Bryant 551J installation instructions Completing Installation of Return Air Smoke Sensor

Page 19

Completing Installation of Return Air Smoke Sensor:

1.Unscrew the two screws holding the Return Air Sensor detector plate. See Fig. 34. Save the screws.

2.Remove the Return Air Sensor and its detector plate.

3.Rotate the detector plate so the sensor is facing outwards and the sampling tube connection is on the bottom. See Fig. 35.

4.Screw the sensor and detector plate into its operating position using screws from Step 1. Make sure the sampling tube connection is on the bottom and the exhaust tube is on the top. See Fig. 35.

5.Connect the flexible tube on the sampling inlet to the sampling tube on the basepan.

Screws

Flexible

Exhaust Tubes

Sample Tube

C08126

Fig. 34 - Return Air Detector Shipping Position

C08127

Fig. 35 - Return Air Sensor Operating Position

Additional Application Data — Refer to Catalog No. HKRNKA-1XA for discussions on additional control features of these smoke detectors including multiple unit coordination.

551J

j

19

Image 19
Contents Installation Instructions 551J Unit Dimensional Drawing C10058 Plan for Unit Location Plan for Sequence of Unit InstallationCurb-mounted installation Operating WeightsProvide Unit Support Inspect unitRoof Curb Details Rig and Place Unit Field Fabricate DuctworkInstall Outside Air Hood Convert to Horizontal and Connect Ductwork when requiredPositioning on Curb Indoor Coil Access Panel Relocation Field Power Supply Install External Condensate Trap and LineMake Electrical Connections Convenience Outlets All unitsConvenience Outlet Location Installing Weatherproof Cover Thermostat Field Control WiringFactory-Option Thru-Base Connections Units without Thru-Base ConnectionsElectric Heaters Heat Anticipator SettingsHeater Model Number Typical Component Location Controller SystemSmoke Detectors Typical Supply Air Smoke Detector Sensor Location Smoke Detector LocationsReturn Air Detector Shipping Position Completing Installation of Return Air Smoke SensorRTU-MP Multi-Protocol Control Board RTU-MP control systemRTU-MP System Control Wiring Diagram Type of I/O Connection PIN Name Numbers Inputs RTU-MP Controller Inputs and Outputs55 Space Temperature Sensor Wiring Space Temperature SPT SensorsRTU-MP T-56 Sensor Connections SEN Filter Status Connecting Discrete InputsPower Exhaust output Communication Wiring Protocols GeneralRTU-MP Troubleshooting Communication LEDs Local AccessLEDs on the RTU-MP show the status of certain functions LEDsFLA LRA Unit Wire/Fuse or Hacr Breaker Sizing DataPwrd C.O 27.8 132 42.0 47/47 EconoMi$er IV Occupancy Switch Adjust Factory-Installed OptionsPre-Start and Start-Up Install Accessories