Honeywell AC-140-7 MIN OFF minimum off time for all relays, DI Options digital input options

Page 33

2. SETUP (ADVANCED OPTIONS)

T775A/B/M SERIES 2000 CONTROLLER

SETUP

OUTPUTS OPTIONS

MIN OFF

SETUP

OUTPUTS

OPTIONS

MIN OFF

0SEC

ENTER

 

MINIMUM

 

OFF TIME

 

FOR RELAYS

M24522

2.3.3.2.MIN OFF (minimum off time for all relays)

This is the minimum number of seconds of “off time” for all relays.

1.Press the X button to display the Min Off value.

2.Use the S and T buttons to increase/decrease the desired number of seconds from 0 to 990 seconds in 10 second increments.

Default: 0 (zero)

Range: 0 to 990 seconds

3.Press the X button to accept the seconds and display the DI OPTIONS.

Fig. 56. Setup - Outputs - Options - Min Off Time.

NOTES:

1.The minimum off time applies to all relay outputs.

2.When minimum off time is active, relays waiting to be energized display a flashing square underneath the relay number on the home screen.

3.If the minimum off time is not equal to zero (0), the minimum off time activates at power- up. To manually override, press the W button at any time.

SETUP

OUTPUTS OPTIONS

DI OPTS

SETUP

OUTPUTS

OPTIONS

DI OPTS

DISABLE

SETBACK

IGNORE

SELECT DI

 

OPTIONS

 

FOR

 

OUTPUTS

M24523

 

2.3.3.3.DI OPTIONS (digital input options)

The DI Option you select applies to all outputs. This option overrides any Setpoint/Setback values entered in the Schedule.

1.Press the X button to display the DI Option selec- tions.

2.Use the S and T buttons to highlight DISABLE, SETBACK, or IGNORE.

Default: DISABLE

3.Press the X button to accept the value and display the SHOW RT option.

Fig. 57. Setup - Outputs - Options - DI Options.

When the digital input (DI) closes, all outputs follow the DI option value (Disable, Setback, or Ignore):

DISABLE disables the outputs; relays return to de- energized state and Mod outputs return to 0% output.

SETBACK enables a setback temperature value to be programmed for each output.

To program the Setback temperature, see Fig. 32 on page 16.

IGNORE causes the digital input to have no effect on the Relay or Mod outputs.

SETUP

OUTPUTS OPTIONS

SHOW RT

SETUP

OUTPUTS

OPTIONS

SHOW RT

YES

NO

USE

 

RUNTIME

 

FOR

 

RELAYS

M24524

2.3.3.4.SHOW RT (show run time hours)

1.Press the X button to display the Show RT values.

2.Use the S and T buttons to select YES or NO. Default: YES

3.Press the X button to accept the value and return to the Options menu.

Selecting YES shows the RT (run time) hours for each relay on the home screen displays.

NOTE: Run times can be reset to zero for each individ- ual relay. You must do this for each relay that

Fig. 58. Setup - Outputs - Options - Show Runtime.

you want to reset to zero. See “2.3.4.3. RESET RT (run time hours)” on page 28.

25

62-0254–03

Image 33
Contents Section Introduction FP-4 Freeze Protection KITSection InstallationInstalling the Conduit Control BOX Component Layout and Wiring Diagram Section InstallationOperation Setting the ControllerTroubleshooting Procedures Section TroubleshootingReplacement Parts Section Replacement PartsPER VAN AIR Terms and Conditions of Sale Section WarrantyProduct Description Temperature Sensorsa Controller DimensionsAccessories Installation and Setup Before InstallationWiring MountingTemperature Sensor Wiring Wiring Connections AccessTemperature Sensor Wire Type and Size Multiple Parallel SensorsController Wiring Method Controller WiringController Wiring Details Wiring Applications ExamplesDescription of Wiring Terminal Connections Terminal Label Connection Terminal Label Description SensorsWiring for four-stage control 24 Vac input 24 Vac load Wiring for ML7984 valve actuator Wiring for three Series 90 Modutrol Motors Temperature Sensor Calibration Power LossCheckout Foota MΩ/ft Rating 200 ft 500 ft 000 ftUsing the LCD Panel Interface Interface OverviewHome Screen Using the Menus Accessing the MenusSetup Menu Programming, Scheduling, and Summary MenusCooling Mode Setpoint and Differential Heating Mode Setpoint and DifferentialProgramming Setpoint and DifferentialEntering Program Mode Programming the T775A/B/M ControllerProgram Menu for Outputs Differential or Throttling Range SensorHEAT/COOL Exiting Program Mode SetbackProgram Next Output Mod or Relay Setup Procedure Setup Advanced OptionsEntering Setup Mode Setting up the SensorsUnits F or C Sensor aCalibrate the sensor Label the sensor inputSensor B Exit Sensor a SetupCalibrate LabelLimit Sensor B only HI Limit or LOW Limit Sensor B onlySetting up the Outputs Setting up the Modulating OutputsThrottling Range Sensor B only Type of output signal MIN OUT %Integral Exit ScheduleUSE Sched OptionsMIN OFF minimum off time for all relays DI Options digital input optionsShow RT show run time hours Exit Options Setup Setting up the RelaysType standard or floating Floating Relay Menu Derivative modulating/floating relay only Reset RT run time hoursSetup Outputs Relay Exit Exit Setup ModeEntering Schedule Mode SchedulingCreating a Schedule SET Time SET DateDaylight daylight saving time Setting Individual Schedules Mon-Fri Schedule Defaults1. E1 Setpt setpoint for event Exit exit from selected time period settings Exiting Scheduling Mode2. E1 Time time for event 3. E2 Setpoint setpoint for eventErrors and Diagnostics TroubleshootingError Message Diagnostic MessagesEmissions Compliance Safety ComplianceImmunity Compliance FCC Compliance StatementDOC T775A/B/M Series 2000 Controller

AC-220-7, AC-140-7 specifications

The Honeywell AC-140-7 and AC-220-7 are advanced air conditioning units that exemplify modern air conditioning technology, delivering both comfort and efficiency. Designed for varying space requirements, these units cater to both residential and light commercial settings, providing versatile solutions for climate control.

The AC-140-7 model is particularly known for its compact design, making it suitable for smaller spaces without sacrificing performance. It delivers an impressive cooling output, effectively maintaining comfortable indoor temperatures even during the hottest months. The system utilizes a high-efficiency compressor that operates quietly, ensuring minimal disruption to daily activities. Additionally, the AC-140-7 features an advanced air filtration system that helps to improve indoor air quality by capturing dust, allergens, and other particulates.

In contrast, the AC-220-7 is designed for larger spaces, providing robust cooling capacity. It incorporates multiple fan speeds and advanced thermostatic controls, allowing users to customize their cooling experience according to their preferences and requirements. One of the standout characteristics of the AC-220-7 is its energy efficiency, with a high Seasonal Energy Efficiency Ratio (SEER) rating, which is crucial for reducing energy costs while maintaining optimal performance.

Both models are equipped with state-of-the-art technologies, including smart diagnostic features that help users troubleshoot issues quickly and efficiently. This capability not only enhances the user experience but also prolongs the lifespan of the units. Furthermore, these units are easy to install and maintain, with accessible components for service and cleaning.

A critical characteristic of the Honeywell AC-140-7 and AC-220-7 is their environmentally friendly refrigerants, which align with modern environmental regulations. This aspect makes them a responsible choice for environmentally conscious consumers.

In summary, the Honeywell AC-140-7 and AC-220-7 units are excellent examples of innovation in air conditioning solutions. With their combination of efficiency, advanced features, and quiet operation, these models represent a significant investment in comfort and sustainability for any space. Whether cooling a small room or a larger area, Honeywell’s engineering excellence ensures that users enjoy effective climate control tailored to their needs.