Hearth and Home Technologies 8000TR-OAK-IPI owner manual Install the Ceiling Firestop, Pipe DVP

Page 35

C. Install the Ceiling Firestop

A ceiling firestop MUST be used between floors and attics.

DVP pipe only - Frame an opening 10 in. by 10 in. (254 mm by 254 mm) whenever the vent penetrates a ceiling/floor (see Figure 8.7).

Frame the area with the same sized lumber as used in ceiling/floor joist.

The ceiling firestop may be installed above or below the ceiling joists when installed with a attic insulation shield. It must be under joists between floors that are not insulated. Refer to Figure 8.8.

Secure with three fasteners on each side.

WARNING! Risk of Fire! DO NOT pack insu- lation around the vent. Insulation must be kept back from the pipe to prevent overheating.

 

 

ATTIC ABOVE

 

 

A

 

 

A

 

PIPE

A

 

DVP

10 in. (254 mm)

Figure 8.7

Installing Ceiling Firestop

 

INSTALL ATTIC INSULATION SHIELDS

 

BEFORE OR AFTER INSTALLATION OF VENT SYSTEM

3 FASTENERS

 

 

PER SIDE

 

 

CEILING FIRESTOP

 

CEILING FIRESTOP

INSTALLED BELOW CEILING

INSTALLED ABOVE CEILING

Figure 8.8 Installing the Attic Shield

 

 

Heat & Glo • 8000TR-OAK, 8000TR-OAK-IPI, 8000TRLP-OAKIPI2057-900 Rev. P • 11/08

35

Image 35
Contents What to do if you smell gas Models 8000TR-OAK 8000TR-OAK-IPI 8000TRLP-OAKIPIHomeowner Reference Information CongratulationsUser Guide Table of ContentsReference Materials Appliance SetupTroubleshooting FinishingCONDITIONS, Exclusions & Limitation of Liability Limited Lifetime Warranty Listing and Code Approvals Requirements for the Commonwealth of Massachusetts Installation of Carbon Monoxide DetectorsYour Fireplace Gas Fireplace SafetyOperating Instructions User Guide Clear Space Fixed Glass AssemblyRemote Controls, Wall Controls and Wall Switches Fan Kit optionalFinal inspection by Lighting Instructions IPILighting Instructions Standing Pilot For Your Safety Read Before Lighting Lighting InstructionsAfter Fireplace is Lit Frequently Asked QuestionsRemote Control Maintenance and ServiceMaintenance Tasks-Homeowner Glass CleaningLogs Maintenance Tasks-Qualified Service TechnicianGasket Seal and Glass Assembly Inspection VentingEither cobrahead or SIT Typical Appliance System Getting StartedInspect Appliance and Components Design and Installation ConsiderationsTools and Supplies Needed Selecting Appliance Location Framing and ClearancesClearances Constructing the Appliance ChaseTOP View Mantel and Wall ProjectionsVent Termination Minimum Clearances Termination LocationsCovered Alcove Applications Use of Elbows Vent Information and DiagramsApproved Pipe Vent Table KeyV1 Minimum H1 + H2 Maximum Vent Diagrams Top Vent Horizontal Termination One ElbowTwo Elbows V1 Minimum H1 MaximumMinimum Maximum + V 2 Minimum + H 2 Maximum Top Vent Horizontal Termination Three ElbowsBreak Here H1 Maximum V1 + V2 Minimum Top Vent Vertical Termination Two ElbowsPage H1 Maximum V1 Minimum H2+ H3 H1+ H2+ H3 Maximum Rear Vent Horizontal Termination Two ElbowsH1 Maximum V1 Minimum H1+ H2 Maximum H1+ H2 Maximum V1 Minimum Rear Vent Vertical Termination One ElbowRear Vent Vertical Termination Three Elbows Heat Shield Above First 900 Elbow Vent Clearances and FramingPipe Clearances to Combustibles Non-Combustible Wall Penetration Wall Penetration FramingCombustible Wall Penetration Pipe DVP Install the Ceiling FirestopVaulted Ceiling Installation Install Attic Insulation ShieldFlat Ceiling Installation Proceed to Section Appliance PreparationTop Vent Rear Vent 11 Proper positioning, leveling and securing of an appliance Securing and Leveling the ApplianceChecking Pilot Plate Completing Grate Set-upAssemble Pipe Sections Installing Vent PipeAttach Vent to the Firebox Assembly Assemble Vent SectionsSecure the Vent Sections Assemble Slip SectionsDisassemble Vent Sections 10 Rotate Seams for DisassemblyAssemble and Install Storm Collar Install Metal Roof FlashingApply Sealant TOP & Partial Sides Install RF4-8Heat Shield Requirements for Horizontal Termination Install Vertical Termination CapAnsi Z223.1 and CAN/CGA-B149 installation codes Install Horizontal Termination CapGas Connection Gas InformationFuel Conversion Gas PressureOptional Accessories Requirements Wiring RequirementsIntellifire Ignition System Wiring Standing Pilot Ignition System WiringIntellifire Pilot Ignition IPI Wiring Diagram Electrical Service and RepairWall Switch Installation for Fan Optional Junction Box InstallationCombustible Mantel Legs or Wall Projections FinishingFacing Material Appliance Setup LOG Tabs Install the Log AssemblyPage Air Shutter Settings Install the MeshInstall Trim and/or Surround Air Shutter SettingStanding Pilot Ignition System TroubleshootingSymptom Possible Causes Corrective Action Symptom Possible Cause Corrective Action TroubleshootingIntellifire Ignition System Ues to spark, and main Reference Materials Appliance Dimension DiagramDVP vent components Vent Components DiagramsDVP-TRAP1 DVP-TRAP2 DVP-TRAPK1 DVP-TRAPK2 DVP-HPC1 DVP-HPC2 RF6M RF12M DVP-TV Service Parts Log Set AssemblyAt Depot Service Parts List 8000TR-OAK, 8000TR-OAK-IPIStocked 8000TR-OAK-IPI 8000TR-OAK Contact Information

8000TRLP-OAKIPI, 8000TR-OAK-IPI, 8000TR-OAK specifications

Hearth and Home Technologies is renowned for its innovative approach to home heating solutions, and their series of fireplaces is a testament to that commitment. Among their popular offerings are the 8000TR-OAK, 8000TR-OAK-IPI, and 8000TRLP-OAKIPI models. Each of these fireplaces is designed to deliver warmth, ambiance, and advanced technology wrapped in a refined aesthetic.

The 8000TR-OAK model features an impressive viewing area, which allows the flickering flames to be the centerpiece of any room. With a heating capacity that efficiently warms up spaces, it is ideal for both contemporary and traditional settings. One of its main highlights is the realistic log set that adds to the authenticity of the fire experience. The stove's design is not only visually appealing but also engineered for high efficiency, reducing carbon footprints while maximizing heat output.

Moving to the 8000TR-OAK-IPI, this model integrates the innovative IntelliFire Ignition system, ensuring that operation is reliable and energy-efficient. The IPI system allows the fireplace to be controlled with ease, offering both manual and remote-operation options. This model maintains the authentic charm of the traditional fireplace while incorporating modern technology. The 8000TR-OAK-IPI also boasts multiple flame settings, giving users the flexibility to adjust their experience based on mood or season, along with an outstanding ability to maintain heat with minimal energy consumption.

The 8000TRLP-OAKIPI takes versatility a step further by operating on liquid propane, making it ideal for homes that are not connected to natural gas lines. Along with the IntelliFire Ignition technology, this model ensures exceptional efficiency, making it a premium choice for those who prioritize sustainable energy solutions. The design retains the luxurious oak finish found in its counterparts, ensuring it complements any interior decor seamlessly.

All three models share a range of characteristics that set them apart: a robust construction that promises longevity, an array of customizable options, and built-in safety features that instill confidence in operation. They also offer a variety of venting options, giving homeowners flexibility in installation. With Hearth and Home Technologies’ commitment to quality and innovation, the 8000 series fireplaces provide not just heat, but a captivating focal point for home gatherings.