WP Series
HowtoInstall the Unit
1To prevent vibration and noise, make sure the unit is installed securely and firmly.
2Install the unit where the sunlight does not shine directly on the unit.
3There should be no obstacles, such as a fence and wall, within 20" from the back of the cabinet because it will prevent heat radiation of the condenser.
Restriction of outside air will greatly reduce the cooling efficiency of the air conditioner.
Cooled air
30"~60"
Fence
Awning
Heat radiation
About 1/2"
Over 20"
CAUTION: All side louvers of the cabinet must remain exposed to the outside of the structure.
4Install the unit a little slanted so the back is slightly lower than the front (about 1/2"). This will force condensed water to flow to the outside.
5Install the unit with the bottom about 30"~60" above the floor level.
WindowRequirements
NOTICE : All supporting parts should be secured to firm wood, masonry, or metal.
•This unit is designed for installation in standard double hung windows with actual opening widths from 29"
to 41".
•The top and bottom window sash must open sufficiently to allow a clear vertical opening of 18" from the bottom of the upper sash to the window stool.
Sash
29" to 41"
18" min.
Window
Inner sill
Offset Sill
Exterior
Interior wall
29" min.
(Without frame curtain)
16