State Industries SRT80 120NE warranty Relief Valve, Water Line Connections, Closed System

Page 17

Thermometers are installed in the system as a means of detecting the temperature of the outlet water supply.

RELIEF VALVE

This heater is equipped with an approved temperature and pressure relief valve. ASME ratings cover pressure relief. CSA ratings cover release rate with temperature actuation.

FOR SAFE OPERATION OF THE WATER HEATER, THE RELIEF VALVE(S) MUST NOT BE REMOVED OR PLUGGED.

In addition to the appliance relief valve, each remote storage tank which may be used in conjunction with this appliance shall also be installed with a properly sized, rated and approved temperature (ANSI) and pressure (ASME) relief valve(s). This relief valve shall comply with the standard for relief valves and automatic gas shutoff devices for hot water supply systems, ANSI Z21.22.

Your local code authority may have other specific relief valve requirements.

WARNING

THE PURPOSE OF A RELIEF VALVE IS TO AVOID EXCESSIVE PRESSURE OR TEMPERATURE INTO THE STEAM RANGE, WHICH MAY CAUSE SCALDING AT FIXTURES, TANK EXPLOSION, SYSTEM OR HEATER DAMAGE. NO VALVE IS TO BE PLACED BETWEEN THE RELIEF VALVE AND THE TANK.

A DRAIN LINE MUST BE CONNECTED TO THE RELIEF VALVE TO DIRECT DISCHARGE TO A SAFE LOCATION TO AVOID SCALDING OR WATER DAMAGE. THIS LINE MUST NOT BE REDUCED FROM THE SIZE OF THE VALVE OUTLET AND MUST NOT CONTAIN VALVES OR RESTRICTIONS, NOR SHOULD IT BE LOCATED IN FREEZING AREAS. DO NOT THREAD OR CAP THE END OF THIS LINE. RESTRICTED OR BLOCKED DISCHARGE WILL DEFEAT THE PURPOSE OF THE VALVE AND IS UNSAFE. THE DISCHARGE LINE SHALL BE INSTALLED TO ALLOW COMPLETE DRAINAGE OF BOTH THE VALVE AND LINE.

FIGURE 35

WATER LINE CONNECTIONS

This manual provides detailed installation diagrams (see back section of this manual) for typical methods of application for the water heaters.

The water heater may be installed by itself, or with a separate storage tank. When used with a separate storage tank, the circulation may be either by gravity or by means of circulating pump. When a circulating pump is used, it is important to note that the flow rate should be slow so that there will be a minimum of turbulence inside the heater.

CLOSED SYSTEM

CAUTION

A closed system will exist if a check valve (without bypass), pressure reducing valve (without bypass), or a water meter (without

bypass) is installed in the cold water line between the water heater and street main (or well).

Excessive pressure may develop causing premature tank failure or intermittent relief valve operation. This type of failure is not covered by the limited warranty. An expansion tank or a similar device may be required in the inlet supply line between the appliance and the meter or valve to compensate for the thermal expansion of water under supply pressure.

Water heater damage due to installation in a closed system is not covered by the limited warranty. The solution is to install a thermal expansion tank between the check valve and the water heater.

WATER (POTABLE) HEATING AND SPACE HEATING

1.All piping components connected to this unit for space heating applications shall be suitable for use with potable water.

2.Toxic chemicals, such as those used for boiler treatment, shall NEVER be introduced into this system.

3.This unit may never be connected to any existing heating system or component(s) previously used with non-potable water heating appliance.

4.When the system requires water for space heating at temperatures higher than required for domestic water purposes, a tempering valve must be installed. Please refer to installation diagrams on pages 29 through 33 in back of manual for suggested piping arrangements.

WATER HEATER WIRING

IFANYOFTHE ORIGINALWIREAS SUPPLIED WITHTHEAPPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH 105C WIRE OR ITS EQUIVALENT, EXCEPT INTHE BURNER HOUSING. IN THIS CASE USE 200°C WIRE.

THE COMPUTER CONTROL REQUIRES A SOURCE OF STABLE CLEAN ELECTRICITY FOR PROPER OPERATION. INSTALLING THE HEATER ON A BRANCH CIRCUIT THAT HAS ELECTRONIC NOISE, IS SUBJECT TO FLUCTUATIONS IN VOLTAGE LEVEL OR HAS AN APPLIANCE WHICH GENERATES EMF OF RFI INTERFERENCE CAN CAUSE THE CONTROLLER TO MALFUNCTION. A HIGH QUALITY POWER CONDITIONER MUST BE INSTALLED IF THE ABOVE CONDITIONS EXIST. MALFUNCTIONS CAUSED BY A POOR ELECTRICAL SUPPLYARE NOT COVERED UNDER YOUR WARRANTY.

CAUTION

LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION.

CAUTION

VERIFY PROPER OPERATION AFTER SERVICING UNIT.

The controller is wired to the heater. The model and rating plate provides the electrical information needed to size the complete heater branch supply.

All electrical work must be installed in accordance with the National Electrical Code and local requirements.

When installed, the appliance must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, NFPA 70.

NOTE: This controller is polarity sensitive. If the hot and neutral supply voltage is reversed, the controller will not sense flame. Verify polarity before connecting the unit.

17

Image 17
Contents Rooftop Water Heater Model SRT80 120NE GAS Valve Piping Rooftop SRT80-120NE ROUGH-IN-DIMENSIONSOutback Installation InformationForeword Table of ContentsWater Temperature Control FeaturesHigh Limit Switch E.C.O Plumbing Manifold AssemblyFlow Diagram Dishwashing Machine RequirementHOT Return Recirculation Pump Blower Assembly AIR System AssemblyDrain Valve Blower PlenumControl System ON/OFF Switch LOW GAS Pressure Switch OIM Outdoor Interface ModuleWR Ignition Control Board HOT Surface IgniterTank Assembly System Additional Controls Installation InstructionsCabinet Assembly Roof Curb Provide Unit SupportRIG and Place Unit Clearances Outdoor Stand Hard Water AIR RequirementsVenting Pressure SwitchesVent Terminals GAS PipingSystem Connections Relief Valve Water Heater WiringWater Line Connections Closed SystemPage Menu Navigation OperationMenu Tree Sequence of Operation Error CodesFault Conditions Prior to Start UP Initial START-UP Operating InstructionsFilling Cathodic Protection PrecautionsFor Your Safety Read Before Operating General Information MaintenanceDrain Valve and Access Panels Anode Inspection and ReplacementCirculating Pump Vent SystemInstallation Diagrams Page Page Pipe Relief Valve to Open Drain Page TROUBLE-SHOOTING Checklist and Service InformationBlower Motor will not RUN Replacement PartsMotor RUNS, Burner Lights Momentarily Then Locks OUT GAS Fails to Shut OFFKeepthiswarrantypostedadjacenttotheheaterforfuturereference Tennessee Waltz Parkway Ashland CITY, TN