Hearth and Home Technologies SC60 owner manual Framing & Clearances, Select Fireplace Location

Page 18

6 Framing & Clearances

A. Select Fireplace Location

F

 

G

E

 

 

 

 

 

B

 

 

A

 

 

H

 

Across a

In an exterior chase

BC

or projecting into a

corner

garage

D

Note:1/2 in. (13 mm) min. distance from fireplace to combustible materials.

Note:In addition to these framing dimensions, also reference the following sections:

Clearances (Section 6.B.)

Mantel Projections (Section 11.E.)

Fireplace Dimensions (Section 13.A.)

G

As a room divider

B

48 in.

(1219 mm)

H

Along a wall

H

 

A

 

B

 

5/8 in. (16 mm) all configurations

G

Model

A

B

C

D

E

F

G

H

SC60

inches

52 1/4

43 1/8

93 3/8

47

24 1/4

66

25

12 in. (305 mm) Minimum from FP

 

 

 

 

 

 

 

 

 

opening to any perpendicular wall.

 

mm

1327

1095

2372

1194

616

1676

635

 

 

Figure 6.1 Fireplace Locations (Framing dimensions shown)

18

Heatilator • SC60 • 32838 Rev X • 10/08

Image 18
Contents Wood Burning Fireplace Hot screen/mesh and glass doors will cause burnsFire Risk Listing Label Information/Location GrateNumber Safety Alert Key Table of ContentsInstaller Guide User GuideHearth & Home Technologies Limited Warranty CONDITIONS, Exclusions & Limitation of LiabilityHeatilator SC60 32838 Rev X 10/08 Non-Combustible Materials Listing and Code ApprovalsAppliance Certification Combustible MaterialsOperating Instructions Your FireplaceHot glass will cause burns Grate Seasoned WoodStarting a Fire FirescreenOptional Components Glass DoorsVented Gas Log Sets & Gas Log Lighters Clear SpaceWood Fuel Disposal of Ashes Maintainance and ServiceChimney Inspection/Cleaning Creosote Formation and Need for RemovalInspect Grate Glass CleaningCheck Firebrick Frequency As desiredTroubleshooting Guide Start Fire Problems Possible Cause SolutionGetting Started Typical Fireplace SystemDesign and Installation Considerations DraftNegative Pressure Locating Fireplace & Chimney Frequently open doors Central heat outlets or returnsTools and Supplies Needed Fireplace System RequirementsInspect Fireplace and Components Framing & Clearances Select Fireplace LocationClearances Clearances to Combustible MaterialsSidewalls/Surrounds Frame the FireplacePosition the Fireplace Installation of FireplaceThings to Consider Place Protective Metal Hearth StripsFt min. from top of uppermost chimney section to air inlet Install Outside Air Kit To service or replace the fan kitChimney Assembly Chimney Requirements Height of Chimney ComponentsUsing Offsets/Returns ExampleInstall Chimney Air Kit Install Ceiling FirestopsAssemble Chimney Sections Install Attic Insulation Shield Prepare Attic Insulation ShieldFollowing steps should be skipped if using a chase Complete InstallationInstall Flashing Cut out Hole in RoofChimney Termination Requirements Flat RoofsChase Installations Construct the ChaseInstall Fireplace & Chimney Install Chase TopInstall Termination Cap ST375 Square Termination CapTS345/TS345P Square Termination Cap Field Constructed Shrouds ShroudsRadiation Shield Open Top Shroud TR342 caps require radiation shieldMailbox Style Shroud radiation shield required Roofed Style Shroud radiation shield requiredFinishing Hearth Extension= 1/k x inches of thickness Finishing Material HX3 or HX4 Hearth Ext or equivilent insulationCombustible Mantel Firebrick Installation 13 Side Brick InstallationWood Burning Inserts AccessoriesGas Log/Lighter Provision Gas Code, Ansi Z223.1Materials Fireplace1321 mm 406 mm Chimney Components Catalog #14-1/2 10-7/8 276 mm Service PartsContact Information