4.5.4 - Description of the Setpoints menu

SETPOINTS MENU [2]

ITEM

FORMAT

UNITS

RANGE

COMMENTS

0

±nn.n

°C

See table below

This item lets you display and modify Cooling setpoint 1*

1

±nn.n

°C

See table below

This item lets you display and modify Cooling setpoint 2*

2

nnn

°C

See table below

This item lets you display and modify Heating setpoint*, only displayed for heat pumps.

3 [1]

nnn

°C

See table below

This item lets you display and modify the condensing setpoint*. It is used by the control to regulate the fan

 

 

 

 

stages or a variable-speed fan (air-cooled units) or the condenser water valve control (water-cooled

 

 

 

 

units), if the unit is not in heat reclaim mode.

 

 

 

 

 

4 [1]

nnn

°C

See table below

This item lets you display and modify the heat reclaim setpoint*. As item 3, this is used for condensing

 

 

 

 

setpoint control.

 

 

 

 

 

5

nnn

%

0 to 100

Capacity limit setpoint. Limitation by volt-free contact. This item is used to define the maximum capacity

 

 

 

 

that the unit is authorised to use, if the capacity limit contact activate the limit. See section 5.8.

6 [1]

±nn.n

°C/min

0.1 to 1.1

Cooling ramp loading rate. This parameter is only accessible if the ramp function is validated in the User

 

 

 

 

Configuration 1 menu. This item refers to the maximum rate of temperature rise in °C in the water heat

 

 

 

 

exchanger in cooling mode. When capacity loading is effectively limited by the ramp, mode 11 is active.

7 [1]

±nn.n

°C/min

0.1 to 1.1

Heating ramp loading rate. This parameter is only accessible if the ramp function is validated in the User

 

 

 

 

Configuration 1 menu. This item refers to the maximum rate of temperature drop in °C in the water heat

 

 

 

 

exchanger in heating mode. When capacity loading is effectively limited by the ramp, mode 11 is active.

 

 

 

 

 

8 [1]

±nn.n

[3]

See table below

Zero reset threshold, cooling mode**

 

 

 

 

 

9 [1]

±nn.n

[3]

See table below

Full reset threshold, cooling mode**

 

 

 

 

 

10 [1]

±nn.n

°C

See table below

Full reset value, cooling mode**

 

 

 

 

 

11 [1]

±nn.n

[3]

See table below

Zero reset threshold, heating mode**

 

 

 

 

 

12 [1]

±nn.n

[3]

See table below

Full reset threshold, heating mode**

 

 

 

 

 

13 [1]

±nn.n

°C

-16 to 16

Full reset value, heating mode**

 

 

 

 

 

Legend

1This item is displayed in certain unit configurations only.

2All points contained in this table can be modified.

*Those setpoints can be used for entering or leaving water temperature control. By default the unit controls the evaporator entering fluid temperature. Leaving fluid temperature control requires a parameter modification in the Service Configuration menu.

**These parameters are only accessible when reset based on OAT or delta T has been selected in the User Configuration 1 menu. See section 4.5.7.3.

SETPOINT

DESCRIPTION

CONTROL FOR

CONTROL FOR

 

 

LEAVING WATER

ENTERING WATER

Cooling

Minimum setpoint

 

 

 

- Water

3.3°C

9.3°C

 

- Medium Brine

-10°C

-4°C

 

- Low Brine

-20°C

-14°C

 

Maximum setpoint

 

 

 

 

 

 

Heating

Maximum setpoint

MCT - 4.0

MCT - 10.0

 

 

 

 

Note:

Three setpoint reset configuration modes can be selected in the Client1 menu: 1 Reset using an external 0-10 V d.c. signal

2 Reset using Delta T

3 Reset by external temperature sensor (air-cooled units only)

The items with zero reset or maximum reset are based on these three modes.

17

Image 17
Contents 30GK Series PRO-DIALOG Control Installation, operation and maintenance instructionsTable of Contents Safety Considerations Diagnostics Troubleshooting Avoiding electrocution Safety ConsiderationsGeneral Abbreviations used General DescriptionGeneral Control board Hardware DescriptionElectronic boards Control boxRed LED Board addressesGreen LED Orange LED CCN/clock boardEvaporator leaving water temperature sensor Evaporator entering water temperature sensorCondenser entering and leaving water temperature sensors Heat reclaim condenser entering/leaving water temperaturesUser connections Description Connector Terminal ChannelAvailable Terminals RemarksLocal interface general features Setting UP PRO-DIALOG Plus ControlMain interface Main Interface Button Name DescriptionUnit start/stop control Stopping the unit in local modeDescription Starting unit and selecting an operating typeMenus Modifying the value of a parameter/access to a sub- menuSelecting a menu Selecting a menu itemStructure MenuStatus Menu treeInformation Menu Format Units Description Description of the Information menuTemperatures Menu Format Units Comments Description of the Temperatures menuDescription of the Pressures menu Pressures Menu Format Units CommentsSetpoints Menu Format Units Range Comments Description of the Setpoints menuDescription of the Outputs/Tests menu General Description of the Inputs menuMenu description Inputs Menu Format Units CommentsFormat Units Description Manual tests Description of the Configuration menu GeneralPassword SUB-MENU Holiday Configuration SUB-MENU Period ConfigurationUser 1 Configuration SUB-MENU Format Units Default Comments Description of the User 1 Configuration sub-menuDate & Time Configuration SUB-MENU Format Comments Description of the User 2 Configuration sub-menuDescription of Date and Time configuration sub Menu Description of the Holidays sub-menus Typical timer programDescription of the Broadcast sub-menu Item # Format CommentsDescription of the Alarms History menu Description of the Alarms menuBroadcast Configuration SUB-MENU Item # Format Comments Alarms Menu Item # Format DescriptionDescription of the Runtimes 1 menu Maintenance menu descriptionRuntime menu description Description of the Runtimes 2 menu PRO-DIALOG Plus Control Operation Chilss Contact Type Mode ShutdownStart/stop control Heating/cooling selectionCondenser water pump control Evaporator water pump control Control interlock contactEvaporator heater control Control pointDemand limit Demand limit by 0-10 V d.c. signalCapacity control Determining the lead circuitControlling the EXV Slave compressor start-up sequenceHead pressure control on air-cooled units Head pressure control on water-cooled unitsHigh pressure load shedding function Master/slave assemblyPumping down Controlling Pro-Dialog Plus units with a System ManagerDisplaying alarms Diagnostics TroubleshootingResetting alarms Optional heat reclaim moduleAlarm Code Descriptions Alarm codesCCN DGT only for units with low-temperature option Compressor faults 6.4.1.1 GeneralCompressor protection devices Starter Guard

30GK specifications

The Carrier 30GK is a prominent chiller model known for its efficiency and reliability in various commercial and industrial applications. Offering a blend of advanced technology and robust design, the 30GK series caters to diverse cooling needs while maintaining energy efficiency and low operational costs.

One of the standout features of the 30GK is its use of the latest scroll compressor technology. This contributes to its efficient performance, enabling the chiller to operate at optimal levels while minimizing energy consumption. The scroll compressor is known for its quiet operation, which reduces noise pollution, making it an ideal choice for buildings located in noise-sensitive environments.

The 30GK chiller series is equipped with microchannel coil technology, which allows for improved heat exchange efficiency. The microchannel design uses a compact coil structure that enhances refrigerant flow and reduces refrigerant volume, leading to a smaller footprint compared to traditional coil designs. This innovative design not only saves space but also improves the chiller's overall performance.

Another notable characteristic of the Carrier 30GK is its environmental consciousness. The chiller operates using environmentally friendly refrigerants, aligning with modern regulations and sustainability goals. Its design incorporates energy-efficient components that contribute to significant reductions in greenhouse gas emissions, making it suitable for environmentally responsible projects.

Moreover, the 30GK is designed for easy serviceability, with accessible components that simplify maintenance. This feature is particularly important for facility managers seeking to minimize downtime and keep maintenance costs low. The chiller also includes advanced monitoring and control systems, which enable real-time performance tracking and diagnostics, enhancing operational efficiency.

In terms of performance, the 30GK chiller is known for its wide capacity range, making it versatile for various applications. Whether for commercial spaces, industrial processes, or large buildings, the 30GK can meet the cooling demands reliably.

Overall, the Carrier 30GK chiller represents a perfect balance of cutting-edge technology, energy efficiency, and sustainability. Its features make it a leading choice in the market, suited for those looking to invest in high-quality and dependable cooling solutions.