Troubleshooting

See the chart below for explanation of error codes that appear in the 3-digit data field of the UPS SETUP LCD Screen, as well as suggested solutions for each error.

This UPS offers a series of Fault and Shutdown codes viewable in the LCD screen to help explain why a UPS shutdown has occurred. Error

&Environmental fault codes include the prefix of “E”. Shutdown codes include the prefix of “S”. See the table below for a complete list- ing of error codes and relevant troubleshooting tips for recovery.

Internal Fault

Error Code

Mode

Description

Solution/Explanation

 

 

 

 

E11

Charger Fault

There are problems with the charger circuit.

If the problem persists, contact Tripp Lite for assistance.

 

 

 

 

E12

Fan Fault

There are problems with the fan.

Check if there is any material to stop the rotating of the

 

 

 

fan. Remove the material. If the problem persists, contact

 

 

 

Tripp Lite for assistance.

 

 

 

 

E13

Over

The inside temperature of the UPS is

Check the UPS to be sure that there is adequate space for

 

Temperature

higher than the limit.

air to circulate near the vents and that the fan is working

 

 

 

properly. Ensure that the UPS is in a 0-40C/32-104F

 

 

 

environment.

 

 

 

 

E14

+/-DC BUS

The internal DC bus voltage is too high or

If the problem persists, contact Tripp Lite for assistance.

 

High/Low

too low.

 

 

 

 

 

E15

BUS OVP

The internal DC bus voltage is too high.

If the problem persists, contact Tripp Lite for assistance.

 

 

 

 

E16

Inverter Fault

There are problems with the inverter circuit.

If the problem persists, contact Tripp Lite for assistance.

 

 

 

 

E18

DC-DC Fault

There are problems with the DC-DC

If the problem persists, contact Tripp Lite for assistance.

 

 

converter circuit.

 

 

 

 

 

Environmental fault

 

 

 

 

 

 

E21

O/P Short

UPS’s output is shorted.

Remove the cause of the short circuit from the

 

 

 

UPS’s output.

NOTE: UPS will attempt to go to bypass if the input voltage is within acceptable range.

Shutdown

 

 

 

 

 

 

 

Sd0

EPO shutdown

The UPS is shut down due to emergency

This is not an error but a shut down mode indicator.

 

 

power off triggered externally.

See EPO section for details.

 

 

 

 

Sd1

RPO shutdown

The UPS is shut down due to remote power

This is not an error but a shut down mode indicator.

 

 

off triggered externally.

See EPO section for details.

 

 

 

 

Sd2

“Shutdown

The UPS is shut down due to a pre-set

This is not an error but a shut down mode indicator.

 

After” Shutdown

software feature called “shutdown after”.

 

 

 

 

 

Sd3

“Battery Save”

The UPS is shut down due to a pre-set

This is not an error but a shut down mode indicator.

 

shutdown

software feature called “Battery Save”

 

 

 

 

 

Sd4

Battery low

The UPS is shut down due to low battery

This is not an error but a shut down mode indicator.

 

shutdown

voltage

Recharge the battery.

Internal Battery Replacement

Battery Replacement Door: Under normal conditions, the original battery in your UPS will last several years. Battery replacement

should be performed only by qualified service personnel. Refer to “Battery Warnings” in the Safety section. If you require a replacement

battery, you can find it at www.tripplite.com/support/battery/index.cfm. See the chart below to find the right replacement battery for your

UPS system:

UPS Model

 

Replacement Battery Cartridge

 

 

 

SU1000XLCD

 

RBC24V-LCD

 

 

 

SU1500XLCD

 

RBC48-SUTWR

 

 

 

SU2200XLCD

 

RBC48-SUTWR

 

 

 

SU3000XLCD

 

RBC96-3U

 

 

 

 