Hearth and Home Technologies SC60 owner manual Chase Installations, Construct the Chase

Page 31

9 Chase Installations

A. Construct the Chase

A chase is a vertical boxlike structure built to enclose the fireplace and/or its vent system. Vertical chimneys that run on the outside of a building must be installed inside a chase.

Construction of the chase may vary with the type of build- ing. These instructions are not substitutes for the require- ments of local building codes. Local building codes MUST be checked.

A chase should be constructed in the manner of all outside walls of the home to prevent cold air drafting problems. The chase should not break the outside build- ing envelope in any manner. All outer walls need to be insulated.

Building codes require false ceiling and ceiling firestops at each floor of the chase or every 10 ft (3.05 m) of clear space to control spread of fire.

Walls, ceiling, base plate and cantilever floor at the first level of the chase should be insulated. See Figure 9.1. Vapor and air infiltration barriers should be installed in the chase as per regional codes for the rest of the home. Ad- ditionally, Hearth & Home Technologies recommends that the inside surfaces be sheet rocked and taped (or the use of an equivalent method) for maximum air tightness.

Round Termination Cap

 

Metal Chase Top

 

 

Ceiling

 

 

Firestop

 

 

False Ceiling

 

 

Attic

 

Tabs

Insulation

 

Shield

 

 

 

 

Ceiling

Insulation in the

 

outside walls

 

Firestop

 

of the chase

 

 

Insulation

Insulation

 

False Ceiling

False Ceiling

 

 

Chimney

 

Figure 9.1

Chase Assembly

 

Gas line holes and other openings should be caulked with high temperature caulk or stuffed with unfaced fiberglass insulation. If the fireplace is being installed on a cement slab, we recommend that in cold climates, a sheet of plywood or other raised platform be placed underneath to prevent conducting cold up into the room.

Three examples of chase applications are shown in Fig- ure 9.2.

1.Fireplace and chimney enclosed in an exterior chase.

2.Chimney offset through exterior wall and enclosed in chase.

3.Chase constructed on roof.

Note: In cooler climates, all chase walls should be insulated.

1

2

3

Figure 9.2 Chase Constructions

WARNING! You must install false ceilings and ceiling

firestops at each floor of the chase or every 10 ft (3.05 m) to control spread of fire.

WARNING! Risk of Fire! DO NOT seal area between fire stop opening and chimney pipe. Restricting air flow around chimney may cause fire.

WARNING! Risk of Fire! You must maintain a minimum 2 in. (51 mm) air space clearance to insulation and other materials surrounding the chimney system.

Insulation and other materials must be firmly secured to prevent accidental contact with chimney system.

The chase must be properly blocked to prevent blown insulation or other combustibles from entering and making contact with fireplace or chimney.

Failure to prevent contact between insulation or other materials and chimney system may cause overheating and fire.

Heatilator • SC60 • 32838 Rev X • 10/08

31

Image 31
Contents Hot screen/mesh and glass doors will cause burns Wood Burning FireplaceFire Risk Grate Listing Label Information/LocationNumber User Guide Table of ContentsInstaller Guide Safety Alert KeyCONDITIONS, Exclusions & Limitation of Liability Hearth & Home Technologies Limited WarrantyHeatilator SC60 32838 Rev X 10/08 Combustible Materials Listing and Code ApprovalsAppliance Certification Non-Combustible MaterialsYour Fireplace Operating InstructionsHot glass will cause burns Firescreen Seasoned WoodStarting a Fire GrateClear Space Glass DoorsVented Gas Log Sets & Gas Log Lighters Optional ComponentsWood Fuel Creosote Formation and Need for Removal Maintainance and ServiceChimney Inspection/Cleaning Disposal of AshesFrequency As desired Glass CleaningCheck Firebrick Inspect GrateStart Fire Problems Possible Cause Solution Troubleshooting GuideTypical Fireplace System Getting StartedDraft Design and Installation ConsiderationsNegative Pressure Frequently open doors Central heat outlets or returns Locating Fireplace & ChimneyFireplace System Requirements Tools and Supplies NeededInspect Fireplace and Components Select Fireplace Location Framing & ClearancesClearances to Combustible Materials ClearancesFrame the Fireplace Sidewalls/SurroundsPlace Protective Metal Hearth Strips Installation of FireplaceThings to Consider Position the FireplaceFt min. from top of uppermost chimney section to air inlet To service or replace the fan kit Install Outside Air KitChimney Assembly Height of Chimney Components Chimney RequirementsExample Using Offsets/ReturnsInstall Ceiling Firestops Install Chimney Air KitAssemble Chimney Sections Prepare Attic Insulation Shield Install Attic Insulation ShieldCut out Hole in Roof Complete InstallationInstall Flashing Following steps should be skipped if using a chaseFlat Roofs Chimney Termination RequirementsConstruct the Chase Chase InstallationsInstall Chase Top Install Fireplace & ChimneyST375 Square Termination Cap Install Termination CapTS345/TS345P Square Termination Cap Open Top Shroud TR342 caps require radiation shield ShroudsRadiation Shield Field Constructed ShroudsRoofed Style Shroud radiation shield required Mailbox Style Shroud radiation shield requiredHearth Extension Finishing= 1/k x inches of thickness HX3 or HX4 Hearth Ext or equivilent insulation Finishing MaterialCombustible Mantel 13 Side Brick Installation Firebrick InstallationGas Code, Ansi Z223.1 AccessoriesGas Log/Lighter Provision Wood Burning InsertsFireplace Materials1321 mm 406 mm Catalog # Chimney Components14-1/2 10-7/8 276 mm Parts ServiceContact Information