Operation
2The OUTPUT FREQUENCY selection screen will appear.
OUTPUT FREQUENCY refers to the
ACCEPT AND ADVANCE | VIEW ALTERNATE SETTINGS | LEAVE UPS SETUP MODE |
To ACCEPT the current value
&ADVANCE to the next configuration screen, press the ON/SELECT button (less than 1 second).
To VIEW ALTERNATE SETTINGS, press the SETUP BUTTON repeatedly (under 1 second each).
AVAILABLE VALUES 60Hz (factory), 50Hz
To leave UPS setup mode,
PRESS and HOLD the SETUP
BUTTON (about 3 seconds).
NOTE - the UPS must be in STANDBY MODE to change the output frequency setting
3The FREQUENCY CONVERTER selection screen will appear.
FREQUENCY CONVERTER refers to the ability of the UPS to convert 60Hz to 50Hz or 50Hz to 60Hz. The UPS system automatically selects 50 Hz or 60 Hz operation based on utility power conditions at
ACCEPT AND ADVANCE | VIEW ALTERNATE SETTINGS | LEAVE UPS SETUP MODE |
To ACCEPT the current value
&ADVANCE to the next configuration screen , press the ON/SELECT button (less than 1 second).
To VIEW ALTERNATE SETTINGS, press the SETUP BUTTON repeatedly (under 1 second each).
AVAILABLE VALUES
OFF(factory), ON
To leave UPS setup mode,
PRESS and HOLD the SETUP
BUTTON (about 3 seconds).
NOTE - the UPS must be in STANDBY MODE to change the frequency converter setting
4The BYPASS RANGE selection screen will appear.
BYPASS RANGE: Sets the allowable voltage deviation from nominal input voltage that is acceptable for the unit to go to bypass in a fault condition. If the voltage goes outside the range, the unit will not go to bypass. If the unit is already in bypass, it will turn the output off. The factory setting of WIDE is compatible with the vast majority of networking equipment. Regardless of the “plus or minus” value entered, the highest bypass voltage available is 135V. The lowest bypass voltage available is 90V (full load) and 70V (<70% load). The “Wide” range reflects these same values (full load 90 to 135V / <70% load 70 to 135V).
ACCEPT AND ADVANCE | VIEW ALTERNATE SETTINGS | LEAVE UPS SETUP MODE |
To ACCEPT the current value
&ADVANCE to the next configuration screen, press the ON/SELECT button (less than 1 second).
To VIEW ALTERNATE SETTINGS, press the SETUP BUTTON repeatedly (under 1 second each).
AVAILABLE VALUES
HI (factory), 5%, 6%, 7%, 8%, 9%, 10%, 11%, 12%, 13%, 14%, 15%
22
To leave UPS setup mode, PRESS and HOLD the SETUP BUTTON (about 3 seconds).
3/28/2013 1:05:38 PM |