8.CHECK EMERGENCY HEAT OPERATION (Heat Pumps Only)

Notes:

1.To avoid the minimum off times during system checkout, always start the check out procedure in the OFF mode.

Set the thermostat to the OFF mode:

Set the thermostat to the EMERGENCY HEAT (EMERG) mode:

The B terminal will energize when in the Emergency Heat mode.

Raise the heat setting to 5° higher than the room temperature to initiate a heat call. The mode display will change from “E-HEAT MODE” to “HEATING”, which will flash when the thermostat is calling for heat:

W1 and W2 (and G if GAS/ELEC dip switch is set in the ELEC position) terminals will energize.

Set the thermostat to the OFF mode.

TROUBLESHOOTING – EMERGENCY HEAT OPERATION

Symptom

Cause

 

 

Thermostat does not call for heat

Minimum-off times. Change the mode to OFF first, then change the mode

 

to EMERGENCY HEAT and make a call for heat.

 

 

Emergency Heat does not come on at all

RH terminal not connected – see wiring diagrams.

 

Heating equipment power not on.

 

 

 

Fan comes on before heat starts, or

Change position of ELEC/GAS dip switch – ELEC for electric heat systems

(fan on with heat call) or to GAS for fossil fuel systems where the fan is

Fan does not come on with heat

controlled internally by the heating equipment.

 

 

 

- 29 -

Image 33
Contents Instructions Table of Contents Check Cooling Operation CustomizeSafety Instructions Model 8570 Specifications Two-Stage Furnace/AC Wire RequirementsRadiant 1st Stage Heat Single-Stage Heat Pump Two-Stage Heat PumpKeep the thermostat 18 from an outside wall Select a Mounting LocationOpen the Thermostat Mount the Thermostat Base to the Wall AHC Set to HP when installed with heat pumps Run a cable with the correct number of wires Wire the Thermostat to the Hvac EquipmentDiagram 1 Single-Stage Furnace and AC Diagram 2 Two-Stage Furnace and AC Diagram 3 Two-Stage Roof Top Unit Diagram 4 Boiler with AC Page Diagram 6 Single-Stage Heat Pump Diagram 7 Two-Stage Heat Pump Mount above anticipated snow line Mount the outdoor temperature sensor see Figure163.8 230.6117.6 85.4IDS ODT CIR GND Mount the AHC and its outdoor temperature sensor Optional Install AN Automatic Humidifier Control AHC+ I- R C H ODT Mount the indoor temperature sensor IDS ODT CIR GND Thermostat Startup Stand Alone Applications From the Main Screen, press the Info button Check FAN OperationTroubleshooting AHC Connection Check Heating Operation Troubleshooting Heating Operation Troubleshooting Cooling Operation Thermostat does not call for coolingTo Cool and make a call for cooling Troubleshooting Emergency Heat Operation Check Emergency Heat Operation Heat Pumps OnlyTo Emergency Heat and make a call for heat Differential Customize the Application SettingsProgressive Recovery Display will show the ADV. Settings MenuOffset Range is 0F to 40F Balance Points Heat Pumps onlyInput Dealer Contact Information To delete a character, press the Back buttonTo delete a number, press the Back button Blower Extension for Humidity Control Press the Menu button Press the Call Dealer button Press the Reset buttonDP 10006198 B2203358B BOX 1467 MADISON, WI