A03188
Fig. 8—Large Decorative Backplate
A03192
Fig. 9—Decorative Backplate Assembly
8.Match and connect thermostat wires to proper terminals on User Interface backplate. See wiring diagram Fig. 12, 13, and 14.
A — Green = Data A
B — Yellow = Data B
C — White = 24VAC (Com) D — Red = 24VAC (Hot)
NOTE: It is not mandatory that the above color code be used, but each ABCD connection in the system MUST be wired consis- tently. A separate ABCD Connector comes inside packaging and should be used when connecting to furnace (or fan coil). Ensure connector is inserted properly into circuit board. (See Fig. 10)
A B C D
A03193
Fig. 10—4–Wire ABCD Connector
CAUTION: ELECTRICAL OPERATION HAZARD Failure to follow this caution may result in equipment damage or improper operation.
Improper wiring of the ABCD connector will cause the Evolution Zone System to operate improperly. Check to make sure all wiring is correct before proceeding with installation or turning on power.
9.Push any excess wire into the wall. Seal hole in wall to prevent any air leaks. Leaks can affect operation.
10.Attach Evolution Zone Control™ to the mounting plastic by lining up the plastic guides on the back of the control with the opening on the mounting plastic and push on.
11.Perform installation of all other system equipment (i.e. zone sensors, dampers, humidifier, ventilator, UV lights, etc.)
12.Turn on power to equipment.
Zone | ZONE | Fan Button |
Button |
|
|
Display Screen (LCD)
ButtonRight-Side
Button
Time |
|
|
|
|
|
Button |
|
|
| HEAT | Heat Button |
|
|
|
|
| |
Hold |
|
|
|
| Cool Button |
Button | HOLD |
|
| COOL | |
|
|
|
|
| |
|
|
|
|
| Temperature |
|
|
|
|
| |
|
|
| SCROLL |
| System |
|
|
|
|
| |
Schedule & Vacation | SCHEDULE | VACATION | BASIC | ADVANCED | On/Off Button |
|
|
|
| Basic & Advanced | |
Program Buttons |
|
|
|
| |
| PROGRAM | SETUPS | Setup Buttons | ||
Up/Down |
|
|
|
|
|
Scroll Buttons |
|
|
|
|
|
| Schedule | Vacation | Basic | Advanced | Flip Down |
| to program | to start/end | to set time, | for all other | |
| temperature | vacation | humidity | settings | Door |
schedule
Scroll
up & down
A04038
Fig. 11—Functional Overview
EQUIPMENT WIRING DIAGRAMS:
See wiring diagrams Fig. 12, 13, and 14 for connecting the Evolution Zone Control and Smart Sensors to the Damper Control Module. More information regarding Damper Control
See wiring diagram Fig. 12 which includes a
See wiring diagram Fig. 13 for connecting a
See wiring diagram Fig. 14 for connecting an FE fan coil with a
NOTE: For other applications not listed, refer to the Network Interface Module (NIM) Installation Instructions.
HUMIDIFIER CONNECTION — A 24vac bypass or fan powered humidifier may be installed.
NOTE: Do Not Use a traditional humidistat to control humidifier operation. If a humidifier is installed, let the Evolution™ Zone Control operate humidifier.
Bypass Humidifiers — A bypass humidifier should be wired directly to the furnace or fan coil HUM and 24vac COM terminals. The Evolution Zone Control will automatically energize the HUM output during a call for humidification.
Fan Powered Humidifiers — Most fan powered humidifiers produce internal 24vac in order to energize upon a switch or contact closure. For this application, a 24vac N.O. Isolation Relay (DPST) MUST be used to prevent mixing the internal humidifier power with the indoor equipment transformer. Applying 24vac