Hearth and Home Technologies ST-36TRB-IPI Gas Information, Fuel Conversion, Gas Pressure

Page 51

11 Gas Information

A. Fuel Conversion

Make sure the appliance is compatible with available gas types.

Conversions must be made by a qualified service technician using Hearth & Home Technologies specified and approved parts.

B. Gas Pressure

Optimum appliance performance requires proper input pressures.

Gas line sizing requirements will be determined in ANSI Z223.1 National Fuel Gas Code in the USA and CAN/ CGA B149 in Canada.

Pressure requirements are:

Gas Pressure

Natural Gas

Propane

Minimum inlet pressure

5.0 in. w.c.

11.0 in. w.c.

Maximum inlet pressure

14.0 in. w.c.

14.0 in. w.c.

Manifold pressure

3.5 in. w.c.

10.0 in. w.c.

C. Gas Connection

Refer to Reference Section 16 for location of gas line access in appliance.

Gas line may be run through knockout(s) provided.

The gap between supply piping and gas access hole may be caulked with high temperature caulk or stuffed with non-combustible, unfaced insulation to prevent cold air infiltration.

Ensure that gas line does not come in contact with outer wrap of the appliance. Follow local codes.

Pipe incoming gas line into valve compartment.

Connect incoming gas line to the 1/2 in. (13 mm) connection on manual shutoff valve.

WARNING! Risk of Fire or Explosion! Support control when attaching pipe to prevent bending gas line.

• A small amount of air will be in the gas supply lines.

WARNING! Risk of Fire or Explosion! Gas build-up dur- ing line purge could ignite.

WARNING! Risk of Fire/Explosion! High pressure will damage valve. Low pressure may cause explosion.

Verify inlet pressures. Verify minimum pressures when other household gas appliances are operating.

Install regulator upstream of valve if line pressure is greater than 1/2 psig.

WARNING

Fire Risk. Explosion Hazard.

High pressure will damage valve.

• Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 1/2 psig.

Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1/2 psig.

Note: Have the gas supply line installed in accordance with local codes, if any. If not, follow ANSI 223.1. Installation should be done by a qualified installer approved and/or licensed as required by the locality. (In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fitter).

Note: A listed (and Commonwealth of Massachusetts ap- proved) 1/2 in. (13 mm) T-handle manual shut-off valve and flexible gas connector are connected to the 1/2 inch (13 mm) control valve inlet.

If substituting for these components, please consult local codes for compliance.

Purge should be performed by qualified service technician.

Ensure adequate ventilation.

Ensure there are no ignition sources such as sparks or open flames.

Light the appliance. It will take a short time for air to purge from lines. When purging is complete the appliance will light and operate normally.

WARNING! Risk of Fire, Explosion or Asphyxiation! Check all fittings and connections with a non-corrosive commercially available leak-check solution. DO NOT use open flame. Fittings and connections could have loos- ened during shipping and handling.

WARNING! Risk of Fire! DO NOT change valve settings. This valve has been preset at the factory.

D. High Altitude Installations

NOTICE: If the heating value of the gas has been reduced, these rules do not apply. Check with your local gas utility or authorities having jurisdiction.

When installing above 2000 feet elevation:

In the USA: Reduce burner orifice 4% for each 1000 feet above 2000 feet.

In the CANADA: Reduce burner orifice 10% for elevations between 2000 feet and 4500 feet. Above 4500 feet, consult local gas utility.

Heat & Glo • ST-36TRB-IPI, PIER-36TRB-IPI, LCOR-36TRB-IPI, RCOR-36TRB-IPI2128-900 Rev B. • 10/08

51

Image 51
Contents Models What to do if you smell gasHot glass will cause burns Homeowner Reference Information CongratulationsUser Guide Table of ContentsFinishing Appliance SetupTroubleshooting Electrical InformationCONDITIONS, Exclusions & Limitation of Liability Limited Lifetime Warranty Listing and Code Approvals Requirements for the Commonwealth of Massachusetts Installation of Carbon Monoxide DetectorsGas Fireplace Safety Operating Instructions User GuideYour Fireplace Clear Space Fixed Glass AssemblyRemote Controls, Wall Controls and Wall Switches Fan Kit optionalFinal inspection by Turn off all electric power to the applianceOn position. The ON/OFF switch may Lighting Instructions IPIAfter Fireplace is Lit Frequently Asked QuestionsRemote Control Maintenance and ServiceMaintenance Tasks-Homeowner Glass CleaningLogs Maintenance Tasks-Qualified Service TechnicianGasket Seal and Glass Assembly Inspection VentingIPI Pilot Flame Patterns Burner Ignition and OperationTypical Appliance System Getting StartedAny such action may cause a fire hazard Design and Installation ConsiderationsTools and Supplies Needed Inspect Appliance and ComponentsSelecting Appliance Location Framing and ClearancesClearances Constructing the Appliance ChaseRCOR-36TRB-IPI PIER/LCOR/RCOR Non-Combustible Mantel Mantel and Wall Projections See-Through Combustible MantelPIER/LCOR/RCOR Combustible Mantel See-Through Non-Combustible MantelTOP View Fireplace Opening Vent Termination Minimum Clearances Termination LocationsCovered Alcove Applications Install Support Brackets To Install the Heat ShieldContinue Adding Vent Components Use of Elbows Vent Information and DiagramsApproved Pipe Vent Table KeyTo SLP series vent pipe, if desired Vent DiagramsV1 Minimum H1 + H2 Maximum Top Vent Horizontal Termination One ElbowTwo Elbows V1 Minimum H1 MaximumTop Vent Horizontal Termination Three Elbows Exhaust restrictor Instructions E a K R E Two Elbows Three Elbows Maximum + V 2 MinimumH1+ H2 V1 + V2 Minimum H1+ H2 Maximum Page Rear Vent Horizontal Termination Two Elbows H1 Maximum V1 Minimum H2 Maximum H1+ H2 MaximumH1 Maximum V1 Minimum H2+ H3 H1+ H2+ H3 Rear Vent Vertical Termination One Elbow V1 Minimum H1 MaximumV1 Minimum H1 + H2 Maximum Rear Vent Vertical Termination Three Elbows H1 Maximum V1 Minimum H1+ H2 MaximumV1 Minimum H1+ H2+ H3 Maximum Combustible Wall Penetration Vent Clearances and FramingPipe Clearances to Combustibles Wall Penetration FramingPipe DVP SLP Vertical Penetration FramingInstall Attic Insulation Shield Flat Ceiling InstallationVaulted Ceiling Installation Appliance Preparation Top VentProceed to . C Cut the metal retaining band Rear VentAttach Nailing Tab to Front Corner of Unit Securing and Leveling the ApplianceAssemble Pipe Sections DVP Pipe Only Installing Vent Pipe DVP and SLP PipeAttach Vent to the Firebox Assembly Assemble Vent Sections DVP Pipe OnlyAssemble Slip Sections Assemble Vent Sections SLP Pipe OnlyDisassemble Vent Sections Secure the Vent SectionsInstall Decorative Ceiling Components SLP only Assemble and Install Storm Collar Install Metal Roof FlashingSLP-FS Install RF4-8Install Vertical Termination Cap Install Decorative Wall Components SLP onlyHeat Shield Requirements for Horizontal Termination Install Horizontal Termination Cap DVP and SLP Pipe Ansi Z223.1 and CAN/CGA-B149 installation codesRefer to of this manual Gas Connection Gas InformationFuel Conversion Gas PressureElectrical Service and Repair Wiring RequirementsIntellifire Ignition System Wiring Optional Accessories RequirementsIntellifire Ignition Wiring Diagram with Remote Receiver Wall Switch Installation for Fan Optional Junction Box InstallationTo install the Splatter Guard FinishingSplatter Guard To Remove the Splatter Guard To Close the Lower Access PanelPIER/LCOR/RCOR Mantel Projection Mantel and Wall Projections See-Through Mantel ProjectionFacing Material Finishing MaterialFinishing materials over 1 inch thick Elevated Hearth Systems Appliance Setup 2128-935 Install the Log AssemblyIndentations Install Trim Kits and Surrounds Air Shutter SettingAir Shutter Settings Troubleshooting Symptom Possible Cause Corrective ActionIntellifire Ignition System Remove any contaminants that may have accumulated on Appliance Dimension Diagram Reference MaterialsLocation Inches Millimeters Electrical Access GAS Line Left View Front View Right View Electrical DVP vent components Vent Components DiagramsHorizontal Termination Cap DVP-TRAP1 DVP-TRAP2 DVP-TRAPK1 DVP-TRAPK2 DVP-HPC1 DVP-HPC213-3/4 13-7/8 352 mm 349 mm 787 mm 13-1/4 367 mm 24-5/8 625 mm 27-1/2 127 mmRoof Flashing Multi-pak 13-3/4 11-7/8 349 mm 302 mmDVP-TV DVP-HRC-SS RF4-8 Elbow660 mm Extended Heat ShieldBlack Support Box-Black Wall Thimble-BlackAdapter Service Parts Log Set AssemblyAt Depot Service Parts ListPIER-36TRB-IPI Stocked LCOR-36TRB-IPI SRV2132-FACE RCOR-36TRB-IPI RCOR-36TRB-IPI ST-36TRB-IPI, PIER-36TRB-IPI Contact Information

PIER-36TRB-IPI, LCOR-36TRB-IPI, ST-36TRB-IPI, RCOR-36TRB-IPI specifications

Hearth and Home Technologies has established itself as a leader in the hearth industry, offering a range of innovative and efficient heating solutions. Among their standout products are the RCOR-36TRB-IPI, ST-36TRB-IPI, LCOR-36TRB-IPI, and PIER-36TRB-IPI, which present an attractive blend of aesthetics and functionality.

The RCOR-36TRB-IPI is designed with a contemporary linear shape that can be the centerpiece of any living space. One of its main features is the advanced IntelliFire® ignition system, allowing for easy lighting and enhanced reliability. This model boasts an extensive selection of flame adjustment options, providing users with the ability to customize the fire's appearance to fit their mood. Additionally, it offers an impressive direct vent technology, ensuring optimal efficiency and maintaining indoor air quality by drawing air from outside.

The ST-36TRB-IPI takes traditional elements and fuses them with modern efficiency. This model is compatible with various styles of venting, making it versatile for different home layouts. Its clear, tempered glass front adds a touch of elegance while maximizing heat output. With a built-in blower option, the ST-36TRB-IPI circulates warmth effectively throughout larger spaces. The easy-to-use remote control enhances user experience, allowing homeowners to manage their heating with convenience.

The LCOR-36TRB-IPI is another exciting option, featuring a more rustic design perfect for those looking to bring a touch of traditional charm into their home. This model is equipped with a powerful heat exchanger that optimizes heat output while minimizing fuel consumption. The LCOR-36TRB-IPI also promotes safety with its glass safety barrier, ensuring that the flames are safely contained.

Finally, the PIER-36TRB-IPI is all about dramatic beauty and functionality. This model features a unique, vertical design that sets it apart in any room. It utilizes advanced combustion technology, creating a clean-burning, efficient fire. Equipped with innovative heat management features, the PIER-36TRB-IPI delivers warmth where it's needed most, while also enhancing the ambiance of the space.

In summary, the RCOR-36TRB-IPI, ST-36TRB-IPI, LCOR-36TRB-IPI, and PIER-36TRB-IPI from Hearth and Home Technologies cater to various tastes and needs, combining leading-edge technology with impressive heating capabilities. These models not only provide warmth but also elevate the aesthetic appeal of any home, making them an excellent investment for comfort and style.