Aprilaire 8570 installation instructions Optional Install AN Automatic Humidifier Control AHC

Page 23

(7) OPTIONAL – INSTALL AN AUTOMATIC HUMIDIFIER CONTROL (AHC)

Note: The AHC uses its own outdoor temperature sensor, which is read by the thermostat. If an AHC is to be installed, do not wire an outdoor temperature sensor to the ODT terminal of the thermostat.

1. Mount the AHC and its outdoor temperature sensor.

Follow the directions provided with the AHC except do not mount the AHC temperature sensor in a fresh air intake. The temperature sensor must be mounted outside.

Maximum wire length from AHC to thermostat is 300 feet.

The AHC must have constant power. DO NOT power the

AHC through furnace accessory terminals.

DO NOT operate the AHC in Manual Mode – this will result in the outdoor temperature shown on the thermostat to always be 20°F.

2. Run a 2-wire cable from the AHC to the thermostat.

CAUTION

Do not run the wire along side line voltage (120 VAC) or higher lines as this can cause erratic readings.

3.Wire the AHC to the thermostat (see Figure 8).

• Strip 1/4" of insulation from the ends of the wires.

Connect the I- terminal of the AHC to the I- terminal of the thermostat.

Connect the I+ terminal of the AHC to the I+ terminal of the thermostat.

4.You will need to power up the thermostat to verify the connection. Refer to step 5 of THERMOSTAT START UP on page 24.

5.After completing the thermostat installation, you will also need to verify proper operation of the AHC – see AHC installation instructions for details on how this is done.

WARNING

Improper installation may cause serious

 

injury from electrical shock. Do not power up humidifier before completing the thermostat installation.

- 19 -

Image 23
Contents Instructions Table of Contents Check Cooling Operation CustomizeSafety Instructions Model 8570 Specifications Single-Stage Heat Pump Two-Stage Heat Pump Wire RequirementsTwo-Stage Furnace/AC Radiant 1st Stage HeatKeep the thermostat 18 from an outside wall Select a Mounting LocationOpen the Thermostat Mount the Thermostat Base to the Wall AHC Set to HP when installed with heat pumps Run a cable with the correct number of wires Wire the Thermostat to the Hvac EquipmentDiagram 1 Single-Stage Furnace and AC Diagram 2 Two-Stage Furnace and AC Diagram 3 Two-Stage Roof Top Unit Diagram 4 Boiler with AC Page Diagram 6 Single-Stage Heat Pump Diagram 7 Two-Stage Heat Pump Mount above anticipated snow line Mount the outdoor temperature sensor see Figure85.4 230.6163.8 117.6IDS ODT CIR GND Mount the AHC and its outdoor temperature sensor Optional Install AN Automatic Humidifier Control AHC+ I- R C H ODT Mount the indoor temperature sensor IDS ODT CIR GND Thermostat Startup Stand Alone Applications From the Main Screen, press the Info button Check FAN OperationTroubleshooting AHC Connection Check Heating Operation Troubleshooting Heating Operation To Cool and make a call for cooling Troubleshooting Cooling OperationThermostat does not call for cooling To Emergency Heat and make a call for heat Troubleshooting Emergency Heat OperationCheck Emergency Heat Operation Heat Pumps Only Differential Customize the Application SettingsOffset Progressive RecoveryDisplay will show the ADV. Settings Menu Range is 0F to 40F Balance Points Heat Pumps onlyTo delete a number, press the Back button Input Dealer Contact InformationTo delete a character, press the Back button Blower Extension for Humidity Control Press the Menu button Press the Call Dealer button Press the Reset buttonDP 10006198 B2203358B BOX 1467 MADISON, WI