(3) MOUNT THE THERMOSTAT BASE TO THE WALL

1.Place the wire opening in the base over the wire entry hole in the wall. Level the base (for appearance only) and mark the screw locations. See Figure 4.

2.Use the supplied screws and wall anchors to mount the thermostat to the wall. It is recommended that wall anchors be used for installation to drywall/sheet rock.

Drill a 3/16" hole for wall anchors.

Drill a 3/32" starter hole for screws only.

3.For junction box mounting, screws are field supplied. The thermostat can be installed on a vertical j-box.

4.Seal the wire entry hole(s) with caulk, drywall putty or insulation to prevent drafts from inside the wall cavity from affecting thermostat performance.

Figure 4

 

 

W2

 

W1

 

RH

 

R

 

RC

 

G

IDS

Y1

ODT

Y2

CIR

B

GND

ZA

O

ZB

I+

C

I-

CAUTION

Minimize wire entry hole size and seal the hole – drafts from inside the wall could affect temperature readings.

- 5 -

Image 9
Contents Instructions Table of Contents Check Cooling Operation CustomizeSafety Instructions Model 8570 Specifications Two-Stage Furnace/AC Wire RequirementsRadiant 1st Stage Heat Single-Stage Heat Pump Two-Stage Heat PumpKeep the thermostat 18 from an outside wall Select a Mounting LocationOpen the Thermostat Mount the Thermostat Base to the Wall AHC Set to HP when installed with heat pumps Run a cable with the correct number of wires Wire the Thermostat to the Hvac EquipmentDiagram 1 Single-Stage Furnace and AC Diagram 2 Two-Stage Furnace and AC Diagram 3 Two-Stage Roof Top Unit Diagram 4 Boiler with AC Page Diagram 6 Single-Stage Heat Pump Diagram 7 Two-Stage Heat Pump Mount above anticipated snow line Mount the outdoor temperature sensor see Figure163.8 230.6117.6 85.4IDS ODT CIR GND Mount the AHC and its outdoor temperature sensor Optional Install AN Automatic Humidifier Control AHC+ I- R C H ODT Mount the indoor temperature sensor IDS ODT CIR GND Thermostat Startup Stand Alone Applications From the Main Screen, press the Info button Check FAN OperationTroubleshooting AHC Connection Check Heating Operation Troubleshooting Heating Operation Troubleshooting Cooling Operation Thermostat does not call for coolingTo Cool and make a call for cooling Troubleshooting Emergency Heat Operation Check Emergency Heat Operation Heat Pumps OnlyTo Emergency Heat and make a call for heat Differential Customize the Application SettingsProgressive Recovery Display will show the ADV. Settings MenuOffset Range is 0F to 40F Balance Points Heat Pumps onlyInput Dealer Contact Information To delete a character, press the Back buttonTo delete a number, press the Back button Blower Extension for Humidity Control Press the Menu button Press the Call Dealer button Press the Reset buttonDP 10006198 B2203358B BOX 1467 MADISON, WI