PLANNING YOUR INSTALLATION

REDUCED MASONRY STRUCTURE CLEARANCE (ALCOVE)

Your Earth Stove can be installed in a masonry struc- ture with reduced clearances if the structure was built to National Building Code for fireplaces and chimneys (UBC 37).

The firebox of the masonry structure must be of ade- quate size to allow a minimum of 6" (152 mm) clear- ance to the sides and top of the stove and 2" (51 mm) clearance to the rear. All stove models must be installed on their original listed legs or base unless otherwise specified by OMNI Testing Laboratory.

FLOOR PROTECTION

This appliance requires a non-combustible floor protection for ember protection. If the floor protection is to be stone, tile, brick, etc., it must be mortared or grouted to form a continu- ous non-combustible surface. If a chimney connector ex- tends horizontally over the floor, protection must cover the floor under the connector and at least 2" (51 mm) to either side.

The floor protection must extend completely beneath the stove and to the front, sides, and rear as indicated:

USA Requirements

16” (406 mm) min. to the front of the fuel door glass

8” (203 mm) min. beyond the sides of the fuel door opening

Canada Requirements

18” (457 mm) min. to the front of the fuel door glass 8” (203 mm) min. beyond the sides of the stove body

STANDARD PARALLEL HEARTH PAD SHOWN

0” - USA 8” – Can.

8” (203 mm)

8” (203 mm)

Canada

Canada

8” - USA

 

8” - USA

 

18”

(457 mm) – Canada

 

16”

(406 mm) - USA

PROTECTED WALL CLEARANCE

Some local codes will allow reduced clearances when the stove is installed adjacent to a protected wall system. The variance must be approved by your local building official. Normally, the protected wall system is defined as a non- combustible material with a minimum of 1" (25.4 mm) air space behind. Check your local building codes or with a qualified installer (Ref. NFPA 211).

OUTSIDE AIR

In all manufactured (mobile) homes and in many site built residences (subject to local code), a stove may be required to use outside air for combustion. A 3” (76 mm) diameter outside air floor duct is available through your dealer.

This appliance utilizes a 3" (76 mm) diameter outside air floor duct (Catalog # 14M66). Outside air can be taken from beneath the home or through an outside wall. The collar for connecting flex to stove in on the underside of the stove as shown here.

PAGE 6

Image 6
Contents EPA Certified Wood Burning Stove Retain These Instructions Reference775000M, Rev. G, 12/03 Important Warnings Table of Contents Planning Your Installation Smoke DetectorsSelecting a Location Alcove Clearances Corner Installation Parallel Alcove ClearanceCombustible Wall Clearance Optional Arch TreatmentStandard Parallel Hearth PAD Shown Reduced Masonry Structure Clearance AlcoveFloor Protection Protected Wall ClearanceManufactured Mobile Homes Only InstallationSecuring the Stove to the Floor Grounding StoveAcceptable Connector Pipe for INSTALLA- Tions Types of ChimneysChimney Inspection Chimney Height Requirements 2’ by 10’ Rule for Vent TerminationDraft Test Procedure Draft RequirementsResidential Standard Manufactured Mobile Home Standard Important NotesSolid-Pak chimney section shall be flush with the inside PenetrationPrimary AIR Control Product Features and ControlsCare and OPERATI0N Fuel Door Door OperationCare and Operation USE Control Settings That Work for YOUHOW to Start and Maintain a Fire BREAK-IN PeriodMaintenance FuelDoor and Glass Gaskets Reinstall Baffle BrickCleaning Blower Intake Servicing GlassTroubleshooting Overfiring Damage Specifications Model 1400HT Description Door Assembly Handle Assembly P/N LB-102214Primary AIR Draft Module Outside Air Floor Duct OAFD-R Blower KitStove-Stat Kit SAFETY/LISTING Label EPA Label Service and Maintenance LOG Ownership RecordsWest Taft Avenue Orange, CA