Step 5 — Field Fabricate Ductwork

Cabinet return-air static pressure (a negative condition) shall not exceed 0.35 in. wg (87 Pa) with economizer or

j0.45 in. wg (112 Pa) without economizer.

For vertical ducted applications, secure all ducts to roof curb and building structure on vertical ducted units. Do not connect ductwork to unit.

Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.

Ducts passing through unconditioned spaces must be insulated and covered with a vapor barrier.

If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.

For units with accessory electric heaters: Horizontal applications require a minimum clearance to combustible surfaces of 1-in (25 mm) from duct for first 12-in (305 mm) away from unit. Vertical applications do not require a minimum clearance around ductwork.

Step 6 — Rig and Place Unit

Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 1 and Fig. 5 for additional information.

Lifting holes are provided in base rails as shown in Fig. 5. Refer to rigging instructions on unit.

Before setting the unit onto the curb, recheck gasketing on curb.

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage.

All panels must be in place when rigging. Unit is not designed for handling by fork truck.

If using top crate as spreader bar, once unit is set, carefully lower wooden crate off building roof top to ground. Ensure that no people or obstructions are below prior to lowering the crate.

C06005

 

MAX WEIGHT

 

 

DIMENSIONS

 

 

UNIT

 

A

 

B

 

C

 

 

 

 

 

 

LB

KG

IN

MM

IN

MM

IN

MM

551J*04A

700

318

74.5

1890

36.5

925

33.5

850

551J*05A

830

377

74.5

1890

36.5

925

41.5

1055

551J*06A

865

393

74.5

1890

36.0

915

41.5

1055

NOTES:

1.Dimensions in ( ) are in millimeters.

2.Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the unit center of gravity. Use wooden top to prevent rigging straps from damaging unit.

Fig. 5 - Rigging Details

8

Image 8
Contents Installation Instructions 551J Unit Dimensional Drawing C10058 Plan for Sequence of Unit Installation Curb-mounted installationOperating Weights Plan for Unit LocationInspect unit Provide Unit SupportRoof Curb Details Field Fabricate Ductwork Rig and Place UnitPositioning on Curb Convert to Horizontal and Connect Ductwork when requiredInstall Outside Air Hood Indoor Coil Access Panel Relocation Make Electrical Connections Install External Condensate Trap and LineField Power Supply All units Convenience OutletsConvenience Outlet Location Installing Weatherproof Cover Field Control Wiring Factory-Option Thru-Base ConnectionsUnits without Thru-Base Connections ThermostatHeater Model Number Heat Anticipator SettingsElectric Heaters Typical Component Location Smoke Detectors SystemController Smoke Detector Locations Typical Supply Air Smoke Detector Sensor LocationCompleting Installation of Return Air Smoke Sensor Return Air Detector Shipping PositionRTU-MP control system RTU-MP Multi-Protocol Control BoardRTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs Type of I/O Connection PIN Name Numbers InputsSpace Temperature SPT Sensors 55 Space Temperature Sensor WiringRTU-MP T-56 Sensor Connections SEN Connecting Discrete Inputs Power Exhaust outputCommunication Wiring Protocols General Filter StatusLocal Access RTU-MP Troubleshooting Communication LEDsLEDs LEDs on the RTU-MP show the status of certain functionsUnit Wire/Fuse or Hacr Breaker Sizing Data FLA LRAPwrd C.O 27.8 132 42.0 47/47 Adjust Factory-Installed Options EconoMi$er IV Occupancy SwitchInstall Accessories Pre-Start and Start-Up