1 Input Cord: This permanently attached power cord connects your UPS to a power outlet.
2 AC Receptacles (Varies by Model): These output receptacles provide connected equipment with pure sine-wave AC output during normal operation and battery power during blackouts and severe brownouts. Power provided at these outlets is filtered to protect connected equipment against damaging surges and line noise. The receptacles are divided into numbered load banks, as labeled on the unit. Using PowerAlert software and cabling, load banks one and two may be individually turned off and on from a remote location, allowing users to reset or reboot connected equipment.
3 Telephone or Telephone/Network Protection Jacks: These jacks protect your equipment against surges over a telephone line or telephone/network data line, depending on model. Connecting your equipment to these jacks is optional. Your UPS will work properly without this connection. Note: Not compatible with PoE (Power Over Ethernet) applications.
4 Communications Ports (USB or RS-232):These ports connect your UPS to any workstation or server. Use with Tripp Lite’s PowerAlert Software and included cables to enable your computer to automatically save open files and shut down equipment during a blackout. Also use PowerAlert Software to monitor a wide variety of AC line power and UPS operating conditions. Consult your PowerAlert Software manual or contact Tripp Lite Customer Support for more information. The 9-pinRS-232 port also supports dry-contact communications. See USB & RS-232 Serial Communications in the Optional Connections section for installation instructions.
5 EPO (Emergency Power Off) Port: Your UPS features an EPO port that may be used to connect the UPS to a contact closure switch to enable emergency inverter shutdown. See Basic Connection and Start-Upsection for details.
6 Accessory Slot: Remove the small cover panel from this slot to use optional accessories to remotely monitor and control your UPS. Visit www.tripplite.com to see a full list of accessories, including the SNMPWEBCARD for remote control and UPS monitoring, and other network management products.
7 Input Circuit Breaker: This resettable breaker prevents high input current from damaging the UPS or the attached load. If this breaker trips, verify your UPS load before resetting the breaker switch in.
8 External Battery Pack Connector (configuration varies by model): Your UPS supports the use of optional Tripp Lite external battery packs for additional runtime. An external battery pack is not provided. If you want to extend the runtime with an external battery pack, contact Tripp Lite Customer Support at 773.869.1234 for the appropriate Tripp Lite battery pack to connect. Refer to instructions available with the battery pack for complete information and safety warnings.
Note: The connector is protected by a cover plate held in place by two screws.
9 Ground Screw: Use this to connect any equipment that requires a chassis ground.
10 Output Circuit Breakers Switches (Select Models Only): These resettable circuit breakers protect your UPS from output overload. If one or both breakers trip, remove some of the load on the circuit(s) and allow the UPS to cool before pressing the breaker switch(es) in to reset.