9 Chase Installations
A. Construct the Chase | Gas line holes and other openings should be caulked with | |||
A chase is a vertical boxlike structure built to enclose the | high temperature caulk or stuffed with unfaced fiberglass | |||
insulation. If the fireplace is being installed on a cement | ||||
fireplace and/or its vent system. Vertical chimneys that | ||||
slab, we recommend that in cold climates, a sheet of |
| |||
run on the outside of a building must be installed inside a |
| |||
plywood or other raised platform be placed underneath to | ||||
chase. | ||||
prevent conducting cold up into the room. |
| |||
Construction of the chase may vary with the type of build- |
| |||
Three examples of chase applications are shown in Fig- | ||||
ing. These instructions are not substitutes for the require- | ||||
ure 9.2. |
|
| ||
ments of local building codes. Local building codes MUST |
|
| ||
|
|
| ||
be checked. |
|
|
| |
1. Fireplace and chimney enclosed in an exterior chase. |
| |||
A chase should be constructed in the manner of all outside |
| |||
2. Chimney offset through exterior wall and enclosed in chase. | ||||
walls of the home to prevent cold air drafting problems. The | ||||
3. Chase constructed on roof. |
| |||
chase should not break the outside building envelope in |
| |||
|
|
| ||
any manner. All outer walls need to be insulated. | Note: In cooler climates, all chase walls should be insulated. | |||
Building codes require false ceiling and ceiling firestops |
|
|
| |
at each floor of the chase or every 10 ft (3.05 m) of clear |
|
|
| |
space to control spread of fire. |
|
|
| |
Walls, ceiling, base plate and cantilever floor at the first |
|
|
| |
level of the chase should be insulated. See Figure 9.1. |
|
|
| |
Vapor and air infiltration barriers should be installed in the |
|
|
| |
chase as per regional codes for the rest of the home. Addi- |
|
|
| |
tionally, Hearth & Home Technologies recommends that the |
|
|
| |
inside surfaces be sheet rocked and taped (or the use of an | 1 | 2 | 3 | |
equivalent method) for maximum air tightness. |
Round Termination Cap | Figure 9.2 | Chase Constructions | |
Metal Chase Top | WARNING! You must install false ceilings and ceiling fire- | ||
|
| ||
| Ceiling | stops at each floor of the chase or every 10 ft (3.05 m) to | |
| Firestop | control spread of fire. | |
|
| WARNING! Risk of Fire! DO NOT seal area between | |
|
| firestop opening and chimney pipe except where they enter | |
|
| the attic or leave the | |
|
| 600° F sealant). | |
| False Ceiling | WARNING! Risk of Fire! You must maintain a minimum | |
|
| 2 in. (51 mm) air space clearance to insulation and other | |
| Attic | materials surrounding the chimney system. | |
Tabs | Insulation | • Insulation and other materials must be firmly secured to | |
| Shield | prevent accidental contact with chimney system. | |
| Insulation in the | ||
| • Failure to prevent contact between insulation or other | ||
| outside walls | ||
Insulation | of the chase | materials and chimney system may cause overheating | |
Insulation | and fire. |
| |
False Ceiling | False Ceiling |
|
|
| Chimney |
|
|
Ceiling |
|
|
|
Firestop |
|
|
|
Figure 9.1 | Chase Assembly |
|
|
32 | Heatilator • Birmingham BIR42 • |