P68 Low Draft Voltage Adjustment

Fig.22

C o m b u s t i o n Motor Speed Control

Low draft only set point.

The small straight screwdriver slot is plastic; therefore, the unit can be adjusted while in operation.

Draft Meter bolt hole location

On a P68 the draft test hole is under the left rear corner of the firebox.

Fig. 23

Low Draft Voltage Adjustment

These units are pre-tested at the factory with exactly 120 Volts A.C., 60 Hz. They are checked and adjusted for firebox tightness, gasket leakage, motor operation and igniter operation. The P68 is then factory set at a mid-point adjustment and in most cases will not need any adjustments. NOTE: The factory low draft setting may not be correct for the unit's permanent installation conditions.

The control board on the P68 is equipped with a low draft adjustment port. Located on the control face just to the right of the igniter light. This voltage adjustment is provided to allow the unit to be adjusted for the household voltage where the unit is going to be in permanent operation. NOTE: The line voltage varies from area to area and often home to home.

The low draft voltage should be adjusted to achieve the most efficient burn on low burn or "maintenance". This voltage adjustment allows the installer to change the lowvoltage set point approximately 10 volts. This adjustment should be done by the installer during set up because a draft meter reading isrequired to insure proper set up.

If the unit is not adjusted properly, it does not cause a safety concern. If the unit is adjusted too high, only effiency is lost. If the unit is adjusted too low, the low draft pressure switch will not allow the feed motor or the igniter to operate.

A simple draft test should be performed after completing the flue pipe installation. To record the results for future reference:

1.Plug unit into a 120VAC, 60 HZ outlet.

2.Close the hopper lid, front view door, and the ash pan. Neither pellets or a fire are required for this test.

3.With the mode selector in the "OFF" position, turn the feed adjuster to "TEST".

4.Record the high draft_____in W.C. (Normal is -.50 to -.60) The control will be on the High Draft for a total of 2 minutes.

5.After 2 minutes, the combustion motor will go down to low draft and the distribution blower will go on high. Allow approximately 15 seconds to pass for the combustion motor to slow before checking the low draft.

6.If the low draft is between -.35 and -.45, record the reading _____ in W.C. If the reading is higher, slowly turn the set screw counter-clockwise until the draft lowers. If the reading is lower, very slowly turn the set screw clockwise until the draft increases.

NOTE: The test mode alternates from high to low draft every 60 seconds. If more time is needed for draft adjustment, wait until the next low draft cycle. NOTE: In some cases, the draft may not go as low

as -.35 to -.45 even with the set screw completely counter-clockwise, ideally, you should just set it as low as possible.

20P68 Pellet Stove

Image 20
Contents Installation & Operating Manual Safety NoticeP68 Pellet Stove Table of Contents IntroductionImportant Notes Assembly and Installation Door Handle InstallationInstallation InstallingWith outside air installed With outside air installed, 6 feetVenting Addition, the following must be observedVenting Vent PipeOutside Air HRVThroughs #1 Preferred method#2 Preferred method #4 Installing into an existing chimney US only #5 Installing into an existing fireplace chimney US only#7 Installing into an existing chimney US and Canada Minimum flue vent configuration #8 Installing through the ceilingRoom Temperature Mode P68 Automatic IGNITION/OPERATIONStove Temperature Mode Shut Down Procedure Feed Adjuster KnobIgniter Switch toAUTOup position Turn Mode Selector to OFFTurn Feed Adjuster to #4.4 P68 Automatic Start UP P68 Manual IGNITION/OPERATION Room Temperature Mode Stove Temperature Mode Fill hopper with pellets and remove ashes as required.1 Igniter Switch toMANUAL down positionP68 Manual Start UP Status light error messages P68 Automatic Ignition ESP ControlP68 Low Draft Voltage Adjustment Low Draft Voltage AdjustmentRear Shields Room Sensor and Rear Shield InstallationRoom Sensor Installation Maintenance Cleaning the Door GlassCleaning Removing AshesCause a House Fire Soot and FlyAshP68 Maintenance Burn Pot Burn Pot Cleaning and MaintenanceP68 Maintenance Gasket Adjustment P68 Maintenance Cleaning the Feeder Body P68 Trouble-Shooting Cleaning Burn PotP68 Feeder and Specifications SpecificationsOptions Side Heat ShieldsFloor Protector Hopper ExtensionP68 Wiring Diagram P68 Parts List Description Part NumberHarman Gold Warranty Year Limited Warranty Commercial