Honeywell AC-140-7, AC-220-7 manual Throttling Range Sensor B only, Setting up the Outputs

Page 29

2. SETUP (ADVANCED OPTIONS)

T775A/B/M SERIES 2000 CONTROLLER

SETUP

SENSORS

SENSOR B

SETUP

SENSORS SENSOR B

UNITS CALIBRATE LABEL LIMIT

HI LIMIT

THROT RNG

EXIT

SETUP

SENSORS

SENSOR B

THROT RNG

10 oF

ENTER

VALUE FOR

SENSOR B

THROTLING

RANGE

M24510

2.2.4.2. THROTTLING RANGE (Sensor B only)

The throttling range for the modulating high or low limit positions the setpoint at the end of the throttling range. For example, with a high (Heat) limit at Sensor B of 200°F and a throttling range of 10°F, the modulating output controlling Sensor A begins to throttle back at 190°F, and fully closes at 200°F. Conversely, the throttling range for the low limit begins above the Cooling setpoint in the same manner.

1.

From the Limit menu, use the T button to highlight

 

THROT RNG.

2.

Use the S and T buttons to increase/decrease the

 

desired value for the Throttling Range.

 

Default = 0

3.

Press the X button to accept the value and return to

 

the Limit menu.

4.

Press the W button to exit the Limit menu.

Fig. 44. Setup - Sensors - Sensor B - Throttling

Range.

5. Press the W button to exit the Sensors menu and

return to the Setup menu.

SETUP

OUTPUTS

SETUP

OUTPUTS

MOD 1

MOD 2

#RELAYS OPTIONS RELAY 1 RELAY 2 RELAY 3 RELAY 4 EXIT

M24511

2.3. Setting up the Outputs

1.From the Setup menu, use the Sand T buttons to highlight OUTPUTS.

2.Press the X button to display the Outputs menu.

NOTE: The menus (e.g. the Outputs menu shown here) can display only those relays that are defined in Setup (see page 24). For example, if you config- ure only two relays, then only two relays display on the appropriate menus.

The following procedures set up each modulating output

Fig. 45. Setup - Outputs Menu.

and relay output.

SETUP OUTPUTS

MOD 1

SETUP

OUTPUTS

MOD 1

TYPE

MIN OUT %

INTEGRAL

DERIVATIV

SCHEDULE

RESET

EXIT

M24512

2.3.1. Setting up the Modulating Outputs

1.From the Output menu, use the S and T buttons to highlight the desired modulating output (MOD 1 or MOD 2).

2.Press the X button to display the selected MOD menu.

NOTE: Modulating outputs are not available on the T775A and T775B controller models. If you are setting up one of these controllers, skip to “2.3.2. NBR OF RELAYS” on page 24.

Fig. 46. Setup - Outputs - Modulating Output Menu.

Use the remaining procedures, beginning with “2.3.1.1. TYPE (of output signal)”, to set up each modulating output. If you have two modulating outputs, repeat these procedures for each modulating output.

21

62-0254–03

Image 29
Contents Section Introduction FP-4 Freeze Protection KITSection InstallationInstalling the Conduit Control BOX Component Layout and Wiring Diagram Section InstallationOperation Setting the ControllerTroubleshooting Procedures Section TroubleshootingReplacement Parts Section Replacement PartsPER VAN AIR Terms and Conditions of Sale Section WarrantyProduct Description Accessories Temperature SensorsaController Dimensions Installation and Setup Before InstallationWiring MountingTemperature Sensor Wiring Wiring Connections AccessTemperature Sensor Wire Type and Size Multiple Parallel SensorsController Wiring Method Controller WiringController Wiring Details Wiring Applications ExamplesDescription of Wiring Terminal Connections Terminal Label Connection Terminal Label Description SensorsWiring for four-stage control 24 Vac input 24 Vac load Wiring for ML7984 valve actuator Wiring for three Series 90 Modutrol Motors Temperature Sensor Calibration Power LossCheckout Foota MΩ/ft Rating 200 ft 500 ft 000 ftHome Screen Using the LCD Panel InterfaceInterface Overview Using the Menus Accessing the MenusSetup Menu Programming, Scheduling, and Summary MenusCooling Mode Setpoint and Differential Heating Mode Setpoint and DifferentialProgramming Setpoint and DifferentialProgram Menu for Outputs Entering Program ModeProgramming the T775A/B/M Controller HEAT/COOL Differential or Throttling RangeSensor Program Next Output Mod or Relay Exiting Program ModeSetback Setup Procedure Setup Advanced OptionsEntering Setup Mode Setting up the SensorsUnits F or C Sensor aCalibrate the sensor Label the sensor inputSensor B Exit Sensor a SetupCalibrate LabelLimit Sensor B only HI Limit or LOW Limit Sensor B onlyThrottling Range Sensor B only Setting up the OutputsSetting up the Modulating Outputs Integral Type of output signalMIN OUT % Exit ScheduleUSE Sched OptionsShow RT show run time hours MIN OFF minimum off time for all relaysDI Options digital input options Type standard or floating Exit Options SetupSetting up the Relays Floating Relay Menu Derivative modulating/floating relay only Reset RT run time hoursSetup Outputs Relay Exit Exit Setup ModeCreating a Schedule Entering Schedule ModeScheduling Daylight daylight saving time SET TimeSET Date 1. E1 Setpt setpoint for event Setting Individual SchedulesMon-Fri Schedule Defaults Exit exit from selected time period settings Exiting Scheduling Mode2. E1 Time time for event 3. E2 Setpoint setpoint for eventErrors and Diagnostics TroubleshootingError Message Diagnostic MessagesEmissions Compliance Safety ComplianceImmunity Compliance FCC Compliance StatementDOC T775A/B/M Series 2000 Controller

AC-220-7, AC-140-7 specifications

The Honeywell AC-140-7 and AC-220-7 are advanced air conditioning units that exemplify modern air conditioning technology, delivering both comfort and efficiency. Designed for varying space requirements, these units cater to both residential and light commercial settings, providing versatile solutions for climate control.

The AC-140-7 model is particularly known for its compact design, making it suitable for smaller spaces without sacrificing performance. It delivers an impressive cooling output, effectively maintaining comfortable indoor temperatures even during the hottest months. The system utilizes a high-efficiency compressor that operates quietly, ensuring minimal disruption to daily activities. Additionally, the AC-140-7 features an advanced air filtration system that helps to improve indoor air quality by capturing dust, allergens, and other particulates.

In contrast, the AC-220-7 is designed for larger spaces, providing robust cooling capacity. It incorporates multiple fan speeds and advanced thermostatic controls, allowing users to customize their cooling experience according to their preferences and requirements. One of the standout characteristics of the AC-220-7 is its energy efficiency, with a high Seasonal Energy Efficiency Ratio (SEER) rating, which is crucial for reducing energy costs while maintaining optimal performance.

Both models are equipped with state-of-the-art technologies, including smart diagnostic features that help users troubleshoot issues quickly and efficiently. This capability not only enhances the user experience but also prolongs the lifespan of the units. Furthermore, these units are easy to install and maintain, with accessible components for service and cleaning.

A critical characteristic of the Honeywell AC-140-7 and AC-220-7 is their environmentally friendly refrigerants, which align with modern environmental regulations. This aspect makes them a responsible choice for environmentally conscious consumers.

In summary, the Honeywell AC-140-7 and AC-220-7 units are excellent examples of innovation in air conditioning solutions. With their combination of efficiency, advanced features, and quiet operation, these models represent a significant investment in comfort and sustainability for any space. Whether cooling a small room or a larger area, Honeywell’s engineering excellence ensures that users enjoy effective climate control tailored to their needs.