Carrier 30GK manual Evaporator pumps, Condenser pump, Pressure sensors, Discharge pressure sensors

Page 8

3.3.3 - The evaporator pumps

The controller can regulate one or two evaporator pumps, with automatic changeover between the two pumps.

3.3.4 - The condenser pump

In appropriate cases the controller can regulate a condenser pump (for water-cooled units or air-cooled units with heat reclaim option). This control does not require an additional board.

3.3.5 - Pressure sensors

These are used to measure the following pressures in each circuit:

Discharge gas pressure (high pressure type)

Suction pressure (low pressure type)

Oil pressure (option)

These electronic sensors deliver 0 to 5 V d.c. to the main board or to a 4xAI-2xAO slave board. Two sensor versions are used; one is calibrated for high pressure and the other for low pressure and oil pressure.

Discharge pressure sensors

These are on the high pressure side of the lead compressor in each circuit. They replace the usual discharge gas pressure gauges and can be used to control head pressure or by the high pressure load shedding option.

Oil pressure sensors

If installed, these sensors are used to measure the compressor oil pressure on the oil pressure discharge side. The suction pressure is subtracted from the oil pressure value to arrive at the differential oil pressure.

Suction pressure sensors

They are located in the low-pressure side of the unit on the lead compressor of each circuit. The suction pressure sensor reading is used to control the electronic expansion devices EXV. They permit replacement of the low-pressure switches, low-pressure gauges and possibly of the oil pressure safety switch.

3.3.6 - Thermistors

These all have similar characteristics.

Evaporator entering water temperature sensor

The evaporator entering water temperature sensor is installed in the evaporator wall in the free space at the side of the tube bundle.

Evaporator leaving water temperature sensor

The evaporator leaving water temperature sensor is installed in evaporator leaving water piping: The sensor bulb is directly immersed in the water.

Compressor suction sensor

This is located in the lead compressor of each circuit in the suction gas line situated between the motor and the cylinders above the oil pump.

Condenser entering and leaving water temperature sensors

These are used to control the heating capacity on heat pumps. In cooling only units they have no control function. They are installed in the common condenser entering and leaving line.

Heat reclaim condenser entering/leaving water temperatures

These sensors measure the entering and leaving water tempera- tures of heat reclaim condensers and are used on air-cooled units equipped with the heat reclaim option. If not, they may be fitted as options. In this case they only have informative character.

Temperature setpoint reset sensor

This is an optional 0-10 V sensor which can be installed remotely from the unit. It is used to reset the cooling and heating setpoint on the unit as a function of either the outdoor air temperature or ambient room temperature. The sensor is not supplied by Carrier, and must be configured by the User Menu.

Outdoor temperature sensor

Mounted on the control box. It is used for start-up, setpoint temperature reset and frost protection control.

Master/slave assembly temperature control

The optional water temperature sensor can be used for master/ slave assembly control.

8

Image 8
Contents Installation, operation and maintenance instructions 30GK Series PRO-DIALOG ControlTable of Contents Safety Considerations Diagnostics Troubleshooting Avoiding electrocution Safety ConsiderationsGeneral General Description Abbreviations usedHardware Description General Control boardElectronic boards Control boxBoard addresses Red LEDGreen LED Orange LED CCN/clock boardEvaporator entering water temperature sensor Evaporator leaving water temperature sensorCondenser entering and leaving water temperature sensors Heat reclaim condenser entering/leaving water temperaturesDescription Connector Terminal Channel User connectionsAvailable Terminals RemarksSetting UP PRO-DIALOG Plus Control Local interface general featuresMain interface Main Interface Button Name DescriptionStopping the unit in local mode Unit start/stop controlDescription Starting unit and selecting an operating typeModifying the value of a parameter/access to a sub- menu MenusSelecting a menu Selecting a menu itemMenu StructureMenu tree StatusDescription of the Information menu Information Menu Format Units DescriptionDescription of the Temperatures menu Temperatures Menu Format Units CommentsDescription of the Pressures menu Pressures Menu Format Units CommentsDescription of the Setpoints menu Setpoints Menu Format Units Range CommentsDescription of the Inputs menu Description of the Outputs/Tests menu GeneralMenu description Inputs Menu Format Units CommentsFormat Units Description Manual tests Description of the Configuration menu GeneralPassword SUB-MENU Period Configuration SUB-MENU Holiday ConfigurationDescription of the User 1 Configuration sub-menu User 1 Configuration SUB-MENU Format Units Default CommentsDate & Time Configuration SUB-MENU Format Comments Description of the User 2 Configuration sub-menuDescription of Date and Time configuration sub Menu Typical timer program Description of the Holidays sub-menusDescription of the Broadcast sub-menu Item # Format CommentsDescription of the Alarms menu Description of the Alarms History menuBroadcast Configuration SUB-MENU Item # Format Comments Alarms Menu Item # Format DescriptionDescription of the Runtimes 1 menu Maintenance menu descriptionRuntime menu description Description of the Runtimes 2 menu Chilss Contact Type Mode Shutdown PRO-DIALOG Plus Control OperationStart/stop control Heating/cooling selectionEvaporator water pump control Control interlock contact Condenser water pump controlEvaporator heater control Control pointDemand limit by 0-10 V d.c. signal Demand limitCapacity control Determining the lead circuitSlave compressor start-up sequence Controlling the EXVHead pressure control on air-cooled units Head pressure control on water-cooled unitsMaster/slave assembly High pressure load shedding functionPumping down Controlling Pro-Dialog Plus units with a System ManagerDiagnostics Troubleshooting Displaying alarmsResetting alarms Optional heat reclaim moduleAlarm codes Alarm Code DescriptionsCCN Compressor faults 6.4.1.1 General DGT only for units with low-temperature optionCompressor protection devices Starter Guard

30GK specifications

The Carrier 30GK is a prominent chiller model known for its efficiency and reliability in various commercial and industrial applications. Offering a blend of advanced technology and robust design, the 30GK series caters to diverse cooling needs while maintaining energy efficiency and low operational costs.

One of the standout features of the 30GK is its use of the latest scroll compressor technology. This contributes to its efficient performance, enabling the chiller to operate at optimal levels while minimizing energy consumption. The scroll compressor is known for its quiet operation, which reduces noise pollution, making it an ideal choice for buildings located in noise-sensitive environments.

The 30GK chiller series is equipped with microchannel coil technology, which allows for improved heat exchange efficiency. The microchannel design uses a compact coil structure that enhances refrigerant flow and reduces refrigerant volume, leading to a smaller footprint compared to traditional coil designs. This innovative design not only saves space but also improves the chiller's overall performance.

Another notable characteristic of the Carrier 30GK is its environmental consciousness. The chiller operates using environmentally friendly refrigerants, aligning with modern regulations and sustainability goals. Its design incorporates energy-efficient components that contribute to significant reductions in greenhouse gas emissions, making it suitable for environmentally responsible projects.

Moreover, the 30GK is designed for easy serviceability, with accessible components that simplify maintenance. This feature is particularly important for facility managers seeking to minimize downtime and keep maintenance costs low. The chiller also includes advanced monitoring and control systems, which enable real-time performance tracking and diagnostics, enhancing operational efficiency.

In terms of performance, the 30GK chiller is known for its wide capacity range, making it versatile for various applications. Whether for commercial spaces, industrial processes, or large buildings, the 30GK can meet the cooling demands reliably.

Overall, the Carrier 30GK chiller represents a perfect balance of cutting-edge technology, energy efficiency, and sustainability. Its features make it a leading choice in the market, suited for those looking to invest in high-quality and dependable cooling solutions.