D. Install Attic Insulation Shield

WARNING! Fire Risk. DO NOT allow loose materials or insulation to touch vent. Hearth & Home Technologies Inc. requires the use of an attic shield.

The National Fuel Gas Code ANSI Z223.1 and NFPA 54 requires an attic shield constructed of 26 gauge minimum metal that extends at least 2 in. (51 mm) above insulation.

Attic shields must meet specified clearance and be se- cured in place.

Flat Ceiling Installation

• Remove one shield from box.

NOTICE: Cut previously installed batt insulation to make room for the attic insulation shield.

Wrap shield around pipe if pipe is already installed in area to be insulated.

Match the three holes in each side and fasten with three screws to form a tube.

Bend three tabs on the bottom of the shield outward to allow attachment to the ceiling firestop.

Bend the remaining bottom tabs inward 90º to maintain the air space between the pipe and the shield. Set the shield on the ceiling firestop and attach to the firestop.

Bend all tabs inward 90º around the top of the shield. These tabs must be used to prevent blown insulation from getting between the shield and vent pipe, and to maintain air space clearance.

Vaulted Ceiling Installation

• Remove one shield from box.

NOTICE: Cut previously installed batt insulation to make room for the attic insulation shield.

Cut the attic insulation shield (if application is for vaulted ceiling) to fit your ceiling pitch. Snip cut edge to recreate 1 in. bend tabs all the way around the bottom.

Wrap shield around pipe if pipe is already installed in area to be insulated.

Match the three holes in each side and fasten with three screws to form a tube.

Bend three tabs on the bottom of the shield outward to allow attachment to the ceiling firestop.

Bend the remaining bottom tabs inward 90º to maintain the air space between the pipe and the shield. Set the shield on the ceiling firestop and attach to the firestop.

Bend all tabs inward 90º around the top of the shield. These tabs must be used to prevent blown insulation from getting between the shield and vent pipe, and to maintain air space clearance.

BEND ALL TABS INWARD 90° TO MAINTAIN CLEARANCE AND PREVENT INSULATION FROM FALLING INSIDE

INSERT 3

SCREWS

Figure 8.9 Attic Insulation Shield

BEND 3 TABS

OUTWARD TO FASTEN TO CEILING FIRESTOP-BEND REMAINING TABS INWARD 90 DEGREES TO MAINTAIN CLEARANCE

36

Heat & Glo • 8000TR-OAK, 8000TR-OAK-IPI, 8000TRLP-OAKIPI2057-900 Rev. P • 11/08

Image 36
Contents Models 8000TR-OAK 8000TR-OAK-IPI 8000TRLP-OAKIPI What to do if you smell gasCongratulations Homeowner Reference InformationTable of Contents User GuideAppliance Setup TroubleshootingFinishing Reference MaterialsCONDITIONS, Exclusions & Limitation of Liability Limited Lifetime Warranty Listing and Code Approvals Installation of Carbon Monoxide Detectors Requirements for the Commonwealth of MassachusettsGas Fireplace Safety Operating Instructions User GuideYour Fireplace Fixed Glass Assembly Remote Controls, Wall Controls and Wall SwitchesFan Kit optional Clear SpaceLighting Instructions IPI Final inspection byFor Your Safety Read Before Lighting Lighting Instructions Lighting Instructions Standing PilotFrequently Asked Questions After Fireplace is LitMaintenance and Service Maintenance Tasks-HomeownerGlass Cleaning Remote ControlMaintenance Tasks-Qualified Service Technician Gasket Seal and Glass Assembly InspectionVenting LogsEither cobrahead or SIT Getting Started Typical Appliance SystemDesign and Installation Considerations Tools and Supplies NeededInspect Appliance and Components Framing and Clearances Selecting Appliance LocationConstructing the Appliance Chase ClearancesMantel and Wall Projections TOP ViewTermination Locations Vent Termination Minimum ClearancesCovered Alcove Applications Vent Information and Diagrams Approved PipeVent Table Key Use of ElbowsVent Diagrams Top Vent Horizontal Termination One Elbow Two ElbowsV1 Minimum H1 Maximum V1 Minimum H1 + H2 MaximumTop Vent Horizontal Termination Three Elbows Minimum Maximum + V 2 Minimum + H 2 MaximumBreak Here Top Vent Vertical Termination Two Elbows H1 Maximum V1 + V2 MinimumPage Rear Vent Horizontal Termination Two Elbows H1 Maximum V1 Minimum H1+ H2 MaximumH1 Maximum V1 Minimum H2+ H3 H1+ H2+ H3 Maximum Rear Vent Vertical Termination One Elbow H1+ H2 Maximum V1 MinimumRear Vent Vertical Termination Three Elbows Vent Clearances and Framing Pipe Clearances to CombustiblesHeat Shield Above First 900 Elbow Wall Penetration Framing Combustible Wall PenetrationNon-Combustible Wall Penetration Install the Ceiling Firestop Pipe DVPInstall Attic Insulation Shield Flat Ceiling InstallationVaulted Ceiling Installation Appliance Preparation Top VentProceed to Section Rear Vent Securing and Leveling the Appliance 11 Proper positioning, leveling and securing of an applianceCompleting Grate Set-up Checking Pilot PlateInstalling Vent Pipe Attach Vent to the Firebox AssemblyAssemble Vent Sections Assemble Pipe SectionsAssemble Slip Sections Secure the Vent Sections10 Rotate Seams for Disassembly Disassemble Vent SectionsInstall Metal Roof Flashing Assemble and Install Storm CollarInstall RF4-8 Apply Sealant TOP & Partial SidesInstall Vertical Termination Cap Heat Shield Requirements for Horizontal TerminationInstall Horizontal Termination Cap Ansi Z223.1 and CAN/CGA-B149 installation codesGas Information Fuel ConversionGas Pressure Gas ConnectionWiring Requirements Intellifire Ignition System WiringStanding Pilot Ignition System Wiring Optional Accessories RequirementsElectrical Service and Repair Intellifire Pilot Ignition IPI Wiring DiagramJunction Box Installation Wall Switch Installation for Fan OptionalFinishing Facing MaterialCombustible Mantel Legs or Wall Projections Appliance Setup Install the Log Assembly LOG TabsPage Install the Mesh Install Trim and/or SurroundAir Shutter Setting Air Shutter SettingsTroubleshooting Symptom Possible Causes Corrective ActionStanding Pilot Ignition System Troubleshooting Symptom Possible Cause Corrective ActionIntellifire Ignition System Ues to spark, and main Appliance Dimension Diagram Reference MaterialsVent Components Diagrams DVP vent componentsDVP-TRAP1 DVP-TRAP2 DVP-TRAPK1 DVP-TRAPK2 DVP-HPC1 DVP-HPC2 RF6M RF12M DVP-TV Log Set Assembly Service PartsService Parts List 8000TR-OAK, 8000TR-OAK-IPI StockedAt Depot 8000TR-OAK-IPI 8000TR-OAK Contact Information

8000TRLP-OAKIPI, 8000TR-OAK-IPI, 8000TR-OAK specifications

Hearth and Home Technologies is renowned for its innovative approach to home heating solutions, and their series of fireplaces is a testament to that commitment. Among their popular offerings are the 8000TR-OAK, 8000TR-OAK-IPI, and 8000TRLP-OAKIPI models. Each of these fireplaces is designed to deliver warmth, ambiance, and advanced technology wrapped in a refined aesthetic.

The 8000TR-OAK model features an impressive viewing area, which allows the flickering flames to be the centerpiece of any room. With a heating capacity that efficiently warms up spaces, it is ideal for both contemporary and traditional settings. One of its main highlights is the realistic log set that adds to the authenticity of the fire experience. The stove's design is not only visually appealing but also engineered for high efficiency, reducing carbon footprints while maximizing heat output.

Moving to the 8000TR-OAK-IPI, this model integrates the innovative IntelliFire Ignition system, ensuring that operation is reliable and energy-efficient. The IPI system allows the fireplace to be controlled with ease, offering both manual and remote-operation options. This model maintains the authentic charm of the traditional fireplace while incorporating modern technology. The 8000TR-OAK-IPI also boasts multiple flame settings, giving users the flexibility to adjust their experience based on mood or season, along with an outstanding ability to maintain heat with minimal energy consumption.

The 8000TRLP-OAKIPI takes versatility a step further by operating on liquid propane, making it ideal for homes that are not connected to natural gas lines. Along with the IntelliFire Ignition technology, this model ensures exceptional efficiency, making it a premium choice for those who prioritize sustainable energy solutions. The design retains the luxurious oak finish found in its counterparts, ensuring it complements any interior decor seamlessly.

All three models share a range of characteristics that set them apart: a robust construction that promises longevity, an array of customizable options, and built-in safety features that instill confidence in operation. They also offer a variety of venting options, giving homeowners flexibility in installation. With Hearth and Home Technologies’ commitment to quality and innovation, the 8000 series fireplaces provide not just heat, but a captivating focal point for home gatherings.