Honeywell AC-140-7, AC-220-7 manual FP-4 Freeze Protection KIT, Section Introduction

Page 1

February 2008

P/N 32-0228

REV . B

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

FOR

FP-4 FREEZE PROTECTION KIT

P/N 83-0763

FOR TURBO-COOL AFTERCOOLERS

MODELS AC-140-7 thru AC-220-7

(230V-3PH-60Hz & 460V-3PH-60Hz)

WARNING

BEFORE STARTING INSTALLATION OR MAINTENANCE PROCEDURES, TURN OFF ELECTRICAL POWER AND COMPLETELY DEPRESSURIZE THE AFTERCOOLER. FAILURE TO HEED THIS WARNING MAY RESULT IN SERIOUS PERSONAL INJURY AND/OR DAMAGE TO THE UNIT.

NEVER REMOVE, REPAIR, OR REPLACE ANY ITEM ON THE AFTERCOOLER WHILE IT IS PRESSURIZED.

WHEN INSTALLING THIS KIT, ALWAYS COMPLY WITH THE NATIONAL ELECTRICAL CODE AND ALL OTHER APPLICABLE FEDERAL, STATE AND LOCAL CODES.

SECTION 1

INTRODUCTION

 

 

1.1 DESCRIPTION OF OPERATION

The FP-4 freeze protection kit is designed to prevent aftercooler freeze up when the ambient temperature is near or below freezing, 32oF (0oC).

The FP-4 has a two stage solid state temperature controller. The controller is mounted inside a Nema 4 enclosure. The controller is used to energize a control relay which is rated to handle the load of the aftercooler fan at the various voltages.

The linear platinum temperature sensor and thermowell mount into the piping between the outlet manifold of the aftercooler and the separator. When the temperature of the com- pressed air system at the aftercooler outlet falls to 35OF, the controller will automatically turn off of the fan. The controller is set for a 10oF dead band to prevent rapid cycling (fan will turn off at 35OF and on at 45oF).

A 12 foot heat tape and 30 feet of insulation wrap are provided to wrap around the separator. The heat tape is equipped with its own internal temperature control. The heat tape and insula- tion will provide additional freeze up protection.

1.2THIS KIT INCLUDES:

1.Control box

2.12'long heat tape, w/ thermostat

3.30'long roll of insulation wrap

4.Copper 1/2" NPT thermowell w/clip

5.Cord grip connector

6.Linear platinum sensor

7.2'of 3/8" flexible conduit

8.Three (3) seal fittings for connectors

9.3/8" conduit straight connector

10.3/8" 90 degree elbow connector

11.1" x 1/2" NPT bushing

12.Four (4) #12-14 x 1" self tapping screws

13.Heat Condictive Compound

FIGURE 1-A ITEMS INCLUDED WITH THIS KIT

PAGE 1

Image 1
Contents Section Introduction FP-4 Freeze Protection KITSection InstallationInstalling the Conduit Control BOX Component Layout and Wiring Diagram Section InstallationOperation Setting the ControllerTroubleshooting Procedures Section TroubleshootingReplacement Parts Section Replacement PartsPER VAN AIR Terms and Conditions of Sale Section WarrantyProduct Description Controller Dimensions Temperature SensorsaAccessories Installation and Setup Before InstallationWiring MountingTemperature Sensor Wiring Wiring Connections AccessTemperature Sensor Wire Type and Size Multiple Parallel SensorsController Wiring Method Controller WiringController Wiring Details Wiring Applications ExamplesDescription of Wiring Terminal Connections Terminal Label Connection Terminal Label Description SensorsWiring for four-stage control 24 Vac input 24 Vac load Wiring for ML7984 valve actuator Wiring for three Series 90 Modutrol Motors Temperature Sensor Calibration Power LossCheckout Foota MΩ/ft Rating 200 ft 500 ft 000 ftInterface Overview Using the LCD Panel InterfaceHome Screen Using the Menus Accessing the MenusSetup Menu Programming, Scheduling, and Summary MenusCooling Mode Setpoint and Differential Heating Mode Setpoint and DifferentialProgramming Setpoint and DifferentialProgramming the T775A/B/M Controller Entering Program ModeProgram Menu for Outputs Sensor Differential or Throttling RangeHEAT/COOL Setback Exiting Program ModeProgram Next Output Mod or Relay Setup Procedure Setup Advanced OptionsEntering Setup Mode Setting up the SensorsUnits F or C Sensor aCalibrate the sensor Label the sensor inputSensor B Exit Sensor a SetupCalibrate LabelLimit Sensor B only HI Limit or LOW Limit Sensor B onlySetting up the Modulating Outputs Setting up the OutputsThrottling Range Sensor B only MIN OUT % Type of output signalIntegral Exit ScheduleUSE Sched OptionsDI Options digital input options MIN OFF minimum off time for all relaysShow RT show run time hours Setting up the Relays Exit Options SetupType standard or floating Floating Relay Menu Derivative modulating/floating relay only Reset RT run time hoursSetup Outputs Relay Exit Exit Setup ModeScheduling Entering Schedule ModeCreating a Schedule SET Date SET TimeDaylight daylight saving time Mon-Fri Schedule Defaults Setting Individual Schedules1. E1 Setpt setpoint for event Exit exit from selected time period settings Exiting Scheduling Mode2. E1 Time time for event 3. E2 Setpoint setpoint for eventErrors and Diagnostics TroubleshootingError Message Diagnostic MessagesEmissions Compliance Safety ComplianceImmunity Compliance FCC Compliance StatementDOC T775A/B/M Series 2000 Controller

AC-220-7, AC-140-7 specifications

The Honeywell AC-140-7 and AC-220-7 are advanced air conditioning units that exemplify modern air conditioning technology, delivering both comfort and efficiency. Designed for varying space requirements, these units cater to both residential and light commercial settings, providing versatile solutions for climate control.

The AC-140-7 model is particularly known for its compact design, making it suitable for smaller spaces without sacrificing performance. It delivers an impressive cooling output, effectively maintaining comfortable indoor temperatures even during the hottest months. The system utilizes a high-efficiency compressor that operates quietly, ensuring minimal disruption to daily activities. Additionally, the AC-140-7 features an advanced air filtration system that helps to improve indoor air quality by capturing dust, allergens, and other particulates.

In contrast, the AC-220-7 is designed for larger spaces, providing robust cooling capacity. It incorporates multiple fan speeds and advanced thermostatic controls, allowing users to customize their cooling experience according to their preferences and requirements. One of the standout characteristics of the AC-220-7 is its energy efficiency, with a high Seasonal Energy Efficiency Ratio (SEER) rating, which is crucial for reducing energy costs while maintaining optimal performance.

Both models are equipped with state-of-the-art technologies, including smart diagnostic features that help users troubleshoot issues quickly and efficiently. This capability not only enhances the user experience but also prolongs the lifespan of the units. Furthermore, these units are easy to install and maintain, with accessible components for service and cleaning.

A critical characteristic of the Honeywell AC-140-7 and AC-220-7 is their environmentally friendly refrigerants, which align with modern environmental regulations. This aspect makes them a responsible choice for environmentally conscious consumers.

In summary, the Honeywell AC-140-7 and AC-220-7 units are excellent examples of innovation in air conditioning solutions. With their combination of efficiency, advanced features, and quiet operation, these models represent a significant investment in comfort and sustainability for any space. Whether cooling a small room or a larger area, Honeywell’s engineering excellence ensures that users enjoy effective climate control tailored to their needs.