Bard W3RV1, W6RV1, W5LV1 Troubleshooting, FAN Blade Setting Dimensions, Removal of FAN Shroud

Page 19

TROUBLESHOOTING

FAN BLADE SETTING DIMENSIONS

Shown in Figure 8 is the correct fan blade setting for proper air delivery across the outdoor coil. Refer to Table 1 for unit specific dimension.

Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly.

FIGURE 8

FAN BLADE SETTING

MIS-1724

TABLE 1

FAN BLADE DIMENSION

Model

Dimension

A

 

 

 

W3RV1

1.25"

W3LV1

 

 

 

W5RV1

1.75"

W5LV1

 

 

 

W6RV1

1.75"

W6LV1

 

 

 

REMOVAL OF FAN SHROUD

1.Disconnect all power to the unit.

2.Remove the screws holding both grilles, one on each side of unit, and remove grilles.

3.Unwire condenser fan motor.

4.Remove the bolts and nuts holding the condenser fan motor bracket to the fan shroud.

5.Slide the condenser fan motor and bracket to the rear of the condenser section.

6.Remove screws holding fan shroud to condenser and bottom support plate.

7.Slide fan shroud out the left side of the unit.

8.Reverse steps to install.

R-410A

REFRIGERANT CHARGE

This unit was charged at the factory with the quantity of refrigerant listed on the serial plate. AHRI capacity and efficiency ratings were determined by testing with this refrigerant charge quantity.

The following pressure tables show nominal pressures for the units. Since many installation specific situations can affect the pressure readings, this information should only be used by certified technicians as a guide for evaluating proper system performance. They shall not be used to adjust charge. If charge is in doubt, reclaim, evacuate and recharge the unit to the serial plate charge.

Manual

2100-538E

Page

19 of 23

Image 19
Contents Bryan, Ohio Bard Manufacturing Company, IncContents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsShipping Damage Wall Mount General InformationGeneral Condensate Drain Duct WorkFilters Fresh AIR IntakeWall Mounting Information Installation InstructionsMounting the Unit Supply Return W3RV1 Right Unit Left UnitMountinginstructions W5RV1, W5LV1, W6RV1, W6LV1 W3RV1, W3LV1, W5RV1, W5LV1, W6RV1, W6LV1 Electric Heat ClearanceIf Required Wall Mounting InstructionsFree AIR Flow Ducted Supply No Duct Return AT Unit Common Wall Mounting Installations240 253 208 220 Wiring Main PowerWiring LOW Voltage Wiring TAP RangeTopping OFF System Charge Safety PracticesPhase Monitor Important Installer NoteHigh Pressure Switch Three Phase Scroll Compressor Start UP InformationModes of Operation Sequence of OperationCooling Sequence LEAD/LAG SequenceCompressor Control Module Pressure Service PortsRefrigerant Charge TroubleshootingFAN Blade Setting Dimensions Removal of FAN Shroud23.9 26.7 29.4 32.2 35.0 37.8 40.6 43.3 46.1 48.9 51.7 55.0 Cooling Pressure TableElectrical Specifications W*RV / W*LV Series Maximum ESP of Operation Electric Heat only Recommended AirflowElectric Heat W3R/LV W5R/LV W6R/LV Vent & Control Options