Bryant 551J installation instructions All units, Convenience Outlets

Page 12

Units Without Disconnect Option

 

 

 

 

1-ph Belt Drive IFM

 

 

 

C

 

C

IFC

 

or

Direct Drive IFM

 

11

23

11

13

13

23

TB

 

 

Disconnect

 

Disconnect

 

 

 

 

 

 

per

 

per

 

 

 

 

 

 

NEC

 

NEC

 

 

 

 

 

208/230-1-60

L1

L2

L3

 

 

 

 

 

208/230-3-60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460-3-60

 

 

 

 

 

 

 

 

575-3-60

 

 

 

 

 

 

 

Units With Disconnect Option

 

551J

L1

 

2

 

 

 

1

 

j

 

4

Optional

 

3

Factory

 

 

Disconnect

 

 

L2

 

 

Wiring

 

 

 

 

Switch

 

 

 

 

L3

 

6

 

 

 

5

 

Disconnect factory test leads; discard.

C10056

Fig. 15 - Power Wiring Connections

Units with Factory-Installed Disconnect —

The factory-installed option disconnect switch is located in a weatherproof enclosure located under the main control box. The manual switch handle is accessible through an opening in the access panel. Discard the factory test leads (see Fig. 15).

!WARNING

FIRE HAZARD

Failure to follow this warning could result in intermittent operation or performance satisfaction.

Do not connect aluminum wire between disconnect switch and 551J unit. Use only copper wire.

(See Fig. 16.)

ELECTRIC

DISCONNECT

SWITCH

COPPER

WIRE ONLY

ALUMINUM

WIRE

A93033

Fig. 16 - Disconnect Switch and Unit

Units Without Factory-Installed Disconnect —

When installing units, provide a disconnect switch per NEC (National Electrical Code) of adequate size. Disconnect sizing data is provided on the unit informative plate. Locate on unit cabinet or within sight of the unit per national or local codes. Do not cover unit informative plate if mounting the disconnect on the unit cabinet.

All units —

All field wiring must comply with NEC and all local codes. Size wire based on MCA (Minimum Circuit Amps) on the unit informative plate. See Fig. 15 and the unit label diagram for power wiring connections to the unit power terminal blocks and equipment ground. Maximum wire size is #2 ga AWG per pole.

Provide a ground-fault and short-circuit over-current protection device (fuse or breaker) per NEC Article 440 (or local codes). Refer to unit informative data plate for MOCP (Maximum Over-current Protection) device size.

All field wiring must comply with the NEC and local requirements.

All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the control transformer must be rewired by moving the black wire with the 1/4-in. female spade connector from the 230-v connection and moving it to the 200-v1/4-in. male terminal on the primary side of the transformer. Refer to unit label diagram for additional information. Field power wires will be connected line-side pressure lugs on the power terminal block or at factory-installed option non-fused disconnect.

NOTE: Check all factory and field electrical connections for tightness. Field-supplied wiring shall conform with the limitations of 63_F (33_C) rise.

Convenience Outlets —

!WARNING

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal injury or death.

Units with convenience outlet circuits may use multiple disconnects. Check convenience outlet for power status before opening unit for service. Locate its disconnect switch, if appropriate, and open it. Tag-out this switch, if necessary.

Two types of convenience outlets are offered on 551J models: Non-powered and unit-powered. Both types provide a 125-volt GFCI (ground-fault circuit-interrupter) duplex receptacle rated at 15-A behind a hinged waterproof access cover, located on the end panel of the unit. See Fig. 17.

12

Image 12
Contents Installation Instructions 551J Unit Dimensional Drawing C10058 Plan for Sequence of Unit Installation Curb-mounted installationOperating Weights Plan for Unit LocationInspect unit Provide Unit SupportRoof Curb Details Field Fabricate Ductwork Rig and Place UnitConvert to Horizontal and Connect Ductwork when required Install Outside Air HoodPositioning on Curb Indoor Coil Access Panel Relocation Install External Condensate Trap and Line Field Power SupplyMake Electrical Connections All units Convenience OutletsConvenience Outlet Location Installing Weatherproof Cover Field Control Wiring Factory-Option Thru-Base ConnectionsUnits without Thru-Base Connections ThermostatHeat Anticipator Settings Electric HeatersHeater Model Number Typical Component Location System ControllerSmoke Detectors Smoke Detector Locations Typical Supply Air Smoke Detector Sensor LocationCompleting Installation of Return Air Smoke Sensor Return Air Detector Shipping PositionRTU-MP control system RTU-MP Multi-Protocol Control BoardRTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs Type of I/O Connection PIN Name Numbers InputsSpace Temperature SPT Sensors 55 Space Temperature Sensor WiringRTU-MP T-56 Sensor Connections SEN Connecting Discrete Inputs Power Exhaust outputCommunication Wiring Protocols General Filter StatusLocal Access RTU-MP Troubleshooting Communication LEDsLEDs LEDs on the RTU-MP show the status of certain functionsUnit Wire/Fuse or Hacr Breaker Sizing Data FLA LRAPwrd C.O 27.8 132 42.0 47/47 Adjust Factory-Installed Options EconoMi$er IV Occupancy SwitchInstall Accessories Pre-Start and Start-Up