Bryant 551J RTU-MP Controller Inputs and Outputs, Type of I/O Connection PIN Name Numbers Inputs

Page 22

551J

Table 3 – RTU-MP Controller Inputs and Outputs

 

 

 

POINT NAME

BACnet OBJECT

 

TYPE OF I/O

CONNECTION PIN

 

 

 

NAME

 

NUMBERS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INPUTS

 

 

 

 

 

 

 

 

 

Space Temperature Sensor

sptsens

 

AI (10K Thermistor)

J20---1, 2

 

 

 

 

 

 

 

Supply Air Temperature

sat

 

AI (10K Thermistor)

J2---1, 2

 

 

 

 

 

 

 

Local Outside Air Temperature Sensor

oatsens

 

AI (10K Thermistor)

J2---3, 4

 

 

 

 

 

 

 

Space Temperature Offset Pot

sptopot

 

AI (100K Potentiometer)

J20---3

 

 

 

 

 

 

 

Indoor Air Quality

iaq

 

AI (4---20 ma)

J4---2, 3

 

 

 

 

 

 

 

Outdoor Air Quality

oaq

 

AI (4---20 ma)

J4---5, 6

 

 

 

 

 

 

 

Safety Chain Feedback

safety

 

DI (24 VAC)

J1---9

 

 

 

 

 

 

 

Compressor Safety

compstat

 

DI (24 VAC)

J1---2

 

 

 

 

 

 

 

Fire Shutdown

firedown

 

DI (24 VAC)

J1---10

 

 

 

 

 

 

 

Enthalpy Switch

enthalpy

 

DI (24 VAC)

J2---6, 7

 

 

 

 

 

 

j

Humidistat Input Status

humstat

 

DI (24 VAC)

J5---7, 8

 

 

 

 

 

 

 

 

 

 

CONFIGURABLE INPUTS*

 

 

 

 

 

 

 

 

 

 

 

 

Space Relative Humidity

sprh

 

AI (4---20 ma)

J4---2,3 or J4---5,6

 

 

 

 

 

 

 

 

Outside Air Relative Humidity

oarh

 

AI (4---20 ma)

 

 

 

 

 

 

 

 

 

 

Supply Fan Status

fanstat

 

DI (24 VAC)

J5---1,2 or J5---3,4 or

 

 

 

 

 

 

 

 

Filter Status

filtstat

 

DI (24 VAC)

 

 

J5 5,6 or J5---7,8

 

 

 

 

 

 

 

 

Remote Occupancy Input

remocc

 

DI (24 VAC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTPUTS

 

 

 

 

 

 

 

 

Economizer Commanded Position

econocmd

 

4---20ma

J2---5

 

 

 

 

 

 

 

Supply Fan Relay State

sf

 

DO Relay (24VAC , 1A)

J1---4

 

 

 

 

 

 

 

Compressor 1 Relay State

comp_1

 

DO Relay (24VAC , 1A)

J1---8

 

 

 

 

 

 

 

Compressor 2 Relay State

comp_2

 

DO Relay (24VAC , 1A)

J1---7

 

 

 

 

 

 

 

Heat Stage 1 Relay State

heat_1

 

DO Relay (24VAC , 1A)

J1---6

 

 

 

 

 

 

 

Heat Stage 2 Relay State

heat_2

 

DO Relay (24VAC , 1A)

J1---5

 

 

 

 

 

 

 

Power Exhaust Relay State

aux_2

 

DO Relay (24VAC , 1A)

J11---3

 

 

 

 

 

 

 

Dehumidification Relay State

humizer

 

DO Relay (24VAC, 1A)

J11---7, 8

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

AI

---

Analog Input

 

 

 

 

 

AO ---

Analog Output

 

 

 

 

 

DI

---

Discrete Input

 

 

 

 

 

DO ---

Discrete Output

 

 

 

 

*These inputs (if installed) take the place of the default input on the specific channel according to schematic. Parallel pins J5--- 1 = J2--- 6, J5--- 3 = J1--- 10, J5--- 5 = J1--- 2 are used for field--- installation.

The RTU-MP controller requires the use of a Byrant space sensor. A standard thermostat cannot be used with the RTU-MP system.

Supply Air Temperature (SAT) Sensor - On FIOP-equipped 551J unit, the unit is supplied with a supply-air temperature (SAT) sensor (33ZCSENSAT). This sensor is a tubular probe type, approx 6-inches (12.7 mm) in length. It is a nominal 10-k ohm thermistor.

The SAT is factory-wired. The SAT probe is wire-tied to the supply-air opening (on the horizontal opening end) in its shipping position. Remove the sensor for installation. Re-position the sensor in the flange of the supply-air opening or in the supply air duct (as required by local codes). Drill or punch a 1/2-in. hole in the flange or duct. Use two field-supplied, self-drilling screws to secure the

SUPPLY AIR TEMPERATURE

SENSOR

SUPPLY AIR

ROOF CURB

RETURN AIR

C08200

sensor probe in a horizontal orientation. See Fig. 39.

Fig. 39 - Typical Mounting Location for Supply Air Temperature (SAT) Sensor on Small Rooftop Units

22

Image 22
Contents Installation Instructions 551J Unit Dimensional Drawing C10058 Operating Weights Plan for Sequence of Unit InstallationCurb-mounted installation Plan for Unit LocationInspect unit Provide Unit SupportRoof Curb Details Field Fabricate Ductwork Rig and Place UnitInstall Outside Air Hood Convert to Horizontal and Connect Ductwork when requiredPositioning on Curb Indoor Coil Access Panel Relocation Field Power Supply Install External Condensate Trap and LineMake Electrical Connections All units Convenience OutletsConvenience Outlet Location Installing Weatherproof Cover Units without Thru-Base Connections Field Control WiringFactory-Option Thru-Base Connections ThermostatElectric Heaters Heat Anticipator SettingsHeater Model Number Typical Component Location Controller SystemSmoke Detectors Smoke Detector Locations Typical Supply Air Smoke Detector Sensor LocationCompleting Installation of Return Air Smoke Sensor Return Air Detector Shipping PositionRTU-MP control system RTU-MP Multi-Protocol Control BoardRTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs Type of I/O Connection PIN Name Numbers InputsSpace Temperature SPT Sensors 55 Space Temperature Sensor WiringRTU-MP T-56 Sensor Connections SEN Communication Wiring Protocols General Connecting Discrete InputsPower Exhaust output Filter StatusLocal Access RTU-MP Troubleshooting Communication LEDsLEDs LEDs on the RTU-MP show the status of certain functionsUnit Wire/Fuse or Hacr Breaker Sizing Data FLA LRAPwrd C.O 27.8 132 42.0 47/47 Adjust Factory-Installed Options EconoMi$er IV Occupancy SwitchInstall Accessories Pre-Start and Start-Up