Hearth and Home Technologies 8000TR-OAK-IPI Requirements for the Commonwealth of Massachusetts

Page 8

Note: The following requirements reference various Massachusetts and national codes not contained in this document.

H.Requirements for the Commonwealth of Massachusetts

For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, in- cluding but not limited to decks and porches, the following requirements shall be satisfied:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addi- tion, the installing plumber or gas fitter shall observe that a battery operated or hard wired carbon monoxide detec- tor with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fu- eled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that dur- ing said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accor- dance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.

Signage

A metal or plastic identification plate shall be permanent- ly mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fu- eled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) in. in size, “GAS

VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB- STRUCTIONS”.

Inspection

The state or local gas inspector of the side wall horizon- tally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector ob- serves carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.

Exemptions

The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and

Product Approved side wall horizontally vented gas fu- eled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided

When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

Detailed instructions for the installation of the venting system design or the venting system components; and

A complete parts list for the venting system design or venting system.

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not pro- vide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:

The referenced “special venting system” instructions shall be included with the appliance or equipment in- stallation instructions; and

The “special venting systems” shall be Product Ap- proved by the Board, and the instructions for that sys- tem shall include a parts list and detailed installation instructions.

A copy of all installation instructions for all Product Ap- proved side wall horizontally vented gas fueled equip- ment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

See Gas Connection section for additional Common- wealth of Massachusetts requirements.

8

Heat & Glo • 8000TR-OAK, 8000TR-OAK-IPI, 8000TRLP-OAKIPI2057-900 Rev. P • 11/08

Image 8
Contents Models 8000TR-OAK 8000TR-OAK-IPI 8000TRLP-OAKIPI What to do if you smell gasCongratulations Homeowner Reference InformationTable of Contents User GuideAppliance Setup TroubleshootingFinishing Reference MaterialsCONDITIONS, Exclusions & Limitation of Liability Limited Lifetime Warranty Listing and Code Approvals Installation of Carbon Monoxide Detectors Requirements for the Commonwealth of MassachusettsYour Fireplace Gas Fireplace SafetyOperating Instructions User Guide Fixed Glass Assembly Remote Controls, Wall Controls and Wall SwitchesFan Kit optional Clear SpaceLighting Instructions IPI Final inspection byFor Your Safety Read Before Lighting Lighting Instructions Lighting Instructions Standing PilotFrequently Asked Questions After Fireplace is LitMaintenance and Service Maintenance Tasks-HomeownerGlass Cleaning Remote ControlMaintenance Tasks-Qualified Service Technician Gasket Seal and Glass Assembly InspectionVenting LogsEither cobrahead or SIT Getting Started Typical Appliance SystemInspect Appliance and Components Design and Installation ConsiderationsTools and Supplies Needed Framing and Clearances Selecting Appliance LocationConstructing the Appliance Chase ClearancesMantel and Wall Projections TOP ViewTermination Locations Vent Termination Minimum ClearancesCovered Alcove Applications Vent Information and Diagrams Approved PipeVent Table Key Use of ElbowsVent Diagrams Top Vent Horizontal Termination One Elbow Two ElbowsV1 Minimum H1 Maximum V1 Minimum H1 + H2 MaximumTop Vent Horizontal Termination Three Elbows Minimum Maximum + V 2 Minimum + H 2 MaximumBreak Here Top Vent Vertical Termination Two Elbows H1 Maximum V1 + V2 MinimumPage H1 Maximum V1 Minimum H2+ H3 H1+ H2+ H3 Maximum Rear Vent Horizontal Termination Two ElbowsH1 Maximum V1 Minimum H1+ H2 Maximum Rear Vent Vertical Termination One Elbow H1+ H2 Maximum V1 MinimumRear Vent Vertical Termination Three Elbows Heat Shield Above First 900 Elbow Vent Clearances and FramingPipe Clearances to Combustibles Non-Combustible Wall Penetration Wall Penetration FramingCombustible Wall Penetration Install the Ceiling Firestop Pipe DVPVaulted Ceiling Installation Install Attic Insulation ShieldFlat Ceiling Installation Proceed to Section Appliance PreparationTop Vent Rear Vent Securing and Leveling the Appliance 11 Proper positioning, leveling and securing of an applianceCompleting Grate Set-up Checking Pilot PlateInstalling Vent Pipe Attach Vent to the Firebox AssemblyAssemble Vent Sections Assemble Pipe SectionsAssemble Slip Sections Secure the Vent Sections10 Rotate Seams for Disassembly Disassemble Vent SectionsInstall Metal Roof Flashing Assemble and Install Storm CollarInstall RF4-8 Apply Sealant TOP & Partial SidesInstall Vertical Termination Cap Heat Shield Requirements for Horizontal TerminationInstall Horizontal Termination Cap Ansi Z223.1 and CAN/CGA-B149 installation codesGas Information Fuel ConversionGas Pressure Gas ConnectionWiring Requirements Intellifire Ignition System WiringStanding Pilot Ignition System Wiring Optional Accessories RequirementsElectrical Service and Repair Intellifire Pilot Ignition IPI Wiring DiagramJunction Box Installation Wall Switch Installation for Fan OptionalCombustible Mantel Legs or Wall Projections FinishingFacing Material Appliance Setup Install the Log Assembly LOG TabsPage Install the Mesh Install Trim and/or SurroundAir Shutter Setting Air Shutter SettingsStanding Pilot Ignition System TroubleshootingSymptom Possible Causes Corrective Action Troubleshooting Symptom Possible Cause Corrective ActionIntellifire Ignition System Ues to spark, and main Appliance Dimension Diagram Reference MaterialsVent Components Diagrams DVP vent componentsDVP-TRAP1 DVP-TRAP2 DVP-TRAPK1 DVP-TRAPK2 DVP-HPC1 DVP-HPC2 RF6M RF12M DVP-TV Log Set Assembly Service PartsAt Depot Service Parts List 8000TR-OAK, 8000TR-OAK-IPIStocked 8000TR-OAK-IPI 8000TR-OAK Contact Information

8000TRLP-OAKIPI, 8000TR-OAK-IPI, 8000TR-OAK specifications

Hearth and Home Technologies is renowned for its innovative approach to home heating solutions, and their series of fireplaces is a testament to that commitment. Among their popular offerings are the 8000TR-OAK, 8000TR-OAK-IPI, and 8000TRLP-OAKIPI models. Each of these fireplaces is designed to deliver warmth, ambiance, and advanced technology wrapped in a refined aesthetic.

The 8000TR-OAK model features an impressive viewing area, which allows the flickering flames to be the centerpiece of any room. With a heating capacity that efficiently warms up spaces, it is ideal for both contemporary and traditional settings. One of its main highlights is the realistic log set that adds to the authenticity of the fire experience. The stove's design is not only visually appealing but also engineered for high efficiency, reducing carbon footprints while maximizing heat output.

Moving to the 8000TR-OAK-IPI, this model integrates the innovative IntelliFire Ignition system, ensuring that operation is reliable and energy-efficient. The IPI system allows the fireplace to be controlled with ease, offering both manual and remote-operation options. This model maintains the authentic charm of the traditional fireplace while incorporating modern technology. The 8000TR-OAK-IPI also boasts multiple flame settings, giving users the flexibility to adjust their experience based on mood or season, along with an outstanding ability to maintain heat with minimal energy consumption.

The 8000TRLP-OAKIPI takes versatility a step further by operating on liquid propane, making it ideal for homes that are not connected to natural gas lines. Along with the IntelliFire Ignition technology, this model ensures exceptional efficiency, making it a premium choice for those who prioritize sustainable energy solutions. The design retains the luxurious oak finish found in its counterparts, ensuring it complements any interior decor seamlessly.

All three models share a range of characteristics that set them apart: a robust construction that promises longevity, an array of customizable options, and built-in safety features that instill confidence in operation. They also offer a variety of venting options, giving homeowners flexibility in installation. With Hearth and Home Technologies’ commitment to quality and innovation, the 8000 series fireplaces provide not just heat, but a captivating focal point for home gatherings.