Bryant 551J Factory-Option Thru-Base Connections, Units without Thru-Base Connections, Thermostat

Page 14

NOTICE

Convenience Outlet Utilization

Maximum Intermittent use : 15 Amps 2 to 3 Hours

Maximum Continuous use : 8 Amps 24/7

 

 

 

 

 

 

50HJ542739

3.0

 

 

 

 

 

 

 

 

 

 

 

A9225

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 20 - Convenience Outlet Utilization Notice Label

 

 

 

Duty Cycle: the unit-powered convenience outlet has a duty

 

 

 

cycle limitation. The transformer is intended to provide

 

 

 

power on an intermittent basis for service tools, lamps, etc; it

 

 

 

is not intended to provide 15-amps loading for continuous

 

 

 

duty loads (such as electric heaters for overnight use).

 

 

 

Observe a 50% limit on circuit loading above 8-amps.

551J

j

Convenience outlet usage rating:

 

 

 

Continuous usage: 8 amps maximum

 

 

 

 

 

 

Intermittent usage: up to 15 amps maximum for

 

 

 

 

 

up to 2 hours maximum

 

 

 

Test the GFCI receptacle by pressing the TEST button on

 

 

 

the face of the receptacle to trip and open the receptacle.

 

 

 

Check for proper grounding wires and power line phasing

 

 

 

if the GFCI receptacle does not trip as required. Press the

 

 

 

RESET button to clear the tripped condition.

 

 

 

 

 

 

Factory-Option Thru-Base Connections —

 

 

 

 

 

 

This service connection kit consists of a 1/2-in electrical

 

 

 

bulkhead connector and a 3/4-in electrical bulkhead

 

 

 

connector, all factory-installed in the embossed (raised)

 

 

 

section of the unit basepan in the condenser section. The

 

 

 

3/4-in bulkhead connector enables the low-voltage control

 

 

 

wires to pass through the basepan. The 1/2-in electrical

 

 

 

bulkhead connector allows the high-voltage power wires

 

 

 

to pass through the basepan. See Fig. 21.

 

 

 

LOW VOLTAGE

CONDUIT

CONNECTOR

HIGH VOLTAGE

CONDUIT

CONNECTOR

C08637

Fig. 21 - Thru-Base Connection Fittings

Check tightness of connector lock nuts before connecting electrical conduits.

Field-supplied and field-installed liquid tight conduit connectors and conduit may be attached to the connectors on the basepan. Pull correctly rated high voltage and low voltage through appropriate conduits. Connect the power conduit to the internal disconnect (if unit is so equipped) or to the external disconnect (through unit side panel). A

hole must be field cut in the main control box bottom on the left side so the 24-v control connections can be made. Connect the control power conduit to the unit control box at this hole.

Units without Thru-Base Connections —

1.Install power wiring conduit through side panel open- ings. Install conduit between disconnect and control box.

2.Install power lines to terminal connections as shown in Fig. 15.

Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate. See Table 4. On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in the legend for Table 5, Note 2 to determine the percent of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Bryant warranty.

Field Control Wiring —

The 551J unit requires an external temperature control device. This device can be a thermostat emulation device provided as part of a third-party Building Management System.

Thermostat —

Install a Bryant-approved accessory thermostat according to installation instructions included with the accessory. For complete economizer function, select a two-stage cooling thermostat. Locate the thermostat accessory on a solid wall in the conditioned space to sense average temperature in accordance with the thermostat installation instructions.

If the thermostat contains a logic circuit requiring 24-v power, use a thermostat cable or equivalent single leads of different colors with minimum of seven leads. If the thermostat does not require a 24-v source (no “C” connection required), use a thermostat cable or equivalent with minimum of six leads. Check the thermostat installation instructions for additional features which might require additional conductors in the cable.

Using unit-mounted convenience outlets: Units with unit-mounded convenience outlet circuits will often require that two disconnects be opened to de-energize all power to the unit. Treat all units as electrically energized until the convenience outlet power is also checked and de-energization is confirmed. Observe National Electrical Code Article 210, Branch Circuits, for use of convenience outlets.

For wire runs up to 50 ft. (15 m), use no. 18 AWG (American Wire Gage) insulated wire [35_C (95_F) minimum]. For 50 to 75 ft. (15 to 23 m), use no. 16 AWG insulated wire [35_C (95_F) minimum]. For over 75 ft. (23 m), use no. 14 AWG insulated wire [35_C (95_F) minimum]. All wire sizes larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.

14

Image 14
Contents Installation Instructions 551J Unit Dimensional Drawing C10058 Operating Weights Plan for Sequence of Unit InstallationCurb-mounted installation Plan for Unit LocationInspect unit Provide Unit SupportRoof Curb Details Field Fabricate Ductwork Rig and Place UnitPositioning on Curb Convert to Horizontal and Connect Ductwork when requiredInstall Outside Air Hood Indoor Coil Access Panel Relocation Make Electrical Connections Install External Condensate Trap and LineField Power Supply All units Convenience OutletsConvenience Outlet Location Installing Weatherproof Cover Units without Thru-Base Connections Field Control WiringFactory-Option Thru-Base Connections ThermostatHeater Model Number Heat Anticipator SettingsElectric Heaters Typical Component Location Smoke Detectors SystemController Smoke Detector Locations Typical Supply Air Smoke Detector Sensor LocationCompleting Installation of Return Air Smoke Sensor Return Air Detector Shipping PositionRTU-MP control system RTU-MP Multi-Protocol Control BoardRTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs Type of I/O Connection PIN Name Numbers InputsSpace Temperature SPT Sensors 55 Space Temperature Sensor WiringRTU-MP T-56 Sensor Connections SEN Communication Wiring Protocols General Connecting Discrete InputsPower Exhaust output Filter StatusLocal Access RTU-MP Troubleshooting Communication LEDsLEDs LEDs on the RTU-MP show the status of certain functionsUnit Wire/Fuse or Hacr Breaker Sizing Data FLA LRAPwrd C.O 27.8 132 42.0 47/47 Adjust Factory-Installed Options EconoMi$er IV Occupancy SwitchInstall Accessories Pre-Start and Start-Up