6 Termination Locations

A. Vent Termination Minimum Clearances

WARNING

Fire Risk.

Maintain vent clearance to combustibles as specified.

DO NOT pack air space with insulation or other materials.

Failure to keep insulation or other materials away from vent pipe may cause overheating and fire.

 

 

HORIZONTAL

 

 

OVERHANG

2 FT.

20 INCHES MIN.

VERTICAL

MIN.

 

 

WALL

 

LOWEST

 

 

 

DISCHARGE

 

 

OPENING

 

GAS DIRECT VENT

 

 

TERMINATION CAP

 

 

 

 

X

 

 

12

 

 

ROOF PITCH

 

 

IS X/ 12

 

H (MIN.) - MINIMUM HEIGHT FROM ROOF

 

TO LOWEST DISCHARGE OPENING

Roof Pitch

 

H (Min.) Ft.

Flat to 6/12...........................................................1.0*

Over 6/12 to 7/12.................................................1.25*

Over 7/12 to 8/12.................................................1.5*

Over 8/12 to 9/12.................................................2.0*

Over 9/12 to 10/12...............................................2.5

Over 10/12 to 11/12 .............................................3.25

Over 11/12 to 12/12 .............................................4.0

Over 12/12 to 14/12.............................................5.0

Over 14/12 to 16/12.............................................6.0

Over 16/12 to 18/12.............................................7.0

Over 18/12 to 20/12.............................................7.5

Over 20/12 to 21/12.............................................8.0

* 3 foot minimum in snow regions

Figure 6.1 Minimum Height From Roof To Lowest Discharge

Opening

 

 

DIRECT VENT GAS, WOOD OR FUEL

OIL TERMINATION

B

C

A

GAS

TERMINATION

 

 

Minimum Dimensions

 

Gas

Wood & Fuel Oil

Comments

 

Termination

Termination

 

 

 

 

 

 

A

6 in.

20 in.

Horizontal distance between terminations

 

 

 

 

B

20 in.

24 in.

Distance to perpendicular wall

 

 

 

 

C

18 in.

18 in.

Vertical distance between terminations

 

 

 

 

Figure 6.2 Staggered Termination Caps

DIRECT VENT GAS, WOOD OR FUEL

OIL TERMINATION

 

 

20 IN.

 

 

(508 MM)

 

 

(MINIMUM) TO

 

20 IN. MIN. *

PERPENDICULAR

WOOD OR

WALL

(508 MM)

GAS TERMINATION

(GAS ONLY)

 

*IF USING DECORATIVE CAP COVER(S), THIS DISTANCE MAY NEED TO BE INCREASED. REFER TO THE INSTALLATION INSTRUCTIONS SUPPLIED WITH THE DECORATIVE CAP COVER.

Figure 6.3 Leveled Termination Caps

Heat & Glo • ST-36TRB-IPI, PIER-36TRB-IPI, LCOR-36TRB-IPI, RCOR-36TRB-IPI2128-900 Rev B. • 10/08

23

Image 23
Contents Hot glass will cause burns ModelsWhat to do if you smell gas Homeowner Reference Information CongratulationsUser Guide Table of ContentsFinishing Appliance SetupTroubleshooting Electrical InformationCONDITIONS, Exclusions & Limitation of Liability Limited Lifetime Warranty Listing and Code Approvals Requirements for the Commonwealth of Massachusetts Installation of Carbon Monoxide DetectorsYour Fireplace Gas Fireplace SafetyOperating Instructions User Guide Clear Space Fixed Glass AssemblyRemote Controls, Wall Controls and Wall Switches Fan Kit optionalFinal inspection by Turn off all electric power to the applianceOn position. The ON/OFF switch may Lighting Instructions IPIAfter Fireplace is Lit Frequently Asked QuestionsRemote Control Maintenance and ServiceMaintenance Tasks-Homeowner Glass CleaningLogs Maintenance Tasks-Qualified Service TechnicianGasket Seal and Glass Assembly Inspection VentingIPI Pilot Flame Patterns Burner Ignition and OperationTypical Appliance System Getting StartedAny such action may cause a fire hazard Design and Installation ConsiderationsTools and Supplies Needed Inspect Appliance and ComponentsSelecting Appliance Location Framing and ClearancesClearances Constructing the Appliance ChaseRCOR-36TRB-IPI PIER/LCOR/RCOR Non-Combustible Mantel Mantel and Wall Projections See-Through Combustible MantelPIER/LCOR/RCOR Combustible Mantel See-Through Non-Combustible MantelTOP View Fireplace Opening Vent Termination Minimum Clearances Termination LocationsCovered Alcove Applications Continue Adding Vent Components Install Support BracketsTo Install the Heat Shield Use of Elbows Vent Information and DiagramsApproved Pipe Vent Table KeyTo SLP series vent pipe, if desired Vent DiagramsV1 Minimum H1 + H2 Maximum Top Vent Horizontal Termination One ElbowTwo Elbows V1 Minimum H1 MaximumTop Vent Horizontal Termination Three Elbows Exhaust restrictor Instructions E a K R E H1+ H2 V1 + V2 Minimum H1+ H2 Maximum Two Elbows Three ElbowsMaximum + V 2 Minimum Page H1 Maximum V1 Minimum H2+ H3 H1+ H2+ H3 Rear Vent Horizontal Termination Two ElbowsH1 Maximum V1 Minimum H2 Maximum H1+ H2 Maximum V1 Minimum H1 + H2 Maximum Rear Vent Vertical Termination One ElbowV1 Minimum H1 Maximum V1 Minimum H1+ H2+ H3 Maximum Rear Vent Vertical Termination Three ElbowsH1 Maximum V1 Minimum H1+ H2 Maximum Combustible Wall Penetration Vent Clearances and FramingPipe Clearances to Combustibles Wall Penetration FramingPipe DVP SLP Vertical Penetration FramingVaulted Ceiling Installation Install Attic Insulation ShieldFlat Ceiling Installation Proceed to . C Appliance PreparationTop Vent Cut the metal retaining band Rear VentAttach Nailing Tab to Front Corner of Unit Securing and Leveling the ApplianceAssemble Pipe Sections DVP Pipe Only Installing Vent Pipe DVP and SLP PipeAttach Vent to the Firebox Assembly Assemble Vent Sections DVP Pipe OnlyAssemble Slip Sections Assemble Vent Sections SLP Pipe OnlyDisassemble Vent Sections Secure the Vent SectionsInstall Decorative Ceiling Components SLP only Assemble and Install Storm Collar Install Metal Roof FlashingSLP-FS Install RF4-8Heat Shield Requirements for Horizontal Termination Install Vertical Termination CapInstall Decorative Wall Components SLP only Refer to of this manual Install Horizontal Termination Cap DVP and SLP PipeAnsi Z223.1 and CAN/CGA-B149 installation codes Gas Connection Gas InformationFuel Conversion Gas PressureElectrical Service and Repair Wiring RequirementsIntellifire Ignition System Wiring Optional Accessories RequirementsIntellifire Ignition Wiring Diagram with Remote Receiver Wall Switch Installation for Fan Optional Junction Box InstallationSplatter Guard To install the Splatter GuardFinishing To Remove the Splatter Guard To Close the Lower Access PanelPIER/LCOR/RCOR Mantel Projection Mantel and Wall Projections See-Through Mantel ProjectionFacing Material Finishing MaterialFinishing materials over 1 inch thick Elevated Hearth Systems Appliance Setup 2128-935 Install the Log AssemblyIndentations Air Shutter Settings Install Trim Kits and SurroundsAir Shutter Setting Intellifire Ignition System TroubleshootingSymptom Possible Cause Corrective Action Remove any contaminants that may have accumulated on Location Inches Millimeters Appliance Dimension DiagramReference Materials Electrical Access GAS Line Left View Front View Right View Electrical DVP vent components Vent Components DiagramsHorizontal Termination Cap DVP-TRAP1 DVP-TRAP2 DVP-TRAPK1 DVP-TRAPK2 DVP-HPC1 DVP-HPC213-3/4 13-7/8 352 mm 349 mm 787 mm 13-1/4 367 mm 24-5/8 625 mm 27-1/2 127 mmRoof Flashing Multi-pak 13-3/4 11-7/8 349 mm 302 mmDVP-TV DVP-HRC-SS RF4-8 Elbow660 mm Extended Heat ShieldAdapter Black Support Box-BlackWall Thimble-Black Service Parts Log Set AssemblyAt Depot Service Parts ListPIER-36TRB-IPI Stocked LCOR-36TRB-IPI SRV2132-FACE RCOR-36TRB-IPI RCOR-36TRB-IPI ST-36TRB-IPI, PIER-36TRB-IPI Contact Information

PIER-36TRB-IPI, LCOR-36TRB-IPI, ST-36TRB-IPI, RCOR-36TRB-IPI specifications

Hearth and Home Technologies has established itself as a leader in the hearth industry, offering a range of innovative and efficient heating solutions. Among their standout products are the RCOR-36TRB-IPI, ST-36TRB-IPI, LCOR-36TRB-IPI, and PIER-36TRB-IPI, which present an attractive blend of aesthetics and functionality.

The RCOR-36TRB-IPI is designed with a contemporary linear shape that can be the centerpiece of any living space. One of its main features is the advanced IntelliFire® ignition system, allowing for easy lighting and enhanced reliability. This model boasts an extensive selection of flame adjustment options, providing users with the ability to customize the fire's appearance to fit their mood. Additionally, it offers an impressive direct vent technology, ensuring optimal efficiency and maintaining indoor air quality by drawing air from outside.

The ST-36TRB-IPI takes traditional elements and fuses them with modern efficiency. This model is compatible with various styles of venting, making it versatile for different home layouts. Its clear, tempered glass front adds a touch of elegance while maximizing heat output. With a built-in blower option, the ST-36TRB-IPI circulates warmth effectively throughout larger spaces. The easy-to-use remote control enhances user experience, allowing homeowners to manage their heating with convenience.

The LCOR-36TRB-IPI is another exciting option, featuring a more rustic design perfect for those looking to bring a touch of traditional charm into their home. This model is equipped with a powerful heat exchanger that optimizes heat output while minimizing fuel consumption. The LCOR-36TRB-IPI also promotes safety with its glass safety barrier, ensuring that the flames are safely contained.

Finally, the PIER-36TRB-IPI is all about dramatic beauty and functionality. This model features a unique, vertical design that sets it apart in any room. It utilizes advanced combustion technology, creating a clean-burning, efficient fire. Equipped with innovative heat management features, the PIER-36TRB-IPI delivers warmth where it's needed most, while also enhancing the ambiance of the space.

In summary, the RCOR-36TRB-IPI, ST-36TRB-IPI, LCOR-36TRB-IPI, and PIER-36TRB-IPI from Hearth and Home Technologies cater to various tastes and needs, combining leading-edge technology with impressive heating capabilities. These models not only provide warmth but also elevate the aesthetic appeal of any home, making them an excellent investment for comfort and style.