Hearth and Home Technologies SC60 owner manual Sidewalls/Surrounds, Frame the Fireplace

Page 20

C. Sidewalls/Surrounds

Adjacent combustible sidewalls must be located a minimum of 12 in. (305 mm) from the fireplace opening.

Combustible and noncombustible mantel legs, surrounds and stub walls may be constructed within the gridded area, Figure 6.3.

10 3/4 in.

[273 mm]

FLUSH

FRONT

50°

angle

 

12 in.

[305 mm]

4 in.

BRICK [102 mm]

FRONT

36 in.

[914 mm]

39°

14 1/2 in.

angle

[368 mm]

42 1/8 in.

[1070 mm]

12 in.

[305 mm]

Figure 6.3 Mantel Leg or Wall Projections (Acceptable on both sides of opening)

D. Frame the Fireplace

Figure 6.4 shows typical framing using combustible materials (2x4 lumber shown).

Observe all required air space clearances to combustible materials as shown in Figure 6.1 & 6.2.

Framing across the top of fireplace must be above top standoffs.

2 in. (51 mm) min. air space clearance from chimney.

Note: Framing must be extended straight up, all the way to the ceiling.

 

Header MUST NOT be notched!

 

 

 

 

 

D = extra space needed for outside air connection.

 

 

 

 

C

If outside air duct has no bend, this dimension may be

 

 

 

 

reduced as long as minimum clearances are met.

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

A

 

 

 

 

 

B

 

 

 

 

 

 

 

Model

A

B*

C**

D

 

 

 

 

SC60

in.

43 1/8

25

41 1/4

8

 

 

 

 

 

 

 

 

 

mm

1095

635

1048

203

 

 

 

* If interior of chase will be drywalled, add the thickness to this measurement.

** Adjust header height for a raised floor under fireplace.

Figure 6.4 Framing the Fireplace

20

Heatilator • SC60 • 32838 Rev X • 10/08

Image 20
Contents Fire Risk Wood Burning FireplaceHot screen/mesh and glass doors will cause burns Number Listing Label Information/LocationGrate Table of Contents Installer GuideSafety Alert Key User GuideHearth & Home Technologies Limited Warranty CONDITIONS, Exclusions & Limitation of LiabilityHeatilator SC60 32838 Rev X 10/08 Listing and Code Approvals Appliance CertificationNon-Combustible Materials Combustible MaterialsHot glass will cause burns Operating InstructionsYour Fireplace Seasoned Wood Starting a FireGrate FirescreenGlass Doors Vented Gas Log Sets & Gas Log LightersOptional Components Clear SpaceWood Fuel Maintainance and Service Chimney Inspection/CleaningDisposal of Ashes Creosote Formation and Need for RemovalGlass Cleaning Check FirebrickInspect Grate Frequency As desiredTroubleshooting Guide Start Fire Problems Possible Cause SolutionGetting Started Typical Fireplace SystemNegative Pressure Design and Installation ConsiderationsDraft Locating Fireplace & Chimney Frequently open doors Central heat outlets or returnsInspect Fireplace and Components Tools and Supplies NeededFireplace System Requirements Framing & Clearances Select Fireplace LocationClearances Clearances to Combustible MaterialsSidewalls/Surrounds Frame the FireplaceInstallation of Fireplace Things to ConsiderPosition the Fireplace Place Protective Metal Hearth StripsFt min. from top of uppermost chimney section to air inlet Install Outside Air Kit To service or replace the fan kitChimney Assembly Chimney Requirements Height of Chimney ComponentsUsing Offsets/Returns ExampleAssemble Chimney Sections Install Chimney Air KitInstall Ceiling Firestops Install Attic Insulation Shield Prepare Attic Insulation ShieldComplete Installation Install FlashingFollowing steps should be skipped if using a chase Cut out Hole in RoofChimney Termination Requirements Flat RoofsChase Installations Construct the ChaseInstall Fireplace & Chimney Install Chase TopInstall Termination Cap ST375 Square Termination CapTS345/TS345P Square Termination Cap Shrouds Radiation ShieldField Constructed Shrouds Open Top Shroud TR342 caps require radiation shieldMailbox Style Shroud radiation shield required Roofed Style Shroud radiation shield required= 1/k x inches of thickness FinishingHearth Extension Finishing Material HX3 or HX4 Hearth Ext or equivilent insulationCombustible Mantel Firebrick Installation 13 Side Brick InstallationAccessories Gas Log/Lighter ProvisionWood Burning Inserts Gas Code, Ansi Z223.1Materials Fireplace1321 mm 406 mm Chimney Components Catalog #14-1/2 10-7/8 276 mm Service PartsContact Information