Bard W6RV1, W3RV1, W5LV1 Installation Instructions, Wall Mounting Information, Mounting the Unit

Page 6

INSTALLATION INSTRUCTIONS

WALL MOUNTING INFORMATION

1.Two holes for the supply and return air openings must be cut through the wall as shown in Figures 3A & 3B.

2.On wood frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration.

3.Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installed unit.

MOUNTING THE UNIT

1.These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides. A bottom mounting bracket, attached to skid for shipping, is provided for ease of installation, but is not required.

2.The supply air duct flange and the first 3 feet of supply air duct require a minimum of 1/4 inch clearance to combustible material for model series W3R/LV, W5R/LV and W6R/LV. However, it is generally recommended that a 1-inch clearance is used for ease of installation and maintaining the required clearance to combustible material. See Figures 3A & 3B for details on opening sizes.

3.Locate and mark lag bolt locations and bottom mounting bracket location. See Figures 3A & 3B.

4.Mount bottom mounting bracket.

5.Hook top rain flashing, attached to front - right of supply flange for shipping, under back bend of top.

WARNING

Failure to provide the 1/4 inch clearance between the supply duct and a combustible surface for the first 3 feet of duct can result in fire causing damage, injury or death.

6.Position unit in opening and secure with 5/16 lag bolts; use 7/8 inch diameter flat washers on the lag bolts.

7.Secure rain flashing to wall and caulk across entire length of top. See Figures 3A & 3B.

8.For additional mounting rigidity, the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance if combustible wall.

9.On side-by-side installations, maintain a minimum of 20 inches clearance on right side to allow access to control panel and heat strips, and to allow proper airflow to the outdoor coil. Additional clearance may be required to meet local or national codes.

Clearances Required for Service Access and Adequate Condenser Airflow

MODELS

LEFT SIDE

RIGHT SIDE

W3RV1

15"

20"

W3LV1

20"

15"

W5RV1, W6RV1

20"

20"

W5LV1, W6LV1

20"

20"

NOTE: For side by side installation of two (2) W*RV models there must be 20" between units. This can be reduced to 15" by using a W*LV model (left side compressor and controls) for the left unit and W*R (right side compressor and controls) for right unit.

See Specification Sheet.

Minimum Clearances Required to Combustible Materials

MODELS

SUPPLY AIR DUCT

CABINET

FIRST THREE FEET

W3R/LV1

1/4"

0"

W5R/LV1

1/4"

0"

W6R/LV1

 

 

Manual 2100-538E Page 6 of 23

Image 6
Contents Bard Manufacturing Company, Inc Bryan, OhioContents Getting Other Information and Publications For More INFORMATION, Contact These PublishersWall Mount General Information Shipping DamageGeneral Fresh AIR Intake Duct WorkFilters Condensate DrainInstallation Instructions Wall Mounting InformationMounting the Unit Right Unit Left Unit Supply Return W3RV1Mountinginstructions W5RV1, W5LV1, W6RV1, W6LV1 Electric Heat Clearance W3RV1, W3LV1, W5RV1, W5LV1, W6RV1, W6LV1Wall Mounting Instructions If RequiredCommon Wall Mounting Installations Free AIR Flow Ducted Supply No Duct Return AT UnitTAP Range Wiring Main PowerWiring LOW Voltage Wiring 240 253 208 220Safety Practices Topping OFF System ChargeThree Phase Scroll Compressor Start UP Information Important Installer NoteHigh Pressure Switch Phase MonitorSequence of Operation Modes of OperationLEAD/LAG Sequence Cooling SequencePressure Service Ports Compressor Control ModuleRemoval of FAN Shroud TroubleshootingFAN Blade Setting Dimensions Refrigerant ChargeCooling Pressure Table 23.9 26.7 29.4 32.2 35.0 37.8 40.6 43.3 46.1 48.9 51.7 55.0Electrical Specifications W*RV / W*LV Series Recommended Airflow Maximum ESP of Operation Electric Heat onlyElectric Heat Vent & Control Options W3R/LV W5R/LV W6R/LV