Tripp Lite SU2200XLCD, SU1500XLCD, SU1000XLCD Basic Connection and Start-Up, EPO Port Connection

Models: SU3000XLCD SU2200XLCD SU1000XLCD SU1500XLCD

1 96
Download 96 pages 42.15 Kb
Page 14
Image 14
3EPO Port Connection

Basic Connection and Start-Up

3EPO Port Connection

This optional feature is only for those applications that require connection to a facility’s Emergency Power Off (EPO) circuit. When the UPS is connected to this circuit, it enables emergency shutdown of the UPS’s inverter and inhibits transfer to internal bypass. Using the cable provided, connect the EPO port of your UPS (see 3a ) to a user-supplied normally closed or normally open switch according to the circuit diagram (see 3b ).

Note:

1.If using a cable other than what is supplied, the cable should not exceed 350 feet or have a resistance of greater than 10 ohms.

2.If a non-latching EPO switch is used, the EPO must be held for a minimum of 1 second. This does not apply to a latching EPO switch.

CAUTION: The EPO port is not a phone line surge suppressor; do not connect a phone line to this port.

UPS Unit State when asserting EPO with AC line present:

Output

Fans

Serial

SNMP

USB

LCD Screen*

 

 

 

 

 

 

OFF

ON

ON

ON

ON

sdo

 

 

 

 

 

 

To restart the UPS unit after asserting EPO with AC line present:

Option 1:

1.Verify that the EPO assertion has been removed or cleared.

2.Press ON button until unit beeps, then release.

3.UPS output will turn back on after it completes diagnostics.

Option 2:

1.Verify that the EPO assertion has been removed or cleared.

2.Remove AC line power to the UPS unit, wait until the LCD is completely off.

3.Reapply AC line power. Now the UPS will start back up in normal operation mode.

UPS Unit State when asserting EPO without AC line power:

Output

Fans

Serial

SNMP

USB

LCD Screen*

 

 

 

 

 

 

OFF

OFF

OFF

OFF

OFF

sdo

 

 

 

 

 

 

To restart the UPS unit after asserting EPO without AC line present:

1.Verify that the EPO assertion has been removed or cleared.

2.Reapply AC line power to the UPS unit. Now the UPS will start back up in normal operation mode.

*”sdo” indicates emergency power off

Your model may differ.