State Industries SRT80 120NE Blower Motor will not RUN, GAS Fails to Shut OFF, Replacement Parts

Page 34

NOTE: ANY BYPASS OR ALTERATION OF THE UNITS SAFETIES WILL RESULT IN VOIDING THEAPPLIANCE WARRANTY.

Before performing any troubleshooting familiarize yourself with the particular appliance.

Refer to the SEQUENCE OF OPERATION on page 21 before continuing.

Make sure the appliance is connected to a 120V AC power supply, manual gas valve is in the ON position, and all electrical connections are secure before continuing to troubleshoot this appliance.

CAUTION

THE WATER HEATER IS POLARITY SENSITIVE. BEFORE APPLYING ELECTRICITY TO THIS HEATER BE CERTAIN THAT SUPPLY NEUTRAL WIRE TO GROUND CHECK INDICATES ZERO VOLTAGE.

BLOWER MOTOR WILL NOT RUN

1.Confirm 120V AC to the controller. Also, to verify correct polarity, check for 120 V AC between hot supply and ground.

If there is no voltage, check for a loose connection where it connects to the controller.

2.If there is 120 volts to the controller, check for loose connections or a locked rotor. If the rotor cannot be freed the motor and blower assembly must be replaced.

MOTOR RUNS, PREPURGE TIME ELAPSES BUT MAIN

FLAME NOT ESTABLISHED.

1.Check to see if main manual gas valve is open.

2.Check for a loose connection at the transformer, or a defective transformer.

3.Check for a loose connection at the gas valve.

4.Check for open pressure switches or open E.C.O. Check for blockage in the intake and exhaust vent hoods. If no blockage is found, check vinyl tubing for cuts or crimps. If this tubing is damaged it must be replaced. If these steps do not eliminate the problem, replace the pressure switches.

5.Check to see if there is resistance across the igniter terminal with an ohmmeter. If there is no continuity, the igniter is broken and should be replaced.

If the igniter appears to function properly, then verify that the inlet pressure is 14" Natural Gas (3 kPa) maximum. The gas valve supplied on this appliance is not designed to open against a higher pressure. At this time also check that the inlet pressure is not lower than the minimal gas supply pressure, as shown in Table 4: that is, for Natural Gas, 6.2" W.C. If the inlet pressure is not within these limits then adjust the supply pressure accordingly.

If the inlet pressure falls within the allowable limits, then verify that the manifold pressure, when the gas is fully open, with the heater running, is as called out in Table 4: that is, 4.5" (1 kPa) W.C. for Natural Gas. If the manifold pressure is not correct then adjust accordingly. See ADJUSTMENT PROCEDURE in OPERATING INSTRUCTIONS selection, page 21, for the manifold pressure adjustment procedure.

6.If the inlet and manifold pressures are within the limits specified in step 5, then reset the appliance. Verify 24V AC at the gas valve during the three (3) second ignition trial, after the igniter reaches operating temperature. If 24V AC at the gas valve is not seen during this period, the controller must be replaced.

If there is 24V AC at the gas valve during the four second ignition trial and the manifold pressure does not increase above 0" W.C. then verify that the manual gas control valve is in the “ON” position. If the valve is in the “ON” position and the previous voltage and gas pressure conditions are met, then the gas valve is defective and must be replaced.

Note that a positive manifold pressure reading of approximately 1.5" (.38 kPa) W.C. is normal during the prepurge portion of the ignition cycle due to the location of the gas orifice.

MOTOR RUNS, BURNER LIGHTS MOMENTARILY,

THEN LOCKS OUT

1.Reset the appliance two more times to ensure that all of the air has been purged from the gas line.

2.If the burner lights momentarily but does not sustain ignition, verify that the inlet pressure is not greater than 14.0" (3.5 kPa) W.C. or lower than the minimal gas supply pressure, as shown in Table 4: that is, 6.0" for Natural Gas. Also, the manifold pressure should rise during the three (3) second trial for ignition. If the manifold pressure is not correct then adjust accordingly. See ADJUSTMENT PROCEDURE in OPERATING INSTRUCTIONS section, page 18, for the manifold pressure adjustment procedure.

3.Check for the reversed polarity in the supply wiring. This controller is polarity sensitive. If the hot and neutral supply wires are reversed, the controller will not sense flame. Reverse the supply wires and try to fire the unit.

NOTE: Always turn off and disconnect main supply wiring before servicing the unit.

4.Check connecting wire to the flame sensor. Verify that the flame sensor has not been damaged in any way.

5.Verify that the air supply is adequate. The air inlet screen or blower wheel may be restricted. Also, check the installation for proper ventilation. See AIR REQUIREMENTS.

6.Check the venting hoods for obstructions. See VENTING.

7.Check for a maximum inlet pressure of 14" Natural Gas (3 kPa), and the manifold pressure as listed in Table 4: that is, for Natural Gas, 4.5". Please note that the manifold pressure listed is the maximum value for the manifold pressure. Do not set the manifold pressure higher than the value shown for your heater in Table 4. Overfiring the heater will result in rough ignition and/ or noisy operation.

8.Confirm that the air inlet screen is free of obstructions.

CAUTION

Do not reach into the burner housing or combustion chamber if the heater is still hot. Allow the heater to cool and always use gloves as the combustion chamber and the burner sleeve and housing can become very hot after operation. Overfiring is a dangerous condition that must be corrected immediately.

GAS FAILS TO SHUT OFF

Check for defective gas valve or thermostat. If operation is incorrect, replace.

REPLACEMENT PARTS

Replacement parts may be ordered through State dealers, authorized servicers or distributors. Refer to the Yellow Pages for where to call or contact the State Water Heaters, 500 Tennessee Waltz Parkway, Ashland City, TN 37015, 1-800-821-2017. When ordering parts be sure to state the quantity, part number and description of the items including the complete model and serial number as it appears on the product. Refer to the parts list for more information.

34

Image 34
Contents Rooftop Water Heater Model SRT80 120NE Rooftop SRT80-120NE ROUGH-IN-DIMENSIONS GAS Valve PipingInstallation Information OutbackTable of Contents ForewordFeatures Water Temperature ControlFlow Diagram Plumbing Manifold AssemblyHigh Limit Switch E.C.O Dishwashing Machine RequirementDrain Valve AIR System AssemblyHOT Return Recirculation Pump Blower Assembly Blower PlenumControl System WR Ignition Control Board LOW GAS Pressure Switch OIM Outdoor Interface ModuleON/OFF Switch HOT Surface IgniterTank Assembly System Cabinet Assembly Installation InstructionsAdditional Controls Provide Unit Support Roof CurbRIG and Place Unit Hard Water Outdoor StandClearances AIR RequirementsVent Terminals Pressure SwitchesVenting GAS PipingSystem Connections Water Line Connections Water Heater WiringRelief Valve Closed SystemPage Operation Menu NavigationMenu Tree Fault Conditions Error CodesSequence of Operation Prior to Start UP Filling Operating InstructionsInitial START-UP Precautions Cathodic ProtectionFor Your Safety Read Before Operating Maintenance General InformationCirculating Pump Anode Inspection and ReplacementDrain Valve and Access Panels Vent SystemInstallation Diagrams Page Page Pipe Relief Valve to Open Drain Page Checklist and Service Information TROUBLE-SHOOTINGMotor RUNS, Burner Lights Momentarily Then Locks OUT Replacement PartsBlower Motor will not RUN GAS Fails to Shut OFFKeepthiswarrantypostedadjacenttotheheaterforfuturereference Tennessee Waltz Parkway Ashland CITY, TN