figure 6.4 shows typical framing using combustible materials (2x4 lumber shown).

Observe all required air space clearances to combustible materials as shown in Figure 6.2.

2 in. (51 mm) min. air space clearance from chimney.

Note: Framing must be extended straight up, all the way to the ceiling.

Header MUST NOT be notched!

C

D

A

BD

D = extra space needed for outside air connection.

If outside air duct has no bend, this dimension may be reduced as long as minimum clearances are met.

Model #

 

A

B *

C **

D

BIR42

in.

53 7/8

28 3/8

74 1/2

12

 

 

 

 

 

 

 

mm

1368

721

1892

305

 

 

 

 

 

 

*If interior of chase will be drywalled, add the thickness to this meaurement.

**Adjust header height for raised floor under fireplace.

Figure 6.4 Framing the Fireplace

20

Heatilator • Birmingham BIR42 • 4059-308 Rev F • 11/08

Image 20
Contents Hot screen/mesh and glass doors will cause burns Fire RiskNumber Listing Label Information/LocationGrate Table of Contents Warranty Hearth & Home Technologies Limited Warranty CONDITIONS, Exclusions & Limitation of LiabilityHeatilator Birmingham BIR42 4059-308 F 11/08 Listing and Code Approvals Appliance CertificationNon-Combustible Materials Combustible MaterialsOperating Instructions Your FireplaceSeasoned Wood Starting a FireGrate FirescreenGlass Doors Vented Gas Log Sets & Gas Log LightersOptional Components Clear SpaceWood Fuel Hardwood vs SoftwoodDisposal of Ashes Maintainance and ServiceChimney Inspection/Cleaning Glass Cleaning Check Firebox Molded Brick PanelInspect Grate Frequency As desiredTroubleshooting Guide Start Fire Problems Possible Cause SolutionGetting Started Typical Fireplace SystemNegative Pressure Design and Installation ConsiderationsDraft Locating your Fireplace & Chimney Recommended Chimney LocationsTypical Fireplace Components Tools and Supplies NeededInspect Fireplace and Components Framing & Clearances Select Fireplace LocationClearances Air Space ClearancesSidewalls/Surrounds Frame the FireplaceInstallation of Fireplace Things to ConsiderPosition the Fireplace Place Protective Metal Hearth StripsYES Install Outside Air Kit Outside Air InstallationChimney Assembly Chimney Requirements Height of Chimney ComponentsUsing Offsets/Returns ExampleAssemble Chimney Sections Assembling Chimney SectionsInstall Ceiling Firestops Installing the Ceiling FirestopInstall Attic Insulation Shield Prepare Attic Insulation ShieldCut Out Hole in Roof Complete InstallationInstall Flashing Chimney Termination Requirements Flat RoofsChase Installations Construct the ChaseInstall Fireplace & Chimney Install Chase TopInstall Termination Cap ST1175 Square Termination CapTCT1175 Terra Cotta Cap Field Constructed Shrouds ShroudsRadiation Shield Mailbox Style Shroud radiation shield required Installation of Molded Brick Panel Install Hearth Molded Brick PanelInstall Side Molded Brick Panel/Traditional Install Back Molded Brick Panel/TraditionalInstall Side Molded Brick Panel Herring- bone Install Back Molded Brick Panel Herring- boneInstall Mortar Install Screens= 1/k x inches of thickness FinishingHearth Extension Noncombustible Framing MaterialEquivalent insulation Finishing MaterialsNon-combustible Sealant Finishing Material Noncombustible FacingCombustible Mantel Mantel, Adding Extra Support 14 Secure to FramingBrick Front Accessories Gas Log/Lighter ProvisionWood Burning Inserts Gas Code, Ansi Z223.1Fireplace Dimensions Reference MaterialsID6 Insulated Duct .4 mm i.d 1067 mm UD6 Uninsulated Duct Chimney Components Catalog #15-1/4 387 mm 31-3/4 806 mm 34-5/8 879 mm CT56 Chase Top Service PartsContact Information