6. CHECK HEATING OPERATION

Notes:

1.To avoid the minimum off times during system checkout, always start and end the check out procedure in the OFF mode.

2.Do not operate heat pumps in the heating mode at high outdoor temperatures for extended periods of time.

Set the thermostat to the OFF mode.

Set the thermostat to the HEAT mode:

The B terminal will energize when in the Heat mode.

Raise the heat setting to 5° higher than the room temperature to initiate a 1st stage heat call. The mode display will change from "HEAT MODE" to "HEATING", which will flash when the thermostat is calling for heat:

Furnace, Boiler: W1 (and G if GAS/ELEC dip switch is set in the ELEC position) terminals will energize.

Heat pumps: Y1 and G terminals will energize.

Wait for 2nd Stage:

Furnace, Boiler: Minimum-on time for 1st stage is 2 minutes.

W1, W2 (and G if GAS/ELEC dip switch set to the ELEC position) will energize.

Heat pumps: Minimum-on time for 1st stage is 4 minutes.

Y1, W1 and G terminals will energize if SINGLE/MULTI dip switch set to SINGLE and ELEC/GAS dip switch set to ELEC.

Y1, Y2 and G terminals will energize if SINGLE/MULTI dip switch set to MULTI.

W1 will energize if SINGLE/MULTI set to SINGLE and ELEC/GAS set to GAS.

Wait 4 minutes for 3rd Stage (multi-stage compressor heat pump systems only):

Y1, Y2, W1 and G terminals will energize if SINGLE/MULTI set to MULTI and ELEC/GAS set to ELEC.

W1 will energize if SINGLE/MULTI set to MULTI and ELEC/GAS set to GAS.

Set the thermostat to the OFF mode.

- 26 -

Image 30
Contents Instructions Table of Contents Customize Check Cooling OperationSafety Instructions Model 8570 Specifications Radiant 1st Stage Heat Wire RequirementsTwo-Stage Furnace/AC Single-Stage Heat Pump Two-Stage Heat PumpSelect a Mounting Location Keep the thermostat 18 from an outside wallOpen the Thermostat Mount the Thermostat Base to the Wall AHC Set to HP when installed with heat pumps Wire the Thermostat to the Hvac Equipment Run a cable with the correct number of wiresDiagram 1 Single-Stage Furnace and AC Diagram 2 Two-Stage Furnace and AC Diagram 3 Two-Stage Roof Top Unit Diagram 4 Boiler with AC Page Diagram 6 Single-Stage Heat Pump Diagram 7 Two-Stage Heat Pump Mount the outdoor temperature sensor see Figure Mount above anticipated snow line117.6 230.6163.8 85.4IDS ODT CIR GND Optional Install AN Automatic Humidifier Control AHC Mount the AHC and its outdoor temperature sensor+ I- R C H ODT Mount the indoor temperature sensor IDS ODT CIR GND Thermostat Startup Stand Alone Applications Check FAN Operation From the Main Screen, press the Info buttonTroubleshooting AHC Connection Check Heating Operation Troubleshooting Heating Operation Troubleshooting Cooling Operation Thermostat does not call for coolingTo Cool and make a call for cooling Troubleshooting Emergency Heat Operation Check Emergency Heat Operation Heat Pumps OnlyTo Emergency Heat and make a call for heat Customize the Application Settings DifferentialProgressive Recovery Display will show the ADV. Settings MenuOffset Balance Points Heat Pumps only Range is 0F to 40FInput Dealer Contact Information To delete a character, press the Back buttonTo delete a number, press the Back button Blower Extension for Humidity Control Press the Call Dealer button Press the Reset button Press the Menu buttonDP 10006198 B2203358B BOX 1467 MADISON, WI