Aprilaire 8570 Check FAN Operation, From the Main Screen, press the Info button

Page 28

NOTE: Refer to the Owner’s Manual for thermostat operating instructions.

1.PLACE THE THERMOSTAT ON THE BASE.

2.TURN ON POWER TO THE HVAC SYSTEM.

The display will show the Aprilaire screen for approximately 5 seconds (up to 10 seconds if installed as part of a Model 6504 Intelligent Zone System).

After this initial screen the thermostat will enter operational mode.

3.VERIFY OUTDOOR TEMPERATURE SENSOR CONNECTION (if optional outdoor temperature sensor installed).

If an outdoor temperature sensor has been installed and is operational, an outdoor temperature will appear on main display.

4.CHECK FAN OPERATION

• Turn on the fan (set to ON).

The thermostat G terminal will energize and the system blower will start. The Fan Status on the display will show “FAN ON.”

If an AHC has been installed, allow the fan to operate for no less than 40 seconds. If an AHC is not part of this installation, you can turn the fan off at any time. A humidity value can be displayed only after at least 40 seconds of blower run-time to ensure the humidity reading is representative of the room air.

Turn the fan off (set to AUTO).

5.VERIFY AHC CONNECTION (if optional Automatic Humidifier Control installed).

Ensure that the AHC has power (the green status light on the AHC should be on) and make sure the AHC is functioning properly – see AHC installation procedure for start up and diagnostics.

From the Main Screen, press the “INFO” button.

The outdoor temperature and relative humidity will be displayed for five seconds after which the contact screen will be displayed (see page 33 for additional information on the contact screen).

When the humidifier is operating, the message “HUMIDIFIER ON” appears at the message center, alternating with the time and date and any other currently active messages.

- 24 -

Image 28
Contents Instructions Table of Contents Customize Check Cooling OperationSafety Instructions Model 8570 Specifications Wire Requirements Two-Stage Furnace/ACRadiant 1st Stage Heat Single-Stage Heat Pump Two-Stage Heat PumpSelect a Mounting Location Keep the thermostat 18 from an outside wallOpen the Thermostat Mount the Thermostat Base to the Wall AHC Set to HP when installed with heat pumps Wire the Thermostat to the Hvac Equipment Run a cable with the correct number of wiresDiagram 1 Single-Stage Furnace and AC Diagram 2 Two-Stage Furnace and AC Diagram 3 Two-Stage Roof Top Unit Diagram 4 Boiler with AC Page Diagram 6 Single-Stage Heat Pump Diagram 7 Two-Stage Heat Pump Mount the outdoor temperature sensor see Figure Mount above anticipated snow line230.6 163.8117.6 85.4IDS ODT CIR GND Optional Install AN Automatic Humidifier Control AHC Mount the AHC and its outdoor temperature sensor+ I- R C H ODT Mount the indoor temperature sensor IDS ODT CIR GND Thermostat Startup Stand Alone Applications Check FAN Operation From the Main Screen, press the Info buttonTroubleshooting AHC Connection Check Heating Operation Troubleshooting Heating Operation Thermostat does not call for cooling Troubleshooting Cooling OperationTo Cool and make a call for cooling Check Emergency Heat Operation Heat Pumps Only Troubleshooting Emergency Heat OperationTo Emergency Heat and make a call for heat Customize the Application Settings DifferentialDisplay will show the ADV. Settings Menu Progressive RecoveryOffset Balance Points Heat Pumps only Range is 0F to 40FTo delete a character, press the Back button Input Dealer Contact InformationTo delete a number, press the Back button Blower Extension for Humidity Control Press the Call Dealer button Press the Reset button Press the Menu buttonDP 10006198 B2203358B BOX 1467 MADISON, WI
Related manuals
Manual 25 pages 10.1 Kb