COOLING SEQUENCE
Compressor Operation
The cooling capacity of the WV series is controlled by loading or unloading the compressor. On a call for cooling, the unloader solenoid is energized for one second to ensure pressure equalization in the compressor. The compressor contactor, RLY 2, is then energized and the compressor will start. A PI control loop then calculates the compressor capacity needed to reach set point and modulates the compressor . Modulation range is from 20% to 100% capacity. Modulation is accomplished by a pulse width modulated signal from OUT 8 which energizes the solid state relay (SSR) and energizes or
20% load means 0 VDC for 3.0 seconds and 5 VDC for 12.0 seconds from OUT 8.
30% load means 0 VDC for 4.5 seconds and 5 VDC for 10.5 seconds from OUT 8.
40% load means 0 VDC for 6.0 seconds and 5 VDC for 9.0 seconds from OUT 8.
50% load means 0 VDC for 7.5 seconds and 5 VDC for 7.5 seconds from OUT 8.
60% load means 0 VDC for 9.0 seconds and 5 VDC for 6.0 seconds from OUT 8.
70% load means 0 VDC for 10.5 seconds and 5 VDC for 4.5 seconds from OUT 8.
80% load means 0 VDC for 12.0 seconds and 5 VDC for 3.0 seconds from OUT 8.
90% load means 0 VDC for 13.5 seconds and 5 VDC for 1.5 seconds from OUT 8.
100% load means 0 VDC for 15 seconds and 5 VDC for 0.0 seconds from OUT 8.
Outdoor Temperature Sensor
A sensor probe projects out the bottom of the ECU control box into the outdoor section, and this provides input for the outdoor fan sequences below 55F and above 115F described under Outdoor Fan Motor Operation.
Discharge Temperature Sensor
This sensor is mounted on the compressor discharge line and protects the compressor against overheating. It opens at 250F and closes at 200F.
HEATING SEQUENCE
On a call for heating, if the space temperature falls 1°F below setpoint, the first stage of heating, RLY 4, will cycle ON. If the space temperature falls 3°F below setpoint, the second stage of heating, RLY 5, will cycle ON. Indoor Blower airflow is maintained at the Rated unit airflow at all times during heating.
Control |
|
|
|
| |
Device |
| Normal | Abnormal | ||
|
|
|
| ||
Indoor | Red LED | lit, Green LED | No Red LED, and no Green | ||
|
|
|
| ||
Motor | flashes long and short | ||||
flashes when | |||||
Blower | flashes when Fan is called | ||||
present from Signal to | |||||
Control | for, | ||||
Common. Jumper is on P. | |||||
Board | Common. Jumper is on P. | ||||
| |||||
|
|
| |||
Outdoor | Red LED not lit. Green long | Red LED lit, and no Green | |||
Motor | and short flashes when 2- | ||||
flashes when | |||||
Fan | 10Vdc present from Signal | ||||
present from Signal to | |||||
Control | to Common on board. | ||||
Common. Jumper is on P. | |||||
Board | Jumper is on P. | ||||
| |||||
|
|
| |||
| Red LED lit when 24Vac | Red LED not lit. 5Vdc not | |||
5Vdc | present. 5Vdc present at | present at solid Red and | |||
Power | solid Red and solid Black | solid Black wires. | |||
Supply | wires. Both jumpers on Half. | Both jumpers on Half. | |||
| 3A 250V fuse. | Check 3A fuse. | |||
|
|
|
|
|
LEAD/LAG SEQUENCE
The digital controllers can be used for dual units used in a redundant application by using the scheduling function as follows:
1.The controllers should be mounted side by side so that they are in the same temperature zone.
2.The time setting on both controllers need to be synchronized to the same time of day. NOTE: there is a
3.Set one controller #1 to be Occupied for a
4.Set Occupied cooling setpoint the same for each controller, and Unoccupied the same for each. 4°F difference is suggested.
5.Set controllers to “Auto” mode of operation. Example:
1.Both Unit #1 and #2 have Occupied setpoint of 74°F and Unoccupied setpoint of 78°F
2.Unit #1 set for Occupied from 1:00 a.m. to 1:00 p.m. & Unoccupied from 1:00 p.m. to 1:00 a.m.
3.Unit #2 set for Unoccupied from 1:00 a.m. to 1:00 p.m. & Occupied from 1:00 p.m. to 1:00 a.m.
4.Every 12 hours the units will swap position as being the lead unit, and the lag unit is available for back up operation at the higher temperature should the situation ever arise.
Manual | |
Page | 17 of 23 |