Features

2ON button: This button offers five main functions depending on the state of the UPS when it is pressed: Power-on control, alarm-cancel, self test, setup mode control and dimming control.

POWER ON

Turns the UPS ON into ONLINE or ECONOMY mode when pressed as the UPS is in STANDBY mode

PRESS and HOLD the ON BUTTON until a BEEP is heard and RELEASE

The UPS display will flash ON for 30 seconds then automatically switches to report the last viewed information screen.

HOW? PRESS and HOLD the ON BUTTON until a BEEP is heard (about 3 seconds), then RELEASE

WHEN? The UPS must be in standby mode and the LCD screen reporting “OFF” for the POWER ON function to take effect.

COLD START

Turns the UPS ON into BATTERY MODE during a power failure for temporary AC output

PRESS and HOLD the ON BUTTON until a BEEP is heard and RELEASE

The UPS will turn on after about 30 seconds and momentarily report ON before switching to the last viewed informational screen

HOW? PRESS and HOLD the ON BUTTON until a BEEP is heard (about 3 seconds), then RELEASE

WHEN? The UPS must be completely OFF with the LCD screen UNLIT and have adequate battery charge for COLD START to take effect.

ALARM SILENCE

Temporarily sets the audible alarm to MUTE during a power failure. Alarm will sound again for future power failures

TAP the ON BUTTON during BATTERY MODE

The Alarm will be temporarily silenced, but will re-sound for the next alarm condition

HOW? TAP the ON BUTTON (less than 1 second)

WHEN? The UPS must be running in BATTERY MODE with the Alarm sounding for the ALARM SILENCE to take effect.

SELF TEST

Performs a momentary test of the UPS battery system and reports PASS / FAIL results.

PRESS and HOLD the ON BUTTON until a BEEP is heard and RELEASE

The LCD screen will flash TEST and BATTERY while reporting battery voltage for 10-15 seconds, then the screen will report the testing results using the three digit display:

PAS = PASS / BAD = FAIL

See the Troubleshooting section for more information

HOW? PRESS and HOLD the ON BUTTON until a BEEP is heard (about 3 seconds), then RELEASE

WHEN? The UPS must be running in ONLINE (shown above), ECONOMY, FREQUENCY REGULATION or FREQUENCY CONVERSION MODE for the SELF TEST to take effect.

NOTE: After first plugging in the unit, wait 24 hours before running the first self-test. The self-test will not run if battery voltage is too low.