SINGLE TEMPERATURE
| VACUUM RELIEF |
|
|
| VALVE |
|
|
| * INSTALL PER |
|
|
| LOCAL CODES |
|
|
CIRCULATING RETURN LINE CONNECTIONS |
|
|
|
WARNING |
| ||
TEMPERED WATER LOOP, IF USED, CONNECT TO POINT "A". |
| ||
STORED TEMPERATURE WATER LOOP, IF USED, CONNECT TO | TEMPERATURE | SETTING SHOULD NOT | |
COLD WATER INLET. | EXCEED SAFE USE TEMPERATURE AT | ||
| FIXTURES. SEE TEMPERATURE REGULATION | ||
| ON PAGE 11. | IF HIGHER PREHEAT | |
CAUTION: IF BUILDING COLD WATER SUPPLY HAS A | TEMPERATURES ARE NECESSARY TO OBTAIN | ||
PREVENTER, CHECK VALVE OR WATER METER WITH CHECK VALVE, | ADEQUATE BOOSTER OUTPUT, ADD AN | ||
PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT | |||
WATER SYSTEM MUST BE PROVIDED. | SUPPLIED TO FIXTURES. |
FIGURE3
In addition to the appliance relief valve, each remote storage tank which may be used in conjunction with this appliance shall also be installed with a properly sized, rated and approved combination temperature (ANSI) and pressure (ASME) relief valve(s).
WARNING
THE PURPOSE OF RELIEF VALVE IS TO AVOID EXCESSIVE PRESSURE OR TEMPERATURE INTO THE STEAM RANGE, WHICH MAY CAUSE SCALDING AT FIXTURES, TANK EXPLOSION, SYSTEM OR HEATER DAMAGE. NO VALVE IS TO BE PLACED BETWEEN THE RELIEF VALVE AND TANK.
Your local code authority may have other specific relief valve requirements.
A DRAIN LINE MUST BE CONNECTED TO THE RELIEF VALVE TO DIRECT DISCHARGE TO A SAFE LOCATION TO AVOID SCALDING OR WATER DAMAGE. THIS LINE MUST NOT BE REDUCED FROM THE SIZE OF THE VALVE OUTLET AND MUST NOT CONTAIN VALVES, RESTRICTIONS NOR SHOULD IT BE LOCATED IN FREEZING AREAS. DO NOT THREAD OR CAP THE END OF THIS LINE. RESTRICTED OR BLOCKED DISCHARGE WILL DEFEAT THE PURPOSE OF THE VALVE AND IS UNSAFE. DISCHARGE LINE SHALL BE INSTALLED TO ALLOW COMPLETE DRAINAGE OF BOTH THE VALVE AND LINE.
See SERVICE INFORMATION section for procedure and precautions.
The type, size and location of the relief valve(s) must be in accordance with local codes. The location of the relief valve shown in Figure 3 is typical. The heater has a factory installed high temperature limit switch.
For circulating heaters, the separate storage vessel must have a temperature and pressure relief valve installed. This valve shall comply with the standard for relief valves and automatic gas shut- off devices for hot water supply systems.
GAS PIPING
Contact your local gas service company to ensure that adequate gas service is available and to review applicable installation codes for your area.
Size the main gas line in accordance with Table 1. The figures shown are for straight lengths of pipe at 0.5 in. W.C. pressure drop, which is considered normal for low pressure systems. Note: Fittings such as elbows, tees and line regulators will add to the pipe pressure drop. Also refer to the latest version of the National Fuel Gas Code. For Canadian installations consult Canadian Installation Code CAN/CSA
WARNING
THE HEATER IS NOT INTENDED FOR OPERATION AT HIGHER THAN 10.5" W.C.(2.61 kPa) - NATURAL GAS, or 13.0" W.C.(3.23 kPa)
IT IS IMPORTANT TO GUARDAGAINST GAS VALVE FOULING FROM CONTAMINANTS IN THE GAS WAYS. SUCH FOULING MAY CAUSE IMPROPER OPERATION, FIRE OR EXPLOSION.
IF COPPER SUPPLY LINES ARE USED THEY MUST BE INTERNALLY TINNED AND CERTIFIED FOR GAS SERVICE. BEFORE ATTACHING THE GAS LINE, BE SURE THAT ALL GAS PIPE IS CLEAN ON THE INSIDE.
TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY LINE, A DIRT LEG (SOMETIMES CALLED SEDIMENT TRAP OR DRIP LEG) MUST BE INCORPORATED IN THE PIPING (SEE FIG. 4). THE DIRT LEG MUST BE READILY ACCESSIBLE AND NOT SUBJECT TO FREEZING CONDITIONS. INSTALL IN ACCORDANCE WITH RECOMMENDATIONS OF SERVING GAS SUPPLIERS. REFER TO THE LATEST VERSION OF THE NATIONAL FUEL GAS CODE. For Canadian installations consult Canadian Installation Code CAN/CSA
7